TRIPP-LITE S3MT-Series 3-Phase Input Isolation Transformers Owner’s Manual

June 6, 2024
Tripp Lite

Owner’s Manual
S3MT-Series 3-Phase
Input Transformers:
480V-208V and 600V-208V
Models:
S3MT-60K480V, S3MT-100K480V, S3MT-60K600V, S3MT-100K600V

WARRANTY REGISTRATION
Register your product today and be automatically entered to win an ISOBAR® surge protector in our monthly drawing!
tripplite.com/warranty

http://www.tripplite.com/warranty

Introduction

Tripp Lite’s S3MT-60K480V and S3MT-100K480V input isolation transformers provide 480V (Delta) to 208V (Wye) stepdown and Isolation protection to the connected UPS and its load. The S3MT-60K600V and S3MT-100K600V Input isolation transformers provide 600V (Delta) to 208V (Wye) step-down and isolation protection to the connected  PS and its load.
The transformer has input isolation to mitigate utility line surges and spikes, while protecting the UPS. The transformer includes a built-in breaker at the transformer output side for protection. The ball-bearing fans maintain quiet operation (four fans for 60K models, three large fans for 100K models). An overheat-sensing relay and switch combine with a warning light to provide over-temperature warning and overheating protection. The UPS system’s small footprint and quiet acoustic profile enable installations with minimal space and noise impact. All transformer models feature rugged stainless steel housings with front panels similar to the S3M-Series 208V 3-Phase UPS line.

UPS Model Series Number Capacity Description
S3MT-60K480V AG-050D 60kW 480V to 208V Input Isolation Transformer
S3MT-100K480V AG-0510 100kW 480V to 208V Input Isolation Transformer
S3MT-60K600V AG-050F 60kW 600V to 208V Input Isolation Transformer
S3MT-100K600V AG-050E 100kW 600V to 208V Input Isolation Transformer

Typical applications
4-Wire (3Ph+N+PE) IT equipment loads in government, manufacturing, hospitals, industrial settings, and corporate settings that have 480V or 600V electrical mains and 208V/120V or 220V/127V IT Loads.

Key Features

  • Isolation protection to the UPS input, with stepped-down input from 480V (Delta) to 208V/120V (Wye) or 600V (Delta) to 208V/120V (Wye)
  • Circuit breaker and overheating protection
  • 96.5% to 97.5% efficiency
  • Wide input voltage and frequency operating range: Voltage: -20% to +25% @ 100% load and 40-70 Hz
  • Insulation class: 180°C material
  • Reliability-tested according to ISTA-3B for vibration, shock, drop (tip test)
  • UL and CSA TUV certifications
  • Rugged stainless steel housing shipped ready for installation
  • 2-year warranty

Typical Configurations

These 480V Input Transformers may be purchased separately or as part of kit model with a Tripp Lite S3M Series 3-Phase UPS:

Input

Transformer Models

| Maximum Constant Load| Compatible with 208V 3Ph UPS| Kit Models: UPS + Transformer
---|---|---|---
Kit Models| Kit Models Include

480V

|

S3MT-60K480V

|

60kW

|

50-60kW UPS

| S3M50K-60K4T| S3M50K UPS + S3MT-60K480V
S3M60K-60K4T| S3M60K UPS + S3MT-60K480V

S3MT-100K480V

|

100kW

|

80-100kW UPS

| S3M80K-100K4T| S3M80K UPS + S3MT-100K480V
S3M100K-100K4T| S3M100K UPS + S3MT-100K480V

600V

|

S3MT-60K600V

|

60kW

|

50-60kW UPS

| S3M50K-60K6T| S3M50K UPS + S3MT-60K600V
S3M60K-60K6T| S3M60K UPS + S3MT-60K600V

S3MT-100K600V

|

100kW

|

80-100kW UPS

| S3M80K-100K6T| S3M80K UPS + S3MT-100K600V
S3M100K-100K6T| S3M100K UPS + S3MT-100K600V

Important Safety Warnings

SAVE THESE INSTRUCTIONS
This manual contains important instructions for models S3MT-60K480V / S3MT- 100K480V / S3MT-60K600V / S3MT-100K600V that should be followed during the installation and maintenance of the transformer and UPS.

**CAUTION! Risk of electrical shock! Hazardous live parts inside this unit are energized from the transformer even when the breaker is turned off.
WARNING! The unit is intended for installation in a controlled environment.
CAUTION!** A transformer can present a risk of electric shock and a high short circuit current. The following precaution should be observed when working on the transformer:
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
To reduce the risk of electric shock, disconnect the transformer and UPS from the main supply before performing maintenance or service.
Servicing of the 3-phase transformer and UPS should be performed by Tripp Lite certified personnel with knowledge of the 3-phase transformer and UPS and all required precautions.
The transformer is extremely heavy. Caution should be taken in moving and positioning equipment. The instructions contained within this manual are important and should be closely followed at all times during installation and follow-up maintenance of the 3-phase transformer and UPS.

