AquaCal T030 Heat Pump Installation Guide
- July 28, 2024
- AquaCal
Table of Contents
T030 Heat Pump
Product Information
Model: T030
Manufacturer: AquaCal AutoPilot, Inc.
Website: www.AquaCal.com
Phone: (1) 727-823-5642
Hours: 8-5 pm, Eastern M-F
Specifications
-
Dimensions: Refer to user manual section 2.5
for detailed dimensions -
Weight: Refer to user manual section 2.7 for
weight information -
Operating Hours: 8-5 pm, Eastern time, Monday
to Friday -
Power Requirements: Refer to user manual
section 1.3.A for electrical requirements
Product Usage Instructions
Safety Precautions
Before operating the heat pump, ensure to read the safety
instructions provided in the manual carefully. Here are some key
safety precautions:
-
Follow all safety instructions displayed on the equipment and
within the manual. -
Repairs and services must be carried out by authorized service
centers to avoid voiding warranties. -
High voltage and rotating equipment are utilized; exercise
caution during servicing. -
Adhere to National Electric Codes (NEC) and local
guidelines. -
Refrigerant circuit repairs should only be handled by qualified
HVAC technicians. -
Maintain proper water chemistry as per the product’s operation
manual to prevent health hazards.
Installation
1.1 Positioning Equipment
Follow the guidelines in section 1.1 of the manual for correct
positioning of the heat pump.
1.2 Plumbing
Refer to sections 1.2.A to 1.2.F for plumbing requirements,
diagrams, and water flow rates.
FAQ
Q: What should I do if I encounter a fault code on the heat
pump display?
A: If a fault code appears, refer to section
3.1 of the manual for a list of fault codes and their resolutions.
If the issue persists, contact AquaCal for further assistance.
AquaCal® Installation Manual
Dial Display
T030
Important Read this document before operating / installing this product For
additional product manuals and operation / installation procedures, please
visit www.AquaCal.com
LTM0139 REL A- (project rel 8.00)
Table of Contents
Contacting AquaCal AutoPilot, Inc.
1
Safety
1
1 – Installation
3
1.1 Positioning Equipment
3
1.2 Plumbing
5
1.2.A Plumbing Requirements
5
1.2.B Plumbing Diagrams
5
1.2.C Maintaining Ability to Winterize
8
1.2.D Water Connections to Heat Pump
8
1.2.E In-Line Chlorine Feeders
9
1.2.F Water Flow Rates
9
1.3 Electrical
10
1.3.A Electrical Requirements
10
1.3.B Incoming Power Access Holes
12
1.3.C Access Panels
12
1.3.D Verifying Transformer Setting (Select Units)
12
1.3.E Schematic Location
13
1.4 Connecting an External Controller (Optional)
13
1.4.A PoolSync®
13
1.4.B 2-WIRE Controllers (Pool-Spa)
14
2 – Appendix
15
2.1 Adjusting Water Flow Using T (Delta-T)
15
2.2 Adjusting Water Pressure Switch (Select Units)
16
2.3 Clearances
18
2.4 Cleaning Equipment After Installation
18
2.5 Dimensions
20
2.6 Identifying Model Specifications
20
2.7 Weights
20
2.8 Initial Heating Recommendations
21
2.9 Winterizing
21
2.10 Available Accessories
22
3 – Troubleshooting
23
3.1 Fault Codes
24
3.2 Issues and Resolutions
26
i
Contacting AquaCal AutoPilot, Inc.
For further assistance, please contact the distributor or installer of this product.
If unavailable, please contact AquaCal® for a partner in your area. To better assist you, please have the heat pump model and serial number available.
Product Information:
Website www.AquaCal.com
Phone
(1) 727-823-5642
Hours
8-5 pm, Eastern M-F
Website
Service Information: www.AquaCal.com/request-heat-pump-service/
SAFETY
l For personal safety, and to avoid damage to equipment, follow all safety
instructions displayed on the equipment and within this manual. Repair and
service of heat pump must be performed by an authorized service center.
l Warranties may be voided if the equipment has been improperly installed,
maintained or serviced.
l If service is deemed necessary, please contact AquaCal.
SAFETY SIGNALS
Throughout this document, safety signals have been placed where particular attention is required.
DANGER
Failure to heed the following will result in injury or death.
WARNING
Failure to heed the following may result in injury or death.
NOTICE
Failure to heed the following may result in damage to equipment.
When installing and using your heat pump basic safety precautions must always be followed, including the following:
DANGER
Failure to heed the following will result in injury or death.
l The heat pump utilizes high voltage and rotating equipment. Use caution when servicing. l Follow all National Electric Codes (NEC) and / or State and Local guidelines.
Page – 1
WARNING
Failure to heed the following may result in injury or death.
l Repairs must be performed by a qualified technician.
l The heat pump contains refrigerant under pressure. Repairs to the
refrigerant circuit must not be attempted by untrained and / or unqualified
individuals. Service must be performed only by qualified HVAC technicians.
