TRIPP-LITE S3MT-Series 3-Phase Input Isolation Transformers Owner’s Manual
- June 6, 2024
- Tripp Lite
Table of Contents
Owner’s Manual
S3MT-Series 3-Phase
Input Transformers:
480V-208V and 600V-208V
Models:
S3MT-60K480V, S3MT-100K480V, S3MT-60K600V, S3MT-100K600V
WARRANTY REGISTRATION
Register your product today and be automatically entered to win an ISOBAR®
surge protector in our monthly drawing!
tripplite.com/warranty
http://www.tripplite.com/warranty
Introduction
Tripp Lite’s S3MT-60K480V and S3MT-100K480V input isolation transformers
provide 480V (Delta) to 208V (Wye) stepdown and Isolation protection to the
connected UPS and its load. The S3MT-60K600V and S3MT-100K600V Input isolation
transformers provide 600V (Delta) to 208V (Wye) step-down and isolation
protection to the connected PS and its load.
The transformer has input isolation to mitigate utility line surges and
spikes, while protecting the UPS. The transformer includes a built-in breaker
at the transformer output side for protection. The ball-bearing fans maintain
quiet operation (four fans for 60K models, three large fans for 100K models).
An overheat-sensing relay and switch combine with a warning light to provide
over-temperature warning and overheating protection. The UPS system’s small
footprint and quiet acoustic profile enable installations with minimal space
and noise impact. All transformer models feature rugged stainless steel
housings with front panels similar to the S3M-Series 208V 3-Phase UPS line.
UPS Model | Series Number | Capacity | Description |
---|---|---|---|
S3MT-60K480V | AG-050D | 60kW | 480V to 208V Input Isolation Transformer |
S3MT-100K480V | AG-0510 | 100kW | 480V to 208V Input Isolation Transformer |
S3MT-60K600V | AG-050F | 60kW | 600V to 208V Input Isolation Transformer |
S3MT-100K600V | AG-050E | 100kW | 600V to 208V Input Isolation Transformer |
Typical applications
4-Wire (3Ph+N+PE) IT equipment loads in government, manufacturing, hospitals,
industrial settings, and corporate settings that have 480V or 600V electrical
mains and 208V/120V or 220V/127V IT Loads.
Key Features
- Isolation protection to the UPS input, with stepped-down input from 480V (Delta) to 208V/120V (Wye) or 600V (Delta) to 208V/120V (Wye)
- Circuit breaker and overheating protection
- 96.5% to 97.5% efficiency
- Wide input voltage and frequency operating range: Voltage: -20% to +25% @ 100% load and 40-70 Hz
- Insulation class: 180°C material
- Reliability-tested according to ISTA-3B for vibration, shock, drop (tip test)
- UL and CSA TUV certifications
- Rugged stainless steel housing shipped ready for installation
- 2-year warranty
Typical Configurations
These 480V Input Transformers may be purchased separately or as part of kit model with a Tripp Lite S3M Series 3-Phase UPS:
Input
Transformer Models
| Maximum Constant Load| Compatible with 208V 3Ph UPS| Kit
Models: UPS + Transformer
---|---|---|---
Kit Models| Kit Models Include
480V
|
S3MT-60K480V
|
60kW
|
50-60kW UPS
| S3M50K-60K4T| S3M50K UPS + S3MT-60K480V
S3M60K-60K4T| S3M60K UPS + S3MT-60K480V
S3MT-100K480V
|
100kW
|
80-100kW UPS
| S3M80K-100K4T| S3M80K UPS + S3MT-100K480V
S3M100K-100K4T| S3M100K UPS + S3MT-100K480V
600V
|
S3MT-60K600V
|
60kW
|
50-60kW UPS
| S3M50K-60K6T| S3M50K UPS + S3MT-60K600V
S3M60K-60K6T| S3M60K UPS + S3MT-60K600V
S3MT-100K600V
|
100kW
|
80-100kW UPS
| S3M80K-100K6T| S3M80K UPS + S3MT-100K600V
S3M100K-100K6T| S3M100K UPS + S3MT-100K600V
Important Safety Warnings
SAVE THESE INSTRUCTIONS
This manual contains important instructions for models S3MT-60K480V / S3MT-
100K480V / S3MT-60K600V / S3MT-100K600V that should be followed during the
installation and maintenance of the transformer and UPS.
