GOODWE GM1000D Three-Phase Smart Meter Installation Guide

June 5, 2024
GOODWE

GOODWE GM1000D Three Phase Smart Meter Quick Installation Guide
Smart Meter
(GM1000D/GM3000/GM1000)
V1.0 -2022-01-25

Product Introduction

GOODWE GM1000D Three Phase Smart Meter - Product
Introduction

Installation

Packing ListGOODWE GM1000D Three Phase Smart Meter - Packing
List

[1]: For GM1000D and GM3000 only.
[2]: GM1000D x 8; GM1000 x 4; GM3000 x 6.
Installation and Cable Connection

GOODWE GM1000D Three Phase Smart Meter - Cable
Connection

Wiring System

GM1000D

GOODWE GM1000D Three Phase Smart Meter - GM1000D

  • Recommended cable connected to the voltage input terminal: 1mm² (17AWG).
  • CT direction: House (K)–>Grid (L).

GM1000

GOODWE GM1000D Three Phase Smart Meter - GM1000

  • Recommended cable connected to the voltage input terminal: 1mm² (17AWG).
  • CT direction: House (K)–>Grid (L).

GM3000

GOODWE GM1000D Three Phase Smart Meter - GM3000

  • Recommended cable connected to the voltage input terminal: 1mm² (17AWG).
  • CT direction: House (K)–>Grid (L).

Commissioning

Power ON
Step 1 Connect the smart meter cables.
Step 2 Power on the inverter and make sure that the inverter is working normally. Then the smart meter is powered on.
Indicator

Type Status Description
Steady on Power on
Off Power off
Steady on Purchasing from the utility grid.
Blinking Selling to the utility grid.
Blinking The communication is normal.
Blink 5 The meter is resetting

Reset Button

Press Time Description
< 3s Reset the smart meter.
5s Restore factory settings.
>10s Restore factory settings and clear the historical energy data.

Technical Parameters

Model GM1000D GM1000 GM3000
Application Single-phase Single-phase Three-phase
Voltage Nominal Voltage 110V/230V 3 x 230V/380V
Voltage Range 100V-240V
Frequency 50Hz/60Hz
Current Input Nominal Current CT in: 120A/40mA
Current Range 0.48A-120A
Self-Consumption <3W
Data Detection CurrentNoltage/Active Power/Reactive Power/Power

Factor/Frequency
Energy Calculation| Active/Reactive Power Energy
Precision| Voltage/Current| Class I
Active Power| Class I
Reactive Power| Class II
Communication| RS485(Bund Rate 9600/Modbus Protocol/Communication cable max. length 100m)
Interface| 3 LED (Power, Energy Consumption, Communication), USB port, Reset button
Mechanical| Size (L xWxH mm)| 36 x 85 x 66.5
Weight| 360g| 250g| 450g
Protection Class| IP20 (For indoor use)
Installation Method| Mounting rack
Operating Temperature| -25 – +60° C
Operating Humidity| <95%, No condensation
Altitude| <2000m

EU Declaration of Conformity

The module sold in the European market meets the following directives and requirements:

  • Electromagnetic compatibility Directive 2014/30/EU (EMC)
  • Electrical Apparatus Low Voltage Directive 2014/35/EU (LVD)
  • Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS)
  • Waste Electrical and Electronic Equipment 2012/19/EU
  • Registration, Evaluation, Authorization, and Restriction of Chemicals (EC) No 1907/2006 (REACH)
    You can download the EU Declaration of Conformity at https://en.goodwe.com.

Official Website|
---|---
https://en.goodwe.com/| https://en.goodwe.com/contact-us.asp

No. 90 Zijin Rd., New District, Suzhou, 215011, China
**** www.goodwe.com
[email protected]

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

GOODWE User Manuals

Related Manuals