Recover refrigerant before opening the system.
l Improper water chemistry can present a serious health hazard. To avoid
possible hazards, maintain pool / spa water per standards as detailed in the
product’s operation manual.
l Prolonged immersion in water warmer than normal body temperature may cause a
condition known as Hyperthermia. The symptoms of Hyperthermia include
unawareness of impending hazard, failure to perceive heat, failure to
recognize the need to exit the pool or spa, and unconsciousness. The use of
alcohol, drugs, or medication can greatly increase the risk of fatal
Hyperthermia. People having an adverse medical history, or pregnant women
should consult a physician before using a hot tub or spa. Children and the
elderly should be supervised by a responsible adult.
l This appliance is not to be used by persons (including children) with
reduced physical, sensory, or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction.
l Children must be supervised and are not to play with the appliance.
NOTICE
Failure to heed the following may result in damage to equipment.
l Maintain proper water chemistry to avoid damage to the pump, filter, pool
shell, etc.
l Water flow exceeding the maximum flow rate requires a bypass. Damage due to
excessive water flow will void the warranty.
l Failure to protect equipment against corrosive conditions will adversely
affect the life of the equipment and will void equipment warranty.
SAVE THESE INSTRUCTIONS
Page – 2
1 – Installation
DANGER
Failure to heed the following will result in injury or death.
l Deactivate power while routing wiring to control board. l Units supplied
with a wired plug must use a (GFCI) rated outlet. Please note, the power cord
for this unit is 6.5
feet (198 cm) long. l Follow all National Electric Codes (NEC) and/or State
and Local guidelines.
WARNING
Failure to heed the following may result in injury or death.
l Installation of this equipment by anyone other than a qualified installer
can result in a safety hazard.
l The information contained throughout the “Installation” section is intended
for use by qualified installation technicians familiar with the swimming
Pool/Spa safety standards.
NOTICE
Failure to heed the following may result in damage to equipment.
l Failure to protect equipment against corrosive conditions will adversely
affect the life of the equipment and will void equipment warranty.
l Do not install equipment inside of a building.
IN THIS SECTION:
1.1 Positioning Equipment
3
1.2 Plumbing
5
1.3 Electrical
10
1.4 Connecting an External Controller (Optional)
13
1.1 Positioning Equipment
NOTICE
Failure to heed the following may result in damage to equipment.
l Do not install equipment inside of a building.
Outdoor Use Only Do not install equipment inside of a room or building.
l Heat Pumps require unobstructed airflow for proper operation. Heat Pumps
should never be installed indoors or in a location where airflow is
restricted.
l If an indoor installation is being considered, the installer and dealer are
strongly urged to contact the AquaCal Application Department, or a local
Professional Engineer prior to proceeding.
l See “Clearances” on page 18.
Controlling Irrigation and Rainwater Runoff
l Irrigation water may damage heat pump components. Direct irrigation water
away from the heat pump.
l The heat pump will withstand normal rainfall. Do not allow a roof slope to
direct rainwater onto the heat pump. Have a gutter installed on the roof edge
to direct this water away from the heat pump. Or install the heat pump in
another location.
1 – Installation
Page – 3
1 – Installation
Planning for Condensation The heat pump can produce a large amount of
condensation. The amount of water depends on air temperature and humidity.
l Install the heat pump with enough height to allow for water drainage.
Mounting Pad Requirements
l The heat pump’s base must be installed on a flat and level surface that
completely supports the entire base. l Build the heat pump pad out of concrete
or other code-approved material. l Confirm the pad can support the weight of
the heat pump. l Elevate the pad enough to allow for drainage. l Make sure the
pad is flat and level. l Have the pad support the entire heat pump base in all
directions. l Do not install the heat pump on soil or grass. l Do not allow
the heat pump base to touch the building’s foundation. l Do not place the heat
pump directly on a concrete floor. This can cause noise to be transmitted to
an occupied
space. If necessary install vibration dampers between the heat pump base and
floor. l Equipment pad must meet all requirements of authorities having code-
related jurisdiction.
Anchoring to Pad
l Follow all applicable local, state, and national requirements regarding wind
load anchoring. l The shipping brackets used to secure the heat pump to the
pallet are approved mounting (hurricane) brackets.
They should be used to anchor the heat pump to the pad. l If needed, contact
AquaCal® to obtain anchoring kit information. Please have the heat pump model
number and
serial number when requesting support.
Page – 4
1 – Installation
1.2 Plumbing 1.2.A Plumbing Requirements
l The heat pump must receive water flow under worst-case conditions such as a
fouled water filter. l Failure to provide clean filtered water to the heat
pump can void the product warranty. l Water flow exceeding maximum flow rates
will negatively affect the total pool filtration performance and may
damage the heat pump. This will not be covered under the equipment warranty.
See “Water Flow Rates” on page 9.
l Install a bypass valve whenever water-flow may exceed the maximum rating. l
See “Available Accessories” on page 22. l For additional guidance testing
water flow rates, please contact AquaCal®.