**CAUTION! Risk of electrical shock! Hazardous live parts inside this
unit are energized from the transformer even when the breaker is turned off.
WARNING! The unit is intended for installation in a controlled
environment.
CAUTION!** A transformer can present a risk of electric shock and a high
short circuit current. The following precaution should be observed when
working on the transformer:
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
To reduce the risk of electric shock, disconnect the transformer and UPS from
the main supply before performing maintenance or service.
Servicing of the 3-phase transformer and UPS should be performed by Tripp Lite
certified personnel with knowledge of the 3-phase transformer and UPS and all
required precautions.
The transformer is extremely heavy. Caution should be taken in moving and
positioning equipment. The instructions contained within this manual are
important and should be closely followed at all times during installation and
follow-up maintenance of the 3-phase transformer and UPS.
CAUTION!
The transformer has a dangerous level of heat. If the transformer’s front-
panel red LED indicator is on, the unit’s outlets may have a dangerous level
of heat.
All servicing on this equipment must be carried out by Tripp Lite-certified
service personnel. Before conducting any maintenance, repair, or shipment,
first, ensure everything is turned off completely and disconnected.
Special Symbols – The following symbols are used on the transformer to
warn you of precautions:
** RISK OF ELECTRIC SHOCK – Observe the warning that risk of electric shock
is present.
CAUTION** – REFER TO THE OWNER’S MANUAL for information regarding important
operating and maintenance instructions.
SAFE GROUNDING TERMINAL – Indicates THE primary safe ground.
Installation
3.1 Mechanical Data
Physical Requirements
Leave space around the cabinet for operation and ventilation (Figure 3-1):
- Leave at least 23.6 in. (600 mm) space in the front for ventilation
- Leave at least 20 in. (500 mm) space at the right and left for operation
- Leave at least 20 in. (500 mm) space at the back for ventilation
3.2 Package Inspection
-
Don’t lean the transformer cabinet when removing it from the packaging.
-
Check the appearance to see if the transformer cabinet was damaged during transport. Do not power on the transformer
cabinet if any damage is found. Contact the dealer immediately. -
Check the accessories against the packing list and contact the dealer in case of missing parts.
3.3 Unpacking the UPS
-
Hold the sliding plate steady. Cut and remove the binding straps (Figure 3-2).
-
Remove the plastic bag and the outer carton (Figure 3-3).
-
Remove the foam packing material and the beveled pallet (Figure 3-4).
-
Remove the screws securing the cabinet to the pallet (Figure 3-5).
-
Lift the cabinet with a forklift and remove the packing pallets (Figure 3-6).
3.4 Package Contents
Contents| TL P/N| S3MT-60K480V| S3MT-60K600V| S3MT-
100K480V| S3MT-100K600V
---|---|---|---|---|---
Input Transformer| | 1| 1| 1| 1
Owner’s Manual| 933D05| 1| 1| 1| 1
Bottom Skirts| 103922A| 2| 2| 2| 2
Bottom Skirts| 103923A| 2| 2| 2| 2
Screws for Skirts| 3011C3| 24| 24| 24| 24
3.5 Cabinet Overview
- Over-Temperature Alarm LED
- Cooling Fans
- Breaker with Trip
- Cabling Terminals
- Bottom Entry Knockouts (for Power Cable Entry and Exit)
3.6 Power Cables
The cable design shall comply with the voltages and currents provided in this
section, and in accordance with local electrical codes.
