CyberPower- OL5KSTF- Step-Down -Transformer
SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during
installation and maintenance of the STEP-DOWN TRANSFORMER module.
The Smart App Online OL5KSTF step-down transformer models that are covered in
this manual are intended for installation in an environment within 32°F to
104°F (0°C to 40°C), free of conductive contaminants.
SPECIAL SYMBOLS
- Warning: High voltage – Risk of Electric Shock
- Caution – Important Instructions: Must always be followed.
- Do Not Discard: The UPS or UPS batteries in trash. The batteries contain lead acid. For more information, contact your local recycling or hazardous waste facility.
- Information, advice, help
- See applicable user manual
PERSONAL SAFETY
CAUTION
The AC electrical service where the step-down transformer is connected should
be close to the unit and easily accessible. Please use only UL-marked mains
cable, (e.g. the mains cable of your equipment), to connect the step-down
transformer to the AC outlet. Please use only UL-marked power cables to
connect any equipment to the step-down transformer. Do not unplug the unit
from AC power during operation, as this will disconnect the protective ground
insulation. Do not use an improper size power cord as it may cause damage to
your equipment and cause fire hazards. Make sure everything is turned off and
disconnected completely before conducting any maintenance, repairs or
shipment. Installation environment should be in a temperature and humidity
controlled indoor area free of conductive contaminants. Do not install this
step-down transformer where excessive moisture or heat is present (Please see
specifications for acceptable temperature and humidity range). Never install a
step-down transformer, or associated wiring or equipment, during a lightning
storm. Do not work alone under hazardous conditions. Input circuit breaker
must be “OFF” during the building installation. Only qualified maintenance
personnel should perform this task. Before connecting to the step-down
transformer, check that the input voltage into the step-down transformer is
within specifications. DO NOT INSTALL THE STEP-DOWN TRANSFORMER WHERE IT WOULD
BE EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE!
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE HOUSING! DO NOT CONNECT
DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO STEP-DOWN TRANSFORMER OUTPUT
SOCKETS!
RISK OF ELECTRIC SHOCK
To prevent the risk of fire or electric shock, only use the supplied hardware to attach the mounting brackets. Remove watches, rings or other metal objects. Use tools with insulated handles. Use tools with insulated handles. The step- down transformer must be connected to a grounded AC power source with fuse or circuit breaker protection. DO NOT plug the step-down transformer into an outlet that is not grounded. If you need to power-drain this equipment, turn off and unplug the unit. (No User Serviceable Parts): Risk of electric shock, do not remove cover. No user serviceable parts inside. Refer servicing to qualified service personnel. To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area, free of conductive contaminants. (Please see specifications for acceptable temperature and humidity range). To avoid electric shock, turn off and unplug the unit before installing the input/output power cord with a ground wire. Connect the ground wire prior to connecting the line wires! Connect the Protection Earth (PE) safety conductor before any other cables are connected. Internal circuit configuration or equivalent. Installation instructions shall carry sufficient information, including the basic internal circuit configuration of the UPS, to emphasize its compatibility with power distribution systems. Signaling circuit connection – Information shall be provided in the installation instructions as to the purpose and connection of any signaling circuits. For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall be easily accessible. For Permanently Connected Equipment:
- A readily accessible disconnect device shall be incorporated in the building installation wiring for AC Input.
- CAUTION – To reduce the risk of fire, connect only to a circuit provided with 30 A maximum branch circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1.
- Wiring Information: Use No. 10 AWG, minimum 90°C copper wire and 18 lb-in Torque force when connecting to AC wiring terminal.
RISK OF ELECTRIC SHOCK
The step-down transformer should be placed near the connected equipment and easily accessible. All step-down transformer models covered in this document are permanently- connected equipment and only qualified maintenance personnel may carry out installations. Wiring must be done by qualified personnel. DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! Under no circumstances should this unit be used for medical applications involving life support equipment and/ or patient care. DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation from the aquarium can come in contact with metal electrical contacts and cause equipment to short out. The unit has a dangerous amount of voltage.