CAUTION!
The transformer has a dangerous level of heat. If the transformer’s front- panel red LED indicator is on, the unit’s outlets may have a dangerous level of heat.
All servicing on this equipment must be carried out by Tripp Lite-certified service personnel. Before conducting any maintenance, repair, or shipment, first, ensure everything is turned off completely and disconnected.

Special Symbols – The following symbols are used on the transformer to warn you of precautions:
** RISK OF ELECTRIC SHOCK – Observe the warning that risk of electric shock is present.
CAUTION** – REFER TO THE OWNER’S MANUAL for information regarding important operating and maintenance instructions.
SAFE GROUNDING TERMINAL – Indicates THE primary safe ground.

Installation

3.1 Mechanical Data

Physical Requirements
Leave space around the cabinet for operation and ventilation (Figure 3-1):

  1. Leave at least 23.6 in. (600 mm) space in the front for ventilation
  2. Leave at least 20 in. (500 mm) space at the right and left for operation
  3. Leave at least 20 in. (500 mm) space at the back for ventilation

3.2 Package Inspection

  1. Don’t lean the transformer cabinet when removing it from the packaging.

  2. Check the appearance to see if the transformer cabinet was damaged during transport. Do not power on the transformer
    cabinet if any damage is found. Contact the dealer immediately.

  3. Check the accessories against the packing list and contact the dealer in case of missing parts.

3.3 Unpacking the UPS

  1. Hold the sliding plate steady. Cut and remove the binding straps (Figure 3-2).

  2. Remove the plastic bag and the outer carton (Figure 3-3).

  3. Remove the foam packing material and the beveled pallet (Figure 3-4).

  4. Remove the screws securing the cabinet to the pallet (Figure 3-5).

  5. Lift the cabinet with a forklift and remove the packing pallets (Figure 3-6).

3.4 Package Contents

Contents| TL P/N| S3MT-60K480V| S3MT-60K600V| S3MT- 100K480V| S3MT-100K600V
---|---|---|---|---|---
Input Transformer| | 1| 1| 1| 1
Owner’s Manual| 933D05| 1| 1| 1| 1
Bottom Skirts| 103922A| 2| 2| 2| 2
Bottom Skirts| 103923A| 2| 2| 2| 2
Screws for Skirts| 3011C3| 24| 24| 24| 24

3.5 Cabinet Overview

  1. Over-Temperature Alarm LED
  2. Cooling Fans
  3. Breaker with Trip
  4. Cabling Terminals
  5. Bottom Entry Knockouts (for Power Cable Entry and Exit)

3.6 Power Cables
The cable design shall comply with the voltages and currents provided in this section, and in accordance with local electrical codes.

WARNING!
UPON STARTUP, ENSURE YOU ARE AWARE OF THE LOCATION AND OPERATION OF THE EXTERNAL ISOLATORS ARE CONNECTED TO THE UPS INPUT/BYPASS SUPPLY OF THE UTILITY DISTRIBUTION PANEL. ENSURE THESE SUPPLIES ARE ELECTRICALLY ISOLATED AND POST ANY NECESSARY WARNING SIGNS TO PREVENT INADVERTENT OPERATION.

Cable Sizes



UPS Model

| Cable Sizes (THHW wiring at 75°C)
---|---
AC Input| AC Output| Neutral| Grounding| Lug
Gauge| Torque| Gauge| Torque| Gauge| Torque| Gauge| Torque|
S3MT- 60K480V| 50mm2 Max.

50mm2x2

| ****

25N•m

| 50mm2 Max.

50mm2x2

| ****

25N•m

| 70mm2x2 Max.

70mm2x2

| ****

25N•m

| 50mm2 Max.

50mm2x2

| ****

25N•m

| ****

M8

S3MT- 60K600V| 35mm2 Max.

50mm2x2

| ****

25N•m

| 50mm2 Max.

50mm2x2

| ****

25N•m

| 70mm2x2 Max.

70mm2x2

| ****

25N•m

| 50mm2 Max.

50mm2x2

| ****

25N•m

| ****

M8

S3MT- 100K480V| 70mm2x2 Max.

120mm2x2

| ****

50N•m

| 70mm2x2 Max.

95mm2x2

| ****

50N•m

| 120mm2x2 Max.

120mm2x2

| ****

50N•m

| 95mm2 Max. 120mm2| ****

50N•m

| ****

M10

S3MT- 100K600V| 50mm2 Max.