1.2.B Plumbing Diagrams Plumbing diagrams are provided in this section as a
planning guide to the sequence of equipment, valves, and fittings.
l The basic plumbing configurations for typical installations are shown. l If
the installation does not closely follow any of the supplied plumbing
diagrams, AquaCal® Technical Support
is available for installation advice and guidance. l Confirm water provided to
the heat pump is clean and filtered. Heat Pump with water flows equal or less
than the maximum listed flow rate
Page – 5
1 – Installation
Heat Pump with water flows greater than the maximum listed flow rate Heat Pump
with Spillover Spa (One filter Pump) Heat Pump with Spillover Spa (Two filter
Pumps)
Page – 6
1 – Installation
Heat Pump with Solar Panels in Plumbing Circuit Heat Pump with Gas Heater
backup Multiple Air Source Heat Pumps
Page – 7
1.2.C Maintaining Ability to Winterize
Do not use glue on the threaded portion of the equipment’s unions. A glued-in-
place union will prevent the equipment from being properly winterized. 1.2.D
Water Connections to Heat Pump
l Heat Pump union sizes are specified on diagrams. l Connections to site
plumbing are made via PVC solvent cement to the female slip socket of the
plumbing
unions. l Plumbing unions are available from AquaCal®.
NOTICE
Failure to heed the following may result in damage to equipment.
l Do not use glue on the threaded portion of the equipment’s unions. A glued- in-place union will prevent the equipment from being properly winterized.
TropiCal® T030
1 – Installation
Page – 8
1.2.E In-Line Chlorine Feeders
Place in-line chlorinators downstream from the heat pump and as low in
elevation as possible.
l If an erosion type feeder is used, it is recommended that a Hartford Loop be
installed to protect internal heat pump components.
l A Hartford Loop is not required when using a Salt Chlorine Generator. l
Avoid storing corrosive chemicals near the heat pump to minimize potential
damage to the exterior of the heat
pump.
Heat Pump with Erosion Tablet Feeder and Hartford Loop
1 – Installation
1.2.F Water Flow Rates
Maintain water flow rates as indicated. Please note, these specifications
relate to the heat pump only. Codespecified whole system turnover rates must
be satisfied.
NOTICE
Failure to heed the following may result in damage to equipment.
l Water flow exceeding maximum flow rates will negatively affect the total pool filtration performance and may damage the heat pump. This will not be covered under the equipment warranty.
MODEL HEAT EXCHANGER TYPE
T030
Titanium ThermoLink®
FLOW RATES
MINIMUM
MAXIMUM
20 GPM (75.7 L/min) 45 GPM (170 L/min)
- Head Loss – 30 GPM = 1.5 PSI, 70 GPM = 8.2 PSI
PLEASE NOTE –
If minimum flow rates are not met, heat pump performance is reduced and
performance will suffer. Internal safety devices may deactivate the heat pump
with the following errors:
l Operate water filtration devices per manufacturer’s specifications. Dirty
filters can cause a reduction of water flow to the heat pump. An increase of
7-10 psi (48 to 69 kPa) higher than the clean filter pressure typically
reduces flow rates. This requires the filter to be cleaned or back-washed.
l Keep baskets free of debris. A large quantity of debris in the pump and
skimmer baskets can reduce water flow.
l Check for improper valve settings. A partially closed valve after the
filter, or a full-open bypass around the heat pump, will cause insufficient
water flow through the heat pump.
l The maximum static pressure (or operating pressure) is 50 psi (345 kPa).
These specifications relate to the heat pump only.
l Code-specified whole system turnover rates must be satisfied.
Page – 9
1.3 Electrical
DANGER
Failure to heed the following will result in injury or death.
l Deactivate power while routing wiring to control board. l Units supplied
with a wired plug must use a (GFCI) rated outlet. Please note, the power cord
for this unit is 6.5
feet (198 cm) long. l Follow all National Electric Codes (NEC) and/or State
and Local guidelines.
WARNING
Failure to heed the following may result in injury or death.
l The information contained in this section is intended for use by qualified
electricians familiar with electrical service-industry safety standards and
methods.
l Locate the equipment disconnect as near to the heat pump as possible. Always
satisfy applicable codes and standards.
l Never mount power-disconnects directly to the heat pump. l In sizing power
wiring, be especially aware of up-sizing requirements necessary due to wiring
distances. Always
satisfy applicable codes and standards.
l AquaCal® heat pumps are designed to use copper conductors, only. Do not use
aluminum wire.
l Units supplied with a wired power plug must use a (GFCI) rated outlet.
1.3.A Electrical Requirements Standards
Standards NFPA 70, Nat’l Elec. Code 2017
IEC 60335-1
IEC 60335-2
UL 1995 & CSA C22.2 No. 236-15 Table 1 – Standards
Title The electrical installation must conform to the current version of the
National Electric Code (NEC), and all applicable local and state codes
Household and similar electrical appliances – Safety General Requirements
Household and similar electrical appliances – Safety Particular requirements
for electrical heat pumps, airconditioners, and dehumidifiers
Standard for Safety – Heating and cooling equipment
Grounding and Bonding Follow local code requirements for proper grounding and
bonding of heat pump equipment.
l A bonding lug has been provided on the heat pump.
1 – Installation
Page – 10
Surge Suppression The use of approved commercial surge protectors is strongly
recommended.
