sauermann CTV 210-R Air Velocity and Temperature Sensor User Guide
- June 5, 2024
- sauermann
Table of Contents
CTV 210-R Air Velocity and Temperature Sensor
User Guide
www.sauermanngroup.com
Quick Start Guide
CTV 210-R
**Air velocity and temperature transmitter
| Airflow function
---|---
| Two 4-wire analog output 0-5 / 10 V 4-20 mA
| 2 relay outputs
| ABS V0 IP65 housing, optional display
General features
Power supply| 24 Vac / Vdc ±10%. 100-240 Vac, 50-60 Hz Warning: risk of
electric shock
---|---
Output| 2 x 4-20 mA or 2 x 0-20 mA or 2 x 0-5 V or 2 x 0-10 V (4 wires) Common
mode voltage <30 Vac. Maximum load: 500 Ohms (0/4-20 mA). Minimum load: 1 K
Ohms (0-5/10 V)
Relay outputs| 2 changeover relays 3 A / 230 V. NO : 5A / NC: 3A / 240 Vac
Galvanic isolation| Inputs and outputs (models 100-240 Vac). The device fully
protected by
DOUBLE ISOLATION or REINFORCED ISOLATION Outputs (models 24 Vac/Vdc)
ExtinctionConsum| CTV210-B: 6 VA. CTV210-H: 8 VA
Electrical conn| Screw terminal block for cable 2.5 mm² Carried out according
to the code of good practice
PC communication| USB-Mini Din cable
Environment| Air and neutral gases
Conditions of use (°C/%RH/m)| From -10 to +50 °C. In non-condensing
conditions. From 0 to 2000 m.
Storage temperature| From -10 to +70 °C
Security| Protection class II; Pollution degree 2; Overvoltage category 2
(OVCII)
European directives| 2014/30/EU EMC; 2014/35/EU Low Voltage; 2011/65/EU RoHS
II; 2012/19/EU WEEE
Features of the housing
Material | ABS V0 as per UL94 |
---|---|
Protection | IP65 |
Display | 75 x 40 mm, LCD 20 digits 2 lines. |
Height of digits: Values: 10 mm; Units: 5 mm
Cable gland| For cables Ø 8 mm maximum
Weight| 340 g
All dimensions are in millimeters.
Used symbols
For your safety and in order to avoid any damage of the device, please follow
the procedure described in this document and read carefully the notes preceded
by the following symbol:
The following symbol will also be used in this document, please read carefully
the information notes indicated after this symbol:
Connections
- DIP switch (d)
- LCC-S software connection
- Relays
- Analogue outputs (a)
- F3.20* fuse
- Power supply terminal block (c)
- Cable glands
Power supply type (b) specified on the label on the side of the transmitter
*Fuse present only for 100-240 Vac models.
Every fuse replacement must be performed with a power-off device using a TR5
630 mA 250 V fuse.
Electrical connections as per NFC15-100 standard
This connection must be made by a formed and qualified technician. To make
the connection, the transmitter must not be energized. Before making the
connection, you must first check the power supply indicated on the transmitter
board (see (b) on the “Connections” part). The presence of a switch and a
circuit breaker upstream of the device is compulsory.
- For transmitters with a 24 Vdc power supply:
- For transmitters with 24 Vac power supply:
- For transmitters with 100-240 Vac power supply:
The selection of the output signal in voltage (0-10 V or 0-5 V) or in the current (4-20 mA or 0-20 mA) is made via the DIP switch (d) of the electronic board of the transmitter: put the on-off switches as shown in the table below:
Connection of the output in current 4-20 mA:
Connection of output in voltage 0-10 V:
On 100-240 Vac models, if fuse protection is used for the power line, it is imperative to use delayed-action fuses in order to absorb the surge of current when first turned on the transmitter.
Transmitters configuration
It is possible on class 210 to configure all the parameters managed by the transmitter: units, measuring ranges, outputs, channels, calculation functions, etc, via different methods:
- Keypad for models with display: a code-locking system allows to secure the installation (See class 210 user manual).
- Software (optional) on all models. Simple user-friendly configuration. See LCC-SD user manual.
Configurable analog output:
Range with central zero (-50/0/+50 Pa), with offset zero (-300/0/+70 Pa) or
standard range (0/+100 Pa), it is possible to configure your own intermediate
ranges.
Caution: the minimum difference between the high range and the low range is
20.
Configure the range according to your needs: outputs are automatically
adjusted to the new measuring range
Mounting
To mount the transmitter, mount the ABS plate on the wall (drilling: Ø6 mm, screws and pins are supplied). Insert the transmitter on the fixing plate (see A on the drawing beside). Rotate the housing in a clockwise direction until you hear a “click” which confirms that the transmitter is correctly installed.
Accessories
Please refer to the datasheet to get more information about available
accessories.
Maintenance: Please avoid any aggressive solvents. Please protect the
transmitter and its probes from any cleaning product containing formalin, that
may be used for cleaning rooms or ducts.
Precautions for use: please always use the device in accordance with its
intended use and within the parameters described in the technical features in
order not to compromise the protection ensured by the device.
Download the full manual
https://sauermanngroup.com/fr-INT/technical-documents?search=ctv+210
Customer service portal
Use our Customer service portal to contact us Utilisez notre Portail service
clients pour nous contacter
QSG CTV 210-R 14/01/2022
Non-contractual document
We reserve the right to modify the characteristics of our products without
prior notice
https://sauermann-en.custhelp.com
www.sauermanngroup.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>