WARNING!
UPON STARTUP, ENSURE YOU ARE AWARE OF THE LOCATION AND OPERATION OF THE
EXTERNAL ISOLATORS ARE CONNECTED TO THE UPS INPUT/BYPASS SUPPLY OF THE
UTILITY DISTRIBUTION PANEL. ENSURE THESE SUPPLIES ARE ELECTRICALLY
ISOLATED AND POST ANY NECESSARY WARNING SIGNS TO PREVENT INADVERTENT
OPERATION.
Cable Sizes
UPS Model
| Cable Sizes (THHW wiring at 75°C)
---|---
AC Input| AC Output| Neutral| Grounding| Lug
Gauge| Torque| Gauge| Torque| Gauge| Torque| Gauge| Torque|
S3MT- 60K480V| 50mm2 Max.
50mm2x2
| ****
25N•m
| 50mm2 Max.
50mm2x2
| ****
25N•m
| 70mm2x2 Max.
70mm2x2
| ****
25N•m
| 50mm2 Max.
50mm2x2
| ****
25N•m
| ****
M8
S3MT- 60K600V| 35mm2 Max.
50mm2x2
| ****
25N•m
| 50mm2 Max.
50mm2x2
| ****
25N•m
| 70mm2x2 Max.
70mm2x2
| ****
25N•m
| 50mm2 Max.
50mm2x2
| ****
25N•m
| ****
M8
S3MT- 100K480V| 70mm2x2 Max.
120mm2x2
| ****
50N•m
| 70mm2x2 Max.
95mm2x2
| ****
50N•m
| 120mm2x2 Max.
120mm2x2
| ****
50N•m
| 95mm2 Max. 120mm2| ****
50N•m
| ****
M10
S3MT- 100K600V| 50mm2 Max.
70mm2x2
| ****
50N•m
| 70mm2x2 Max.
95mm2x2
| ****
50N•m
| 120mm2x2 Max.
120mm2x2
| ****
50N•m
| 95mm2 Max. 120mm2| ****
50N•m
| ****
M10
3.7 Transformer-to-UPS Connection Line Diagram
Connections are shown below for the cabinet with a built-in input isolator
transformer, breakers and the red over-temperature LED.
3.8 Multiple Transformer Connections
WARNING: The transformer output neutral is not bonded to chassis ground.
Please provide a means to connect the transformer chassis ground to the
transformer output neutral.
Note: The transformer chassis ground must be connected to earth ground.
IMPORTANT: You may view and/or download this manual from the tripplite.com
website to view the cable connections in colors.
3.8.1 Connections for S3MT-60K480V/S3MT-60K600V to S3M50K or S3M60K UPS
Transfomer input is Delta 3-Wire (3Ph + Ground) And transformer output is Wye
4-Wire (3Ph + N + Ground).
3.8.2 Connections for S3MT-100K480V/S3MT-100K600V to S3M80K or S3M100K
UPS
Transfomer input is Delta 3-Wire (3Ph + Ground) And transformer output is Wye
4-Wire (3Ph + N + Ground).
Operation
WARNING: It is not advised to connect two UPS in parallel when using individual transformers for each UPS.
4.1 Over-Temperature Protection
4.1.1 Over-Temperature Red Warning LED Light
The transformer includes a warning LED light on the top portion of the front
panel. The light turns ON when the transformer reaches a temperature of 160°C
±5°C, i.e. a range of 155°C to 165°C (311°F to 329°F). The light turns OFF
when the transformer cools to a temperature of 125°C ±5°C, i.e. a range of
120°C to 130°C (248°F to 266°F).
4.1.2 Over-Temperature Protection Relay and Thermal Switch
The transformer includes an over-temperature protection relay and thermal
switch to protect the transformer from overheating. At temperatures of 160°C
±5°C, i.e. a range of 155°C to 165°C (311°F to 329°F), an over-temperature
protection relay and the thermal switch will activate and will open the output
breaker of the transformer. Once the transformer temperature has cooled down
and the warning LED light has turned OFF, you may manually re-activate (close)
the output breaker to restart normal operation.