Ground Fault Circuit Interrupt (GFCI) Breaker The use of a GFCI breaker is
required for units supplied with wired power plugs.
Sizing the Electrical Service Refer to equipment data plate for specific
information required to size electrical service and over-current protection of
the heat pump. Sizing is based on data plate information, wire size, wiring
devices, and overcurrent protection per applicable local codes and standards.
Minimum and Maximum Operating Voltage The heat pump must operate within
specified voltages.
NOTICE
Failure to heed the following may result in damage to equipment.
l Operating equipment under higher or lower voltage conditions may result in damage to your compressor, motors or other electrical components. This damage will not be covered by the product warranty.
1. Measure site voltage. The site voltage MUST be measured under “FULL LOAD”
conditions. Activate all equipment using the same electrical panel as the heat
pump.
2. If measured site voltage is outside listed ranges, immediately deactivate
equipment until site conditions have been corrected. If unsure of heat pump
equipment rating, please
Equipment Rating
J Voltage (110 to 120 Volts) Single Phase 60 hertz
Minimum Maximum Site Voltage Site Voltage
104 Volts 132 Volts
1 – Installation
Page – 11
1.3.B Incoming Power Access Holes 1.3.C Access Panels
DANGER
Failure to heed the following will result in injury or death.
l Deactivate power while routing wiring to control board. l Units supplied
with a wired plug must use a (GFCI) rated outlet. Please note, the power cord
for this unit is 6.5
feet (198 cm) long. l Follow all National Electric Codes (NEC) and/or State
and Local guidelines.
1 – Installation
1.3.D Verifying Transformer Setting (Select Units)
Transformer voltage must be confirmed and set correctly depending on the
measured voltage found on the site. Incorrect settings may cause heat pump
damage. The following procedure will allow the installer to set the heat
pump’s transformer for the appropriate site voltage.
DANGER
Failure to heed the following will result in injury or death.
l Deactivate power while routing wiring to control board. l Units supplied
with a wired plug must use a (GFCI) rated outlet. Please note, the power cord
for this unit is 6.5
feet (198 cm) long. l Follow all National Electric Codes (NEC) and/or State
and Local guidelines.
WARNING
Failure to heed the following may result in injury or death.
l The information contained in this section is intended for use by qualified technicians, familiar with electrical service-industry safety standards and methods.
Page – 12
1. Turn heat pump on by adjusting the thermostat to call for heating. If more
than one heat pump is on-site, turn them all on. Allow time for all heat pump
compressors to activate.
2. Measure the running site voltage.
3. Confirm transformer tap is set for the measured site voltage. If more than
one voltage tap is shown, select the voltage nearest to the running site
voltage.
Example of heat pump
transformer (Varies between models)
PLEASE NOTE –
l If more than one voltage is shown on the equipment’s data plate, the factory
default setting is usually the higher voltage on the transformer.
l As an example, a “208/230” voltage will be set to “240” from the factory.
1.3.E Schematic Location
Schematics are located on the inside of the electrical panel.
1.4 Connecting an External Controller (Optional)
To support a direct connection to an external controller, AquaCal® heat pumps
are equipped with removable terminal blocks on the control board. The control
board is located on the low-voltage side of the
electrical enclosure.
IN THIS SECTION:
1.4.A PoolSync®
13
1.4.B 2-WIRE Controllers (Pool-Spa)
14
1.4.A PoolSync®
Select heat pumps will automatically allow for WI-FI capabilities using a
PoolSync®.
l The PoolSync® device will allow direct control of the heat pump from a
mobile device.
l Contact installing dealer to order this product. See “PoolSync® WI-FI
Controller (ECP0343)” on page 23.
l Go online and download the PoolSync® manual for information on connecting
and using this device with an AquaCal heat pump.
https://www.aquacal.com/ownersmanuals/
1 – Installation
Page – 13
1.4.B 2-WIRE Controllers (Pool-Spa)
NOTICE
Failure to heed the following may result in damage to equipment.
l Confirm equipment connected to heat pump before selecting this option . All existing configurations will be cleared.
1. Deactivate power to heat pump.
2. Remove the heat pump electrical access panel.
3. Route 22-gauge (minimum), 2-conductor, shielded, outdoor rated wires from
the controller to the low voltage side of the heat pump’s electrical
enclosure. Follow all National Electric Codes (NEC) unless State or Local
guidelines supersede.
4. Connect the controller wires to the control board port labeled “2WIRE”
with the terminals labeled “Y” and “Z” as follows. See Figure 1.
l Connect one wire to “Y”.
l Connect other wire to “Z”.
l The polarity of the wire is not important.
5. Connect the 2-WIRE Enable Jumper.
6. Reattach heat pump access panel.
7. Apply power to heat pump.
8. Set the dial on the control panel to 104° F. This will allow the external
control (2wire) device to operate the heat pump.
