MOXA MGate 5105-MB-EIP Series EtherNet/IP Gateways
Overview
The MGate 5105-MB-EIP is an industrial Ethernet gateway for Modbus
RTU/ASCII/TCP and EtherNet/IP network communications.
Package Checklist
Before installing the MGate 5105-MB-EIP, verify that the package contains the
following items:
-
1 MGate 5105-MB-EIP gateway
-
1 serial cable: CBL-RJ45F9-150
-
Quick installation guide (printed)
-
Warranty card
-
Please notify your sales representative if any of the above items are missing or damaged.
Optional Accessories (can be purchased separately) CBL-F9M9-150: DB9 female to DB9 male serial cable, 150 cm -
CBL-F9M9-20: DB9 female to DB9 male serial cable, 20 cm
-
CBL-RJ45SF9-150: RJ45 to DB9 female serial shielded cable, 150 cm
-
ADP-RJ458P-DB9F: DB9 female to RJ45 connector
-
A-ADP-RJ458P-DB9F-ABC01: DB9 female to RJ45 connector
-
Mini DB9F-to-TB: DB9 female to terminal block connector
Hardware Introduction
LED Indicators
LED | Color | Description |
---|
Ready
| Off| Power is off or a fault condition exists
Green
| Steady: Power is on, and the MGate is functioning
normally
Blinking: The MGate has been located by the
MGate Manager’s Location function
Red
| Steady: Power is on, and the MGate is booting up
Blinking slowly: Indicates an IP conflict, or the DHCP or BOOTP server is not
responding properly
Flashing quickly: microSD card failed
EIP
(Scanner)
| Off| No I/O data is exchanged
Green
| Steady: I/O data is exchanged with all devices
Blinking: I/O data is exchanged with at least one
device (not all configured devices can communicate with gateway)
EIP
(Adapter)
| Off| No I/O data is exchanged
Green
| Steady: I/O data is exchanged with all devices
Blinking: I/O data is exchanged with at least one device (not all configured
devices can
communicate with gateway)
MB
| Off| No communication with Modbus device
Green| Modbus communication in progress
Red
| Communication error
When MGate 5105 acts as Master:
1. Slave device returned an error (exception)
2. Received frame error (parity error, checksum error)
3. Timeout (slave device no response)
When MGate 5105 acts as Slave:
1. Received invalid function code
2. Master accessed invalid register address or coil addresses
3. Received frame error (parity error, checksum
error)
Dimensions
Reset Button
Restore the MGate to factory default settings by using a pointed object (such as a straightened paper clip) to hold the reset button down until the Ready LED stops blinking (approx. five seconds).
Remove the MGate 5105-MB-EIP’s top cover and you will find DIP switches to adjust each serial port’s pull-high resistor, pull-low resistor, and terminator.
SW
| 1| 2| 3
---|---|---|---
Pull-high
resistor
| Pull-low
resistor
| Terminator
ON| 1 kΩ| 1 kΩ| 120 Ω
OFF| 150 kΩ| 150 kΩ| –*
Hardware Installation Procedure
- Connect the power adapter. Connect the 12-48 VDC power line or DIN-rail power supply to the MGate 5105-MB-EIP device’s terminal block.
- Use a Modbus serial cable to connect the MGate to a Modbus slave device.
- Use an Ethernet cable to connect the MGate to the EtherNet/IP controller.
- The MGate 5105-MB-EIP is designed to be attached to a DIN rail or mounted on a wall. For DIN-rail mounting, push down the spring and properly attach it to the DIN rail until it “snaps” into place. For wall mounting, install the wall-mount kit (optional) first and then screw the device onto the wall. The following figure illustrates the two mounting options:
Software Installation Information
Please download the user’s manual and Device Search Utility (DSU) from Moxa’s
website: www.moxa.com
Refer to the user’s manual for additional details on using the DSU. The MGate
5105-MB-EIP also supports login via a web browser.
Default IP address: 192.168.127.254
Default account: admin
Default password: moxa
Pin Assignments Modbus Serial Port (Male DB9)
Power Input and Relay Output Pinouts
|
V2+
| ****
V2-
| |
V1+
| ****
V1-
---|---|---|---|---|---
Shielded Ground| DC
Power Input 2
| DC
Power Input 2
| ****
N.O.
| ****
Common
| ****
N.C.
| DC
Power Input 1
| DC
Power Input 1
Specifications
|
V2+
| ****
V2-
| |
V1+
| ****
V1-
---|---|---|---|---|---
Shielded Ground| DC
Power Input 2
| DC
Power Input 2
| ****
N.O.
| ****
Common
| ****
N.C.
| DC
Power Input 1
| DC
Power Input 1
- DEMKO Certification number: 13 ATEX 1307610X IEC Certification Number: IECEx UL 13.0051X;
- Ambient Temperature Range: 0°C to 60°C (for models without the suffix –T)- 40°C to 75°C (for models with suffix –T only)
- Certification String: Ex nA nC IIC T3 Gc
- Standards Covered: EN 60079-0:2013+A11/IEC 60079-0 6th Ed. AND EN 60079-15:2010/IEC 60079-15 4th Ed.
- The conditions of safe usage:
- The Ethernet Communications Devices are intended for mounting in a tool-accessible IP54 enclosure and used in an area of not more than pollution degree 2 as defined by IEC/EN 60664-1.
- Conductors suitable for use in an ambient temperature greater than 86°C must be used for the power supply terminal.
- A 4mm2 conductor must be used when a connection to the external grounding screw is utilized.
- Provisions shall be made, either in the equipment or external to the equipment, to prevent the peak-rated voltage being exceeded by transient disturbances of more than 140% of the peak-rated voltage. Terminal block (plug matched with socket): rated at 300 V, 15 A, 105°C, 12-28 AWG (0.0804 mm2 to 3.31 mm2) wire size, torque value 4.5 lb-in (0.509 N-m). The input terminal cable size: 14 AWG (2.1 mm²).
ATTENTION
For installations in hazardous locations (Class 1, Division 2): These devices
are to be installed in an enclosure with a tool-removable cover or door,
suitable for the environment
.NOTE This equipment is suitable for use in Class 1, Division 2, Groups
A,B, C, D or nonhazardous locations only.
WARNING EXPLOSION HAZARD
Do not disconnect the equipment unless the power has been switched off, or the
area is known to be nonhazardous.
WARNING EXPLOSION HAZARD
The substitution of any components may impair suitability for Class 1,
Division 2.
WARNING
EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE SEALING PROPERTIES OF MATERIALS
USED IN THE FOLLOWING DEVICE: Sealed Relay Device U21.
Moxa Inc. No. 1111, Heping Rd., Bade Dist., Taoyuan City 334004, Taiwan