INTRODUCTION
The CyberPower Step-Down and Isolation Transformers support hardwire and power
cord installations OL5KSTF and are designed for a variety of CyberPower UPS
systems. When connected to a UPS, the step-down transformer converts voltage
from 208V down to 120V.
UNPACKING PROCEDURES
Information, advice, help
The UPS system is very heavy, please handle with care. Wear safety shoes and
use a hydraulic equipment lift if one is available. At least two people are
required for all handling operations, including unpacking, lifting, and
installation in a rack system. Do not use the lifting straps to carry the unit
around; they are provided to manually unpack the unit only.
USE LIFTING STRAPS TO REMOVE UNIT FROM THE BOX.
WHAT’S IN THE BOX
ITEM | CONTENT | QTY |
---|---|---|
1 | OL5KSTF step-down and isolation transformer | 1 |
2 | Left & right hanging brackets | 1 |
3 | Left & right rackmount rail | 1 |
4 | Input terminal block bottom cover | 1 |
5 | 2U Rack mount ears (Tower stands) | 2 |
ITEM | CONTENT | QTY |
--- | --- | --- |
6 | Black M5X7L flat head screws | 8 |
7 | Black M5X12L pan head screws | 12 |
8 | Silver M5X6L pan head screws | 6 |
9 | Plastic washers | 8 |
10 | Installation and operation manual | 1 |
OVERVIEW
STEP-DOWN TRANSFORMER
-
Input Terminal Block with pre-installed L6-30P Power Cord
Connect to input power source (UPS). -
Input circuit breaker
Provides input current overload and fault protection. -
4 x NEMA 5-20R Outlets (120Vac) — segment 1
Output receptacles to connect equipment load. -
Output Circuit Breaker (15A Max) — segment 1
Provides output overload and fault protection. -
Output Circuit Breaker (15A Max) — segment 2
Provides output overload and fault protection. -
4 x NEMA 5-20R Outlets (120Vac) — segment 2
Output receptacles to connect equipment load. -
2 x NEMA 5-20R Outlets (120Vac) — segment 3
Output receptacles to connect equipment load. -
Output Circuit Breaker (15A Max) — segment 3
Provides output overload and fault protection. -
Output Circuit Breaker (15A Max) — segment 4
Provides output overload and fault protection. -
2 x NEMA 5-20R Outlets (120Vac) — segment 4
Output receptacles to connect equipment load.
HARDWARE INSTALLATION
RACKMOUNT INSTALLATION FOR 4-POST RACK
Caution: Important Instructions
To prevent the risk of fire or electric shock, only use the supplied hardware to attach the mounting brackets.
-
Step 1: Rackmount ear & hanging bracket installation
Attach two rack mount ears to the step-down transformer using eight black M5X7L flat head screws. Install hanging brackets using six silver M5X6L pan head screws -
Step 2: Rackmount rail Installation
The rails adjust to mount in 19 in (48 cm) racks from 20.5 in to 36 in (52 cm to 91.5 cm) deep. Select the proper holes in the rack for positioning the step-down transformer in the rack. The step-down transformer takes up 2 rack units: rack hole positions 1 through 6. Position the guide screws on the back of the rackmount rails into the rear rack square holes to temporarily support the rails in place. -
Step 3: Adjust rackmount rails to fit your rack
Adjust the rail depth to match your rack depth. Attach the rackmount rail to your rack with two black M5X6L pan head screws and two plastic washers at the front of the rack (square holes 1 and 4 as shown below). Secure the rail to the rear of the rack with two black M5X12L screws and two plastic washers.
RACKMOUNT INSTALLATION FOR 4-POST RACK CONT.
RACKMOUNT EARS INSTALLATION CONT.
- Step 4: Place and secure the step-down transformer on the rails
Slide the hanging brackets on the step-down transformer on to the rails mounted in the rack with the front of the unit facing toward you. Secure the step-down transformer to your rack with four black M5X12L pan head screws at the front of the rack (square holes 1 and 4 as shown above).