Figure 1
1 – Installation
Page – 14
2 – Appendix
IN THIS SECTION:
2.1 Adjusting Water Flow Using T (Delta-T)
15
2.2 Adjusting Water Pressure Switch (Select Units)
16
2.3 Clearances
18
2.4 Cleaning Equipment After Installation
18
2.5 Dimensions
20
2.6 Identifying Model Specifications
20
2.7 Weights
20
2.8 Initial Heating Recommendations
21
2.9 Winterizing
21
2.10 Available Accessories
22
2.1 Adjusting Water Flow Using T (Delta-T)
The Delta-T is the temperature difference between the water temperatures
entering and leaving the heat pump. The equipment can be fine-tuned for
maximum performance by balancing water flow rates to maintain an ideal T. The
adjustment procedure must be completed with the unit in heating mode
1. Adjust the thermostat to its lowest setting with the unit in heating mode.
2. Deactivate the water filtration pump. 3. Confirm that the filters leading
to the heat pump are clean. 4. Adjust the valves controlling water headed
towards the heat pump to the half-open position. 5. Adjust the valves
controlling water leading away from the heat pump to a fully open position. 6.
Activate the pool water filtration pump. 7. Slowly raise the thermostat
temperature until the heat pump activates.
l After a four-minute delay, the heat pump’s compressor will start.
8. With the heat pump running, confirm the filtration pump is operating
properly with adequate flow and no short cycling.
9. Wait for water temperatures to stabilize (approximately 5 minutes). 10.
Adjust valves in the following order using the temperature chart provided.
a. Adjust the valve that controls water exiting the heat pump until the
correct temperature differential is achieved. Match the temperature measured
with a temperature probe to the chart.
b. Wait for water temperatures to stabilize. Then check the temperature again.
Re-adjust the valve as needed.
11. Mark valves at these positions for future reference.
HEAT EXCHANGER TYPE
Titanium ThermoLink®
MODEL T030
Table 2 – Temperature Chart
TEMPERATURE
1° to 4° F (.5° C to 2.2° C)
2 – Appendix
Page – 15
PLEASE NOTE –
l Temperature differences are based on pool water temperatures of 69° to 75°
F. (20.5° to 23.8° C)
l For water temperatures outside this range, contact AquaCal®. See “Contacting
AquaCal AutoPilot, Inc.” on page 1.
2.2 Adjusting Water Pressure Switch (Select Units)
Adjust the water pressure switch when heat pump attempts to operate without
water flow.
Before attempting any adjustments confirm the following :
l The filter is clean. l Filter pump is operating. l The valves are set to
direct the appropriate amount of water through the
heat pump. See “Water Flow Rates”.
DANGER
Failure to heed the following will result in injury or death.
l Deactivate power while routing wiring to control board. l Units supplied
with a wired plug must use a (GFCI) rated outlet. Please note, the power cord
for this unit is 6.5
feet (198 cm) long. l Follow all National Electric Codes (NEC) and/or State
and Local guidelines.
WARNING
Failure to heed the following may result in injury or death.
l Water Pressure Switch adjustment procedure to be performed by experienced service personnel only; procedure must not be attempted by individuals lacking adequate electrical and mechanical experience.
NOTICE
Failure to heed the following may result in damage to equipment.
l If the heat pump continues to operate after a water pressure switch
adjustment, deactivate equipment and perform additional troubleshooting.
1. Remove heat pump access panel.
2. Locate the water pressure switch. It will be outside and along the bottom
edge of the electrical enclosure. The exact location varies by model.
3. Activate the filter pump.
4. Apply power to heat pump.
5. Slowly rotate the adjustment wheel on the switch. Keep turning the wheel
until the heat pump indicates it is receiving water.
6. Deactivate filter pump. If correctly adjusted, the heat pump will
deactivate and the display will show “”.
7. Re-install heat pump access panel.
2 – Appendix
Page – 16
2 – Appendix
8. If the heat pump continues to operate without water flow, the installation
of a grid flow switch may be required.
l This can become necessary if the heat pump is installed below the elevation
of the body of water to be heated. The standing pressure from the water can
cause the water pressure switch to activate when the circulation pump is off.
Therefore a water flow switch must be used in place of a water pressure switch
to determine if incoming water is being sent to the heat pump. See “Grid Flow
Switch (# 0040S)” on page 22.
9. If the heat pump continues to operate without water flow, contact
AquaCal®.
Page – 17
2.3 Clearances
l Proper air circulation is required for the heat pump to operate efficiently.
The following diagrams show the minimum clearances required for the proper
operation of the heat pump.
l Avoid placing objects near or on top of the heat pump. This includes
shrubbery and lawn furniture. These objects will reduce performance and
efficiency and hinder maintenance access.
(Top View)
2.4 Cleaning Equipment After Installation Installer – If you need to clean the equipment after installation, please use the following guidelines.
WARNING
Failure to heed the following may result in injury or death.
l Possible electric shock hazard – Deactivate power to all electrical devices on the pad when washing heat pump. Do not restore electrical power until equipment is completely dry.
NOTICE
Failure to heed the following may result in damage to equipment.
l Do not use a pressure cleaner to wash the heat pump. Damage to heat pump
components may result. If using a hose-end spray nozzle adjust the spray
pattern to low strength only.
l Do not spray water directly into the interior of the heat pump; damage to
components may result. l Do not use chemicals on the display panel.