70mm2x2

| ****

50N•m

| 70mm2x2 Max.

95mm2x2

| ****

50N•m

| 120mm2x2 Max.

120mm2x2

| ****

50N•m

| 95mm2 Max. 120mm2| ****

50N•m

| ****

M10

3.7 Transformer-to-UPS Connection Line Diagram
Connections are shown below for the cabinet with a built-in input isolator transformer, breakers and the red over-temperature LED.

3.8 Multiple Transformer Connections

WARNING: The transformer output neutral is not bonded to chassis ground. Please provide a means to connect the transformer chassis ground to the transformer output neutral.
Note: The transformer chassis ground must be connected to earth ground.
IMPORTANT: You may view and/or download this manual from the tripplite.com website to view the cable connections in colors.

3.8.1 Connections for S3MT-60K480V/S3MT-60K600V to S3M50K or S3M60K UPS
Transfomer input is Delta 3-Wire (3Ph + Ground) And transformer output is Wye 4-Wire (3Ph + N + Ground).

3.8.2 Connections for S3MT-100K480V/S3MT-100K600V to S3M80K or S3M100K UPS
Transfomer input is Delta 3-Wire (3Ph + Ground) And transformer output is Wye 4-Wire (3Ph + N + Ground).

Operation

WARNING: It is not advised to connect two UPS in parallel when using individual transformers for each UPS.

4.1 Over-Temperature Protection
4.1.1 Over-Temperature Red Warning LED Light
The transformer includes a warning LED light on the top portion of the front panel. The light turns ON when the transformer reaches a temperature of 160°C ±5°C, i.e. a range of 155°C to 165°C (311°F to 329°F). The light turns OFF when the transformer cools to a temperature of 125°C ±5°C, i.e. a range of 120°C to 130°C (248°F to 266°F).
4.1.2 Over-Temperature Protection Relay and Thermal Switch
The transformer includes an over-temperature protection relay and thermal switch to protect the transformer from overheating. At temperatures of 160°C ±5°C, i.e. a range of 155°C to 165°C (311°F to 329°F), an over-temperature protection relay and the thermal switch will activate and will open the output breaker of the transformer. Once the transformer temperature has cooled down and the warning LED light has turned OFF, you may manually re-activate (close) the output breaker to restart normal operation.

Specifications

Models| S3MT-60K480V| S3MT-60K600V| S3MT-100K480V| S3MT-100K600V
---|---|---|---|---

Description

| 3-Phase 60k Input Isolation Transformer, Delta 480V/208V Wye| 3-Phase 60k Input Isolation Transformer, Delta 600V/208V Wye| 3-Phase 100k Input Isolation Transformer, Delta 480V/208V Wye| 3-Phase 100k Input Isolation Transformer, Delta 600V/208V Wye
Transformer Type| Dry-Type
Input
Input Voltage| 480V| 600V| 480V| 600V
Input Voltage Operational Range and De-Rating| -45%, +25% at 40 % Load

-20%, +25% at 100 % Load

Input Amps| 101A| 81A| 168A| 134A
Input Connections| 3-Wire (L1, L2, L3, +PE)
Input Configuration| Delta
Input Connection Type| Copper Bar
Rated AC Input Frequency| 50/60 Hz
Frequency Range and Derating| 40~70 Hz
Voltage Selection| No
Voltage Drop: Ratio Ouput, No Load to Full Load| ≤ 3%
Inrush Current| ≤900A (10 ms)| ≤710A (10 ms)| ≤3330A (10 ms)| ≤1160A (10 ms)
Input Isolation| Yes
Output| |
VA Rating| 60kVA| 60kVA| 100kVA| 100kVA
Transformer Output Voltage| 208/120V, (3-Phase, 4-Wire)
Output Amps| 225A| 374A
Transformer Output Breaker Rating| 250A| 250A| 400A| 400A
Output Watts Detailed| 60,000W| 60,000W| 100,000W| 100,000W
Output Connections| 4-Wire (L1, L2, L3, +PE, +N)
Output Connection Type| Copper Bar
Output Configuration| Wye
Input Tranformer Output Isolation| Yes
Operation
Over-Temperature Warning LED (Red)| Turns ON at 160°C ±5°C, i.e. a range of 155°C to 165°C ( 311°F to 329°F) Turns OFF at 125°C ±5°C, i.e. a range of 120°C to 130°C (248°F to 266°F)

Over-Temperature Protection Reset Device

| Transformer output turns OFF at temperatures of 160°C ±5°C, i.e. a range of 155°C to 165°C (311°F to 329°F).