NOTE: To slide the step-down transformer out from the rack
The step-down transformer will be secured by a safety locking mechanism midway
of pulling it out of the rack. Use both hands to hold the step-down
transformer and press the safety locking tab to pull the step- down
transformer out.
RACKMOUNT INSTALLATION FOR 2-POST RACK
This unit can be installed in a 2-post rack with an optional CyberPower 2-post
mounting kit (model: 2POSTKIT, sold separately). See the instructions included
with the rail kit for installation procedures.
ELECTRICAL INSTALLATION
THE INPUT CONFIGURATION
- Check that all power is turned OFF, before installing the step down transformer.
- IMPORTANT! Make sure the utility circuit breaker feeding the UPS input is in the OFF position.
- IMPORTANT! Make sure the UPS is turned off.
- IMPORTANT! Verify the input wiring meets the recommended sizing.
OL5KSTF NEMA L6-30P POWER CORD CONNECTION: Connect the NEMA L6-30P input
power cord directly to an outlet on the UPS. Refer to the “CONNECTING A STEP-
DOWN TRANSFORMER TO A UPS POWER MODULE” section in this user manual for
instructions.
OL5KSTF ELECTRICAL CONNECTION: Please see the instructions as shown
below. Check wiring dimensions with the following table.
STEP-DOWN AND ISOLATION TRANSFORMERS WITH HARDWIRE INPUT TERMINAL BLOCK|
WIRING AWG
|
WIRING mm 2
|
SCREW
TORQUE lbf-in
---|---|---|---
OL5KSTF| 10 AWG| 5.5 mm2| 18 lbf-in
- Remove the top section of the input terminal cover by removing the top two screws.
-
- Remove the bottom section of the input terminal cover by removing the bottom two screws.
- Secure the bottom section of the input terminal cover using the included screws.
- Insert the input cable through the appropriate cable gland (not included). Connect the three wires to input terminal block.
- Secure the top section of the input terminal cover using the included screws.
CONNECTING A STEP-DOWN TRANSFORMER TO A UPS POWER MODULE
The following illustrations provide the recommended connections between a
step-down transformer and a CyberPower Smart App Online UPS
System.
TECHNICAL SPECIFICATIONS
MODELS | OL5KSTF |
---|
CONFIGURATION
Maximum Output Power (VA)| 5,000 VA/60HZ| 4,800 VA/50HZ
Maximum Output Power (W)| 5,000 W/60HZ| 4,800 W/50HZ
Form Factor| Rackmount
INPUT
Nominal Input Voltage| 208 Vac
Input connection type| Power cord L6-30P Terminal
Input Frequency| 50/60 Hz
Input Current Rating| Power Cord:24A / Terminal:27A
OUTPUT
Nominal Output Voltage| 120 Vac
UPS Outlets| (12) NEMA 5-20R
PHYSICAL
Dimensions| L x W x H = 23.6 x 17 x 3.4 in. (600 x 433 x 86.5mm)
Net Weight| 38 kg / 83.8 lbs
ENVIRONMENTAL
Operating Temperature| 32°F to 104°F (0°C to 40°C)
Operating Relative Humidity| 0 to 90% Non-condensing
SAFETY
Conformance Approvals| UL
PRODUCT REGISTRATION
CyberPower requests that you complete and return the Warranty Registration Card enclosed with the Product or register the Product at its website (www.cyberpowersystems.com/registration) to establish that you are the Initial Customer of the Product, and therefore entitled coverage under the Limited Warranty and the Connected Equipment Guarantee. (Registration is not required for coverage, but note: if you do not register your purchase, you will be required to provide proof of purchase.)
LIMITED WARRANTY AND CONNECTED EQUIPMENT GUARANTEE
Please visit www.CyberPowerSystems.com for a copy of the Limited Warranty and Connected Equipment Guarantee.
- Cyber Power Systems, Inc. | www.CyberPowerSystems.com
- For USA and Canada | 4241 12th Ave East, Suite 400, Shakopee, MN 55379 | Toll-free: 877.297.6937
- For all other regions | Please visit our website for local contact information.
Copyright © 2021 Cyber Power Systems, Inc. All rights reserved.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>