2 – Appendix
Page – 18
2 – Appendix
Cleaning 1. Wash cabinet using a low-pressure water hose. A high-pressure
water stream will cause damage to the aluminum fins of the heat pump. This
damage is not covered under the product warranty. 2. While the heat pump is
still wet, use an approved cleaning agent to clean the exterior of the heat
pump. Do not use chemicals on the display panel. 3. Use a detergent-dampened
cloth to wipe the heat pump’s exterior cabinet. 4. Flush all exterior with
fresh water using a low-pressure water hose. 5. Dry the cabinet using a soft
cloth being careful not to damage fins.
APPROVED CLEANING AGENTS· Fantastic® Formula 409® Cascade® All Power Plain
Detergent (3% Solution) Table 3 – Cleaning Agents · The trademarks used in
approved cleaning agents are the property of their owners and are not related
to AquaCal®.
Polishing 1. Polish the heat pump’s cabinet panels using an approved polishing
agent and following the manufacturer’s instructions. Do not use chemicals on
the display panel. 2. Rinse the heat pump panels with fresh water, wipe, and
buff panels using a dry soft cloth. 3. Allow heat pump interior and
surrounding equipment to “air-dry” for several hours prior to restoring
electrical power.
APPROVED POLISHING AGENTS· Simoniz® Wax Glo-Coat® Armor All® Protectant Table
4 – Polishing Agents · The trademarks used in approved polishing agents are
the property of their owners and are not related to AquaCal®.
Page – 19
2.5 Dimensions
2.6 Identifying Model Specifications
1. Find Data Plate – The data plate is usually posted on the side of the
equipment or the inside of the heat pump’s access plate.
2. Find the model number on the data plate. The first letters and numbers
indicate the model type.
3. The complete model number identifies the equipment’s specifications. Model
Number Example
2 – Appendix
2.7 Weights
NOTE: Specifications subject to change.
Page – 20
2 – Appendix
Model Type TropiCal®
Model Number T030
Install Weight 120 Pounds (54 kg)
2.8 Initial Heating Recommendations
The following recommendations will reduce the amount of time required to heat
a pool. If unsure of equipment heating capability, review equipment data
plate. See “Identifying Model Specifications” on the previous page.
1. Set circulation pump time clock to 24 hours. 2. Set the desired
temperature “HEAT SETPOINT” for the water. 3. Use a pool cover or blanket to
reduce heating time. 4. After the desired temperature has been reached, reset
circulation pump time clock to normal time frame.
2.9 Winterizing Failure to properly winterize the heat pump as needed may result in serious equipment damage.
DANGER
Failure to heed the following will result in injury or death.
l Deactivate power while routing wiring to control board. l Units supplied
with a wired plug must use a (GFCI) rated outlet. Please note, the power cord
for this unit is 6.5
feet (198 cm) long. l Follow all National Electric Codes (NEC) and/or State
and Local guidelines.
WARNING
Failure to heed the following may result in injury or death.
l Deactivate all electrical power to heat pump before performing hard freeze procedures.
NOTICE
Failure to heed the following may result in damage to equipment.
l Failure to winterize heat pump may result in serious equipment damage.
Freeze damage is not covered under the heat pump warranty.
l While the plumbing connections are in the winterized condition (not fully
tightened), it is imperative that water not run through the heat pump. Loss of
water through loose plumbing connections may result in damage to circulation
pump, pool and spa structures, and other equipment.
Light Freeze Conditions
A light freeze is when the ambient air temperature falls below 32 degrees
Fahrenheit (0° C) for less than 8 hours. Typically during light freeze
conditions circulating (or moving) water will not freeze. Temporarily activate
the filter pump for continuous operation during light freeze conditions.
Hard Freeze Conditions
A hard freeze is when the ambient air temperature falls below 32 degrees
Fahrenheit (0° C) for more than 8 hours. In areas where this condition is
prevalent and sustained, the heat pump MUST be winterized for hard freeze
conditions. Follow the correct procedure depending on the type of heat
exchanger found in the heat pump.
Page – 21
Titanium ThermoLink® Exchanger (with no Drain)
1. Disconnect the plumbing to the heat pump at connection unions (removal is
counterclockwise).
2. Allow water to drain completely from the heat pump. Expect to see a lot of
water drain out at first, and then a small amount to continue to drain out
over a long period.
3. After heat pump has fully drained, partially reconnect plumbing connection
unions. 4. Winterizing is complete. 5. When ready to use the heat pump again,
hand-tighten connection unions. Reconnect electrical
power, and set the operating mode on the heat pump. Activate the filter pump.
No Drain
2.10 Available Accessories
Accessories may be purchased through an authorized dealer of AquaCal®
products.
Condensation Drain Kit (# STK0202) l Used when condensation water flow must be
directed to a specific location.
Grid Flow Switch (# 0040S) l Used for automatic pool/spa thermostat switching.
l This switch can also be used in place of the water pressure switch. This may
be needed when the pool/spa elevation is higher than the heat pump. A higher
elevation of the water can cause a false signal to the heat pump; indicating
water is flowing through the heat pump when it isn’t. l This kit is not to be
used on applications exceeding 50 PSI (345 kPa).
