- Q: What is the maximum capacity of the PUHY-P1100YSNW-A2 heat
- Q: What is the total piping length allowed for this model?
- Q: How should I adjust the piping if it exceeds the recommended
R410A Series City Multi VRF Air Conditioner System
“`html
Product Specifications:
- Model: PUHY-P1100YSNW-A2
- Range: Standard Heat Pump
- Capacity: 44 HP
Product Usage Instructions:
Piping Instructions:
The following sections provide piping instructions for the
PUHY-P1100YSNW-A2:
- Section S+T+M+N+A+B+C+D+a+b+c+d
- Section M+N+S+T
- Section M(N)+S+A+B+C+D+d
- Section B+C+D+d
Piping Length Specifications:
-
Total Piping Length: Up to 1000m
-
Distance between Outdoor Units: 10m
-
Height between Outdoor Units: Up to 0.1m
-
Furthest Piping Length (L1): Up to 165m
-
Furthest Piping Length (L2): Up to 40m *3
-
Height between Indoor & Outdoor Units (Outdoor Above): Up
to 50m *1 -
Height between Indoor & Outdoor Units (Outdoor Below): Up
to 40m *2 -
Height between Indoor and Indoor Units: Up to 15m *4
*1. 90m is available depending on the model and installation
conditions. Please refer to the design tool schematic & ‘Height
Check’ document.
*2. 60m is available depending on the model and installation
conditions. Please refer to the design tool schematic & ‘Height
Check’ document.
*3. 90m is available. When the piping length exceeds 40m, use
one size larger liquid pipe starting with the section of piping
where 40m is exceeded and all piping after that point.
In the figure above, if the piping labelled D exceeds 40m (but
does not exceed 90m), increase the size of the liquid piping
labelled D, c, and d by one size.
Frequently Asked Questions (FAQ):
Q: What is the maximum capacity of the PUHY-P1100YSNW-A2 heat
pump?
A: The maximum capacity of this heat pump is 44 HP.
Q: What is the total piping length allowed for this model?
A: The total piping length can be up to 1000m.
Q: How should I adjust the piping if it exceeds the recommended
lengths?
A: If the piping length exceeds the specified limits, increase
the size of the liquid pipe as indicated in the instructions.
“`
0
44 HP
Y Series
PUHY-P1100YSNW-A2
PUHY-P350YNW-A2 PUHY-P350YNW-A2
PUHY-P400YNW-A2
T46heHfPollowing sections lay ouPt UthHeYP-Pip1in1g50reYsStrNicWtio-nAs2and PipPeUSHeYle-Pct3io5n0.YNW-A2
PUHY-P400YNW-A2
Range
Standard heat pump
CoPmUpHriYs-iPn4g00YNW-A2
488HHPP 10 HP 12 HP 1540 HHPP 16 HP 18 HP 2502 HHPP 16 HP
1584 HHPP
20 HP
PUHY-P21020Y0YNSWN-WA2-A2 PUHY-P250YNW-A2 PUHY-P300YNW-A2 PPUUHHYY
–PP315205Y0YNSWN-WA2-A2 PUHY-P400YNW-A2 PUHY-P450YNW-A2 PPUUHHYY
–PP510300Y0YNSWN-WA2-A2 PUHY-P400YSNW-A2
PPUUHHYY–PP415305Y0YSSNNWW-A-A2 2
PUHY-P500YSNW-A2
PUHY-P400YNW-A2 PUHY-P400YNW-A2 PUHY-P400YNW-A2 PUHY-P400YNW-A2 PUHY- P400YNW-A2 PUHY-P450YNW-A2 PUHY-P400YNW-A2 PPUUHHYY-P-P240500YYNNWW-A-A22 PPUUHHYY-P-P240500YYNNWW-A-A22 PPUUHHYY-P-P240500YYNNWW-A-A22 PPUUHHYY-P-P245500YYNNWW-A-A22 PPUUHHYY-P-P245500YYNNWW-A-A22
PUHY-P250YNW-A2
22 HP
PUHY-P550YSNW-A2
PUHY-P250YNW-A2
24 HOPutdoor TwinningPUKHiYts-P600YSNW-A2
PUHY-P300YNW-A2 PUHY-P300YNW-A2
Outdoor Unit YSNW
Twinning Kit PUHY-P300YNW-A2
2P640H0P~ P650
PUHY-P650YSNW-A2 CMYP-UYH10Y0-PV2B5K03YNW-A2
P700 ~ P900
CMYP-UYH20Y0-PV4B0K02YNW-A2
2P895H0P~ P1350
PUHY-P700YSNW-A2 CMYP-UYH30Y0-PV3B5K03YNW-A2
PUHY-P350YNW-A2
30 HP
PUHY-P750YSNW-A2
PUHY-P350YNW-A2
PUHY-P400YNW-A2
32 HP
PUHY-P800YSNW-A2
PUHY-P350YNW-A2
PUHY-P450YNW-A2
34 HP
PUHY-P850YSNW-A2
PUHY-P400YNW-A2
PUHY-P450YNW-A2
36 HP
PUHY-P900YSNW-A2
PUHY-P450YNW-A2
PUHY-P450YNW-A2
38 HP
PUHY-P950YSNW-A2
PUHY-P250YNW-A2
PUHY-P350YNW-A2
PUHY-P350YNW-A2
40 HP
PUHY-P1000YSNW-A2