The transformer output breaker can be turned ON manually when the warning light turns OFF.

Insulation Class| 180°C
Temperature Rise| 125°C
Full Load Efficiency| 96.50%| 96.70%
Models| S3MT-60K480V| S3MT-60K600V| S3MT-100K480V| S3MT-100K600V
---|---|---|---|---
Half Load Efficiency| 97.50%| 97.70%
Physical Info
Unit Height| 47.2 in. (1200 mm)
Unit Width| 23.6 in. (600 mm)
Unit Depth| 33.5 in. (850 mm)
Unit Weight| 789 lb. (358 kg)| 789 lb. (358 kg)| 1078 lb. (489 kg)| 1049 lb. (476 kg)
Floor Loading| 702 (kg/m²)| 702 (kg/m²)| 959 (kg/m²)| 933 (kg/m²)
Unit Carton Height| 55.4 in. (1407 mm)
Unit Carton Width| 29.9 in. (760 mm)
Unit Carton Depth| 38.8 in. (985 mm)
Unit Carton Weight| 855 lb. (388 kg)| 899 lb. (408 kg)| 1202 lb. (545 kg)| 1102 lb. (500 kg)
Tip-n-Tell Label Included on Overpack Box| Yes
Environment
Audible Noise at 1 m| 65 dB max.
RH Humidity, Non-Condensing| 95%
Online Thermal Dissipation, Full Load (BTU/hr)| 7167| 7167| 11263| 11263
Storage Temperature| 5°F to 140°F (-15°C to 60°C)
Operating Temperature| 32°F to 104°F (0°C to 40°C)
Operating Elevation| <1000 m for nominal power (over 1000 m, the power de- rating is 1% per 100 m)
Mechanical
Transformer Windings| Aluminum
Cabinet Material| Cold Rolled Galvanized Steel (SGCC)
Cabinet Color| RAL 9011
Fan (Type/Quantity)| 60K Models: 4x Ball Bearing, 120 mm (576 total CFM) 100K Models: 3x Ball Bearing, 172 x 152 mm (723 total CFM)
Reliability
Vibration| ISTA – 3B
Shock| ISTA – 3B
Drop| ISTA – 3B (Tip Test)
Agency Approvals
Approving Agency| cTUVs
Agency Standard Tested| UL 1778 5th Edition
Canadian Approvals| CSA 22.2-107.3-14
CE Approvals| N/A
EMI Approvals| N/A
RoHS/REACH| Yes

Storage

Before storing the isolation transformer, ensure all connections have been disconnected and all breakers are turned OFF. Replace all input or output access covers to avoid damaging any contacts.
The transformer must be stored in a clean, secure environment with temperatures between 5°F to 140°F (-15°C to 60°C) and relative humidity less than 90% (non-condensing).
Store the transformer in its original shipping container, if possible.

WARNING: The transformer(s) is/are very heavy. Before storing the transformer, make sure to take into account the floor loading (kg/m²) requirements listed in section 5. Specifications under “Physical Info” to store safely.

Warranty and Regulatory Compliance

Limited Warranty
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship for a period of 2 years from the date of initial purchase. If the product should prove defective in material or workmanship within that period, Seller will repair or replace the product, in its sole discretion. Service under this Warranty includes parts only. International customers should contact Tripp Lite support at intlservice@tripplite.com. Continental USA customers should contact Tripp Lite Customer Service at 773-869-1234 or visit tripplite.com/support/help
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE, ABUSE, OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET FORTH ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES. (Some states do not allow limitations on how long an implied warranty lasts, and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights, and you may have other rights, which vary from jurisdiction to jurisdiction.) Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; USA
WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate, or safe for the use intended. Since individual applications are subject to great variation, the manufacturer makes no representation or warranty as to the suitability or fitness of these devices for any specific application.

Product Registration
Visit tripplite.com/warranty today to register your new Tripp Lite product. You will be automatically entered into a drawing for a chance to win a FREE Tripp Lite product!*

  • No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.

WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new electrical and electronic equipment from Tripp Lite they are entitled to:

  • Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
  • Send the new equipment back for recycling when this ultimately becomes waste

Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended.
Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Photos and illustrations may differ slightly from actual products.

1111 W. 35th Street, Chicago, IL 60609 USA •tripplite.com/support
20-08-282 93-3D05_RevA

Documents / Resources

| TRIPP-LITE S3MT-Series 3-Phase Input Isolation Transformers [pdf] Owner's Manual
S3MT-60K480V, S3MT-100K480V, S3MT-60K600V, S3MT-100K600V, S3MT-Series 3-Phase Input Isolation Transformers, S3MT-Series, 3-Phase Input Isolation Transformers
---|---