Liquid Blankets l An invisible liquid heat barrier designed to retain heat and
extend the swimming season. l AquaCal® recommends Lo-Chlor® Aqua BlanketTM.
2 – Appendix
Page – 22
Plumbing Unions l 2 Inch Unions – (# PLS2627)
PoolSync® WI-FI Controller (ECP0343) l This kit will add WiFi control
capabilities to the heat pump. l Contact installing dealer to order this
product.
3 – Troubleshooting
3 – Troubleshooting
IN THIS SECTION:
Fault Codes
FLOW LED is off
24
DEFROST LED is on
24
FAULT LED is rapidly blinking (Control panel unresponsive)
25
FAULT LED is blinking 1 time
25
FAULT LED is blinking 2 times
25
FAULT LED is blinking 3 times
25
FAULT LED is blinking 4 times
26
FAULT LED is blinking 5 times
26
FAULT LED is blinking 6 times
26
FAULT LED is blinking 7 times
26
Issues and resolutions
Display Panel Not Responding
26
Heat Pump Not Running
27
Heat Pump’s Tripping Breaker
27
Heat Pump Won’t Shut Off
27
Heat Pump Is Running, Not Heating
27
Water Coming From Heat Pump
28
Page – 23
3.1 Fault Codes
A fault code indicates a specific issue or condition that will require action
before the equipment can resume operating.
Please perform the following troubleshooting. If the issue reoccurs, please
contact AquaCal. See “Contacting AquaCal AutoPilot, Inc.” on page 1.
WARNING
Failure to heed the following may result in injury or death.
l Repairs must not be attempted by untrained or unqualified individuals.
l The heat pump contains refrigerant under high pressure. Repairs to the
refrigerant circuit must not be attempted by untrained or unqualified
individuals. Service must be performed only by qualified HVAC technicians.
Recover refrigerant before opening the system.
NOTICE
Failure to heed the following may result in damage to equipment.
l Service by unauthorized personnel will void the heat pump warranty.
FLOW LED is off
ISSUE Low or no water detected.
RESOLUTION
1. Confirm the filter pump is on. 2. If a multiple-speed filter pump is being
used, run at a higher speed to determine if the error persists. Do
not exceed the maximum flow rate for your model. 3. Confirm water is not being
diverted away from the heat pump.
l See “Water Flow Rates” on page 9.
DEFROST LED is on
ISSUE The heat pump has sensed the evaporator coil is icing up.
RESOLUTION
PASSIVE DEFROST
When ice starts to form on the coil, the compressor will stop operating while
the fan continues to operate.
l When the coil’s temperature rises above 38° F, the compressor is restarted
and heating resumes. l If the coil’s temperature remains below 38° F, the
compressor will remain off.
3 – Troubleshooting
Page – 24
3 – Troubleshooting
FAULT LED is rapidly blinking (Control panel unresponsive) ISSUE The heat pump
firmware needs to be reloaded on the control board. RESOLUTION
1. If the heat pump is connected to a PoolSync® WI-FI controller and is
connected to the internet, the heat pump will automatically perform a firmware
recovery.
2. If no PoolSync® WI-FI controller is connected, the heat pump will require
service from a qualified technician.
FAULT LED is blinking 1 time ISSUE The refrigerant system’s high-pressure or
low-pressure switch is showing as open. RESOLUTION Determine if an
insufficient amount of water is being supplied to the equipment.
1. Confirm the filter pump is on. 2. If a multiple-speed filter pump is being
used, run filter pump at a higher speed. Do not exceed maximum flow
rate for the model. 3. Confirm water is not being diverted away from the heat
pump.
l See “Water Flow Rates” on page 9. 4. The water pressure switch may be
incorrectly calibrated. See “Adjusting Water Pressure Switch” for more
information.
FAULT LED is blinking 2 times ISSUE The heat pump has locked due to five high-
pressure or five low-pressure faults during one call for heating. RESOLUTION
1. Deactivate power to heat pump, wait five seconds, then reactivate power to
the heat pump to clear error. 2. Troubleshoot the high-pressure issue causing
the error. See “FAULT LED is blinking 1 time” above.
FAULT LED is blinking 3 times ISSUE Incoming water temperature exceeded 110° F
and the unit is locked with a high temperature fault. The heat pump will not
operate until incoming water temperature drops to 100° F or lower. RESOLUTION
1. Determine if another heat source (gas heater, solar heater, etc.) is
heating water being sent directly to the heat pump. This situation will need
to be corrected before continuing.
2. Rule out an incorrect reading from the water temperature sensor. Verify
existing water temperature with an accurate thermometer. If heat pump’s sensor
is inaccurate, the water temperature sensor may require replacement.
Page – 25
3 – Troubleshooting
FAULT LED is blinking 4 times
ISSUE Shorted or open water sensor 1. RESOLUTION A qualified technician should
replace the water sensor.
FAULT LED is blinking 5 times
ISSUE Shorted or open water sensor 2. RESOLUTION A qualified technician should
replace the water sensor.
FAULT LED is blinking 6 times
ISSUE Shorted or open defrost sensor 1. RESOLUTION A qualified technician
should replace the defrost sensor.