Specifications
Models| S3MT-60K480V| S3MT-60K600V| S3MT-100K480V|
S3MT-100K600V
---|---|---|---|---
Description
| 3-Phase 60k Input Isolation Transformer, Delta 480V/208V Wye| 3-Phase 60k
Input Isolation Transformer, Delta 600V/208V Wye| 3-Phase 100k Input Isolation
Transformer, Delta 480V/208V Wye| 3-Phase 100k Input Isolation Transformer,
Delta 600V/208V Wye
Transformer Type| Dry-Type
Input
Input Voltage| 480V| 600V| 480V| 600V
Input Voltage Operational Range and De-Rating| -45%, +25% at 40 % Load
-20%, +25% at 100 % Load
Input Amps| 101A| 81A| 168A| 134A
Input Connections| 3-Wire (L1, L2, L3, +PE)
Input Configuration| Delta
Input Connection Type| Copper Bar
Rated AC Input Frequency| 50/60 Hz
Frequency Range and Derating| 40~70 Hz
Voltage Selection| No
Voltage Drop: Ratio Ouput, No Load to Full Load| ≤ 3%
Inrush Current| ≤900A (10 ms)| ≤710A (10 ms)| ≤3330A (10 ms)| ≤1160A (10 ms)
Input Isolation| Yes
Output| |
VA Rating| 60kVA| 60kVA| 100kVA| 100kVA
Transformer Output Voltage| 208/120V, (3-Phase, 4-Wire)
Output Amps| 225A| 374A
Transformer Output Breaker Rating| 250A| 250A| 400A| 400A
Output Watts Detailed| 60,000W| 60,000W| 100,000W| 100,000W
Output Connections| 4-Wire (L1, L2, L3, +PE, +N)
Output Connection Type| Copper Bar
Output Configuration| Wye
Input Tranformer Output Isolation| Yes
Operation
Over-Temperature Warning LED (Red)| Turns ON at 160°C ±5°C, i.e. a range of
155°C to 165°C ( 311°F to 329°F) Turns OFF at 125°C ±5°C, i.e. a range of
120°C to 130°C (248°F to 266°F)
Over-Temperature Protection Reset Device
| Transformer output turns OFF at temperatures of 160°C ±5°C, i.e. a range of 155°C to 165°C (311°F to 329°F).
The transformer output breaker can be turned ON manually when the warning light turns OFF.
Insulation Class| 180°C
Temperature Rise| 125°C
Full Load Efficiency| 96.50%| 96.70%
Models| S3MT-60K480V| S3MT-60K600V| S3MT-100K480V|
S3MT-100K600V
---|---|---|---|---
Half Load Efficiency| 97.50%| 97.70%
Physical Info
Unit Height| 47.2 in. (1200 mm)
Unit Width| 23.6 in. (600 mm)
Unit Depth| 33.5 in. (850 mm)
Unit Weight| 789 lb. (358 kg)| 789 lb. (358 kg)| 1078 lb. (489 kg)| 1049 lb.
(476 kg)
Floor Loading| 702 (kg/m²)| 702 (kg/m²)| 959 (kg/m²)| 933 (kg/m²)
Unit Carton Height| 55.4 in. (1407 mm)
Unit Carton Width| 29.9 in. (760 mm)
Unit Carton Depth| 38.8 in. (985 mm)
Unit Carton Weight| 855 lb. (388 kg)| 899 lb. (408 kg)| 1202 lb. (545 kg)|
1102 lb. (500 kg)
Tip-n-Tell Label Included on Overpack Box| Yes
Environment
Audible Noise at 1 m| 65 dB max.