PUHY-P250YNW-A2
PUHY-P350YNW-A2
PUHY-P400YNW-A2
42 HP
PUHY-P1050YSNW-A2
PUHY-P250YNW-A2
PUHY-P400YNW-A2
PUHY-P400YNW-A2
1
44 HP 46 HP 48 HP 50 HP 52 HP 54 HP
PUHY-P1100YSNW-A2 PUHY-P1150YSNW-A2 PUHY-P1200YSNW-A2 PUHY-P1250YSNW-A2 PUHY- P1300YSNW-A2 PUHY-P1350YSNW-A2
PUHY-P350YNW-A2 PUHY-P350YNW-A2 PUHY-P400YNW-A2 PUHY-P350YNW-A2 PUHY- P400YNW-A2 PUHY-P400YNW-A2 PUHY-P400YNW-A2 PUHY-P400YNW-A2 PUHY-P400YNW-A2 PUHY-P400YNW-A2 PUHY-P400YNW-A2 PUHY-P450YNW-A2 PUHY-P400YNW-A2 PUHY- P450YNW-A2 PUHY-P450YNW-A2 PUHY-P450YNW-A2 PUHY-P450YNW-A2 PUHY-P450YNW-A2
Outdoor Twinning Kits
Outdoor Unit YSNW
P400 P650 P700 P900 P950 P1350
Twinning Kit CMY-Y100VBK3 CMY-Y200VBK2 CMY-Y300VBK3
Piping Length
2
Item Total piping length Distance between outdoor unit & outdoor unit Height
between outdoor unit
& outdoor unit Furthest piping length (L1) Furthest piping Length (L2)
after first branch Height between indoor & outdoor units (outdoor above)
Height between indoor & outdoor units (outdoor below) Height between indoor
and
indoor units
Piping Length Pipe Section
S+T+M+N+A+B+C+D+a+b+c+d M+N+S+T
h2
M(N)+S+A+B+C+D+d B+C+D+d
H
H`
h1
Max Length 1000 m 10 m
0.1 m
165 m 40 m 3
50 m 1
40 m 2
15 m 4
*1. 90 m is available depending on the model and installation conditions. Please refer to design tool schematic & `Height Check’ document.
*2. 60 m is available depending on the model and installation conditions. Please refer to design tool schematic & `Height Check’ document.
*3. 90 m is available. When the piping length exceeds 40 m, use one size larger liquid pipe starting with the section of piping where 40 m is exceeded and all piping after that point.
In the figure above, if the piping labelled “D” exceeds 40 m (but does not exceed 90 m), increase the size of the liquid piping labelled D, c, and d by one size.
*4. 30 m is available. If the height difference between indoor units exceeds 15 m (but does not exceed 30 m), use one-size larger pipes for indoor unit liquid pipes.
In the figure above, if “h1″ exceeds 15 m, increase the size of the liquid
piping labelled by one size i.e. pipe `d’.
3
Outdoor Unit 1st Branch (Pipe A)
Outdoor Unit P200 P250-P300 P350-P400 P450-P650 P700-P800 P850-P1350
Outdoor Unit 1st Branch (Pipe A)
Liquid mm (in)
Gas mm (in)
9.52 (3/8″)
22.20 (7/8″)
9.52 (3/8″) *1
22.20 (7/8″)
12.70 (1/2″)
28.58 (1-1/8″)
15.88 (5/8″)
28.58 (1-1/8″)
19.05 (3/4″)
34.93 (1-3/8″)
19.05 (3/4″)
41.28 (1-5/8″)
*1 If size 250 piping length L1 exceeds 90m use 12.70(1/2″) If size 300 piping length L1 exceeds 40m use 12.70(1/2″)
Branch Pipe Size (Pipe B, C, D)
Branch Pipe Size (Pipe B, C, D)
Total Capacity of Indoor Units Liquid mm (in)
<P/M140
9.52 (3/8″)
P/M141 ~ P/M200
9.52 (3/8″)
P/M201 ~ P/M300
9.52 (3/8″)
P/M301 ~ P/M400
12.70 (1/2″)
P/M401 ~ P/M650
15.88 (5/8″)
P/M651 ~ P/M800
19.05 (3/4″)
P/M801 ~
19.05 (3/4″)
Gas mm (in) 15.88 (5/8″) 19.05 (3/4″) 22.20 (7/8″) 28.58 (1-1/8″) 28.58 (1-1/8″) 34.93 (1-3/8″) 41.28 (1-5/8″)
Branch Indoor Unit (Pipe a, b, c, d)
Branch Indoor Unit (Pipe a, b, c, d)
Total Capacity of Indoor Units Liquid mm (in)
Gas mm (in)
P/M10 ~ P/M50
6.35 (1/4″)
12.70 (1/2″)
P/M63 ~ P/M140
9.52 (3/8″)
15.88 (5/8″)
P200
9.52 (3/8″)
19.05 (3/4″)
P250
9.52 (3/8″)
22.70 (7/8”)
4
First Joint
Outdoor Unit First Joint
Outdoor Unit Model
Branch Pipe Model
P200 – P400
CMY-Y102LS-G2
P450 – P650
CMY-Y202S-G2
P700 – P1350
CMY-Y302S-G2
Branch Joint
Type of Branch Pipe Joint
Branch Joint Total Capacity of Indoor Unit P/M200 P/M201 ~ P/M400 P/M401 ~ P/M650 P/M651 or above
Branch Pipe Model CMY-Y102SS-G2 CMY-Y102LS-G2 CMY-Y202S-G2 CMY-Y302S-G2
5
6