FAULT LED is blinking 7 times
ISSUE Shorted or open defrost sensor 2. RESOLUTION A qualified technician
should replace the defrost sensor. 3.2 Issues and Resolutions
(missing or bad snippet)
l Repairs must not be attempted by untrained or unqualified individuals. l The
heat pump contains refrigerant under pressure. Repairs to the refrigerant
circuit must not be attempted by
untrained or unqualified individuals. Service must be performed only by
qualified HVAC technicians. Recover refrigerant before opening the system.
(missing or bad snippet)
l Service by unauthorized personnel will void the factory warranty.
Please perform the following troubleshooting. For further assistance, please
contact AquaCal. See “Contacting AquaCal AutoPilot, Inc.” on page 1.
Display Panel Not Responding
1. If the heat pump is controlled be an external controller, confirm the
external controller settings. See “Operating Heat Pump (With an External
Controller)”.
2. If the issue is still occurring, disconnect external controller from the
heat pump. Then check operation at heat pump.
l If display panel responds, the problem lies with the external controller or
its installation. Contact the manufacturer of the external control device.
Page – 26
3 – Troubleshooting
Heat Pump Not Running
1. Confirm equipment is receiving power. Is the heat pump display
illuminated?
l If not, confirm the main breaker (located at the power supply panel) and the
disconnect switch (located near the heat pump) are both turned on.
l Confirm the power switch on the heat pump’s display is set to on. l If the
display still does not illuminate, it is recommended that the heat pump
installer or electrician confirms heat
pump is receiving power.
2. Confirm thermostat is set correctly. See “Dial Control Panel”.
l When heating the water is desired, the thermostat should be set above the
current water temperature.
3. If an error code is displayed, diagnose and correct the cause of the code.
See “Fault Codes” on page 24. 4. If the heat pump is using an external
controller, the heat pump may not be set correctly at the external
controller.
l See “Operating Heat Pump (With an External Controller)”.
Heat Pump’s Tripping Breaker
1. Have an electrician confirm breakers are in good condition and properly
sized for the heat pump. 2. If a fault occurs immediately when the compressor
starts, a qualified technician should evaluate the system.
Heat Pump Won’t Shut Off
1. Confirm the heat pump has reached the desired temperature set on the
thermostat. The heat pump will continue to run until the set temperature is
reached.
2. If the heat pump is using an external controller, it may not be set
correctly.
l See “Operating Heat Pump (With an External Controller)”.
Heat Pump Is Running, Not Heating
1. If the heat pump is using an external controller, confirm it is set
correctly.
l See “Operating Heat Pump (With an External Controller)”. l If the heat pump
is still not running correctly with this device, contact the installer of the
external controller device
or the device’s manufacturer for further assistance.
3. Confirm thermostat is set to the desired water temperature. 4. Confirm
valves are correctly positioned to heat the correct body of water (either the
pool or the spa). If heating
a spa that overflows into a pool, confirm the spa is isolated when being
heated (not flowing into the pool). 5. Confirm heat pump is transferring heat
into the water.
l Measure the temperature of air discharge coming out of the heat pump fan. If
discharge air is between 8° to 10° colder than the outside ambient air, the
heat pump is moving heat into the water.
6. If an error code is displayed, diagnose and correct cause of code. See
“Fault Codes” on page 24. 7. Confirm that filter pump has a sufficient run-
time. The heat pump will not run (or heat the water) without water
flow. Heat Pump equipment will generally be set to run 24 hours a day in
commercial applications.See “Initial Heating Recommendations” on page 21. 8.
If heating a spa, deactivate air blower or venturi (if equipped) to allow for
quicker heating times. For pools, deactivate water features, such as slides,
waterfalls, or fountains to allow water to retain heat. Use of a liquid pool
blanket product can also compensate for excessive heat loss.
l See Available Accessories on page 22.for more information on liquid
blankets.
Ice forming on the heat pump When conditions are too cold for proper
operation, the heat pump will enter a defrost mode. This prevents ice from
building up on the evaporator coil.
Page – 27
3 – Troubleshooting
l The heat pump may develop a fine layer of white frost on the outside coil
before entering the defrost mode. This is normal.
l If heavy ice (not frost) starts to build up, shut off the heat pump. Contact
the installer or manufacturer. l If the ambient air temperature will be
falling below 32° F for more than 8 hours, winterize equipment.
Water Coming From Heat Pump The water may be normal condensation produced as a
by-product of the heat pump’s refrigeration process. The heat pump can produce
8 to 10 gallons of condensation per day depending on the humidity of the
ambient air. Determine if the water is condensation or a possible leak.
1. Deactivate heat pump, leaving the filter pump on. After several hours,
determine if water is still coming from the heat pump.
2. If using chlorine or bromine as a pool / spa sanitizer, test the water
around the heat pump using a test strip. If the test strip indicates that
chlorine or bromine is present, a leak may exist.
PLEASE NOTE If desired, a kit is available to re-direct condensation water
away from the heat pump. See “Condensation Drain Kit (# STK0202)” on page 22.
Page – 28
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>