RH Humidity, Non-Condensing| 95%
Online Thermal Dissipation, Full Load (BTU/hr)| 7167| 7167| 11263| 11263
Storage Temperature| 5°F to 140°F (-15°C to 60°C)
Operating Temperature| 32°F to 104°F (0°C to 40°C)
Operating Elevation| <1000 m for nominal power (over 1000 m, the power de-
rating is 1% per 100 m)
Mechanical
Transformer Windings| Aluminum
Cabinet Material| Cold Rolled Galvanized Steel (SGCC)
Cabinet Color| RAL 9011
Fan (Type/Quantity)| 60K Models: 4x Ball Bearing, 120 mm (576 total CFM) 100K
Models: 3x Ball Bearing, 172 x 152 mm (723 total CFM)
Reliability
Vibration| ISTA – 3B
Shock| ISTA – 3B
Drop| ISTA – 3B (Tip Test)
Agency Approvals
Approving Agency| cTUVs
Agency Standard Tested| UL 1778 5th Edition
Canadian Approvals| CSA 22.2-107.3-14
CE Approvals| N/A
EMI Approvals| N/A
RoHS/REACH| Yes
Storage
Before storing the isolation transformer, ensure all connections have been
disconnected and all breakers are turned OFF. Replace all input or output
access covers to avoid damaging any contacts.
The transformer must be stored in a clean, secure environment with
temperatures between 5°F to 140°F (-15°C to 60°C) and relative humidity less
than 90% (non-condensing).
Store the transformer in its original shipping container, if possible.
WARNING: The transformer(s) is/are very heavy. Before storing the transformer, make sure to take into account the floor loading (kg/m²) requirements listed in section 5. Specifications under “Physical Info” to store safely.
Warranty and Regulatory Compliance
Limited Warranty
Seller warrants this product, if used in accordance with all applicable
instructions, to be free from original defects in material and workmanship for
a period of 2 years from the date of initial purchase. If the product should
prove defective in material or workmanship within that period, Seller will
repair or replace the product, in its sole discretion. Service under this
Warranty includes parts only. International customers should contact Tripp
Lite support at intlservice@tripplite.com.
Continental USA customers should contact Tripp Lite Customer Service at
773-869-1234 or visit
tripplite.com/support/help
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM
ACCIDENT, MISUSE, ABUSE, OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER
THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED
BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES OF
MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET
FORTH ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND
CONSEQUENTIAL DAMAGES. (Some states do not allow limitations on how long an
implied warranty lasts, and some states do not allow the exclusion or
limitation of incidental or consequential damages, so the above limitations or
exclusions may not apply to you. This Warranty gives you specific legal
rights, and you may have other rights, which vary from jurisdiction to
jurisdiction.) Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; USA
WARNING: The individual user should take care to determine prior to use
whether this device is suitable, adequate, or safe for the use intended. Since
individual applications are subject to great variation, the manufacturer makes
no representation or warranty as to the suitability or fitness of these
devices for any specific application.
Product Registration
Visit tripplite.com/warranty today to
register your new Tripp Lite product. You will be automatically entered into a
drawing for a chance to win a FREE Tripp Lite product!*
- No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
WEEE Compliance Information for Tripp Lite Customers and Recyclers
(European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and
implementing regulations, when customers buy new electrical and electronic
equipment from Tripp Lite they are entitled to:
- Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
- Send the new equipment back for recycling when this ultimately becomes waste
Use of this equipment in life support applications where failure of this
equipment can reasonably be expected to cause the failure of the life support
equipment or to significantly affect its safety or effectiveness is not
recommended.
Tripp Lite has a policy of continuous improvement. Specifications are subject
to change without notice. Photos and illustrations may differ slightly from
actual products.
1111 W. 35th Street, Chicago, IL 60609 USA
•tripplite.com/support
20-08-282 93-3D05_RevA
Documents / Resources
|
TRIPP-LITE S3MT-Series 3-Phase Input Isolation