Solplanet ASW 1-3K S-S Series Installation Guide

June 3, 2024
solplanet

Solplanet-ASW-1-3K-S-S-Series-logo

Solplanet ASW 1-3K S-S Series

Safety Instruction

  1. The contents of this document will be updated irregularly for product version upgrade or other reasons. Unless otherwise specified, this document only works as guide. All statements, information and suggestions in this document do not constitute any guarantee.
  2. This product can only be installed, commissioned, operated and maintained by technicians who  have carefully read and fully understood the user manual.
  3. This product must only be connected with PV modules of protection class II( in accordance with IEC 61730, application class A).PV modules with a high capacitance to ground must only be used if their capacity does not exceed 1μF.Do not connect any sources of energy other than PV modules to the product.
  4. When exposed to sunlight, the PV modules generate dangerous high DC voltage which is present in the DC cable conductors and live components. Touching live DC cable conductors and live components can result in lethal injuries due to electric shock.
  5. All components must remain within their permitted operating ranges at all times.
  6. The product complies with Electromagnetic compatibility 2014/30/EU, Low Voltage Directive 2014/35/EU and Radio Equipment Directive 2014/53/EU.

Mounting environment

  1. Ensure that the inverter is installed out of the reach of children.

  2. To ensure best operating status and prolonged service life, the mounting ambient temperature of the inverter should be ≤40°C.

  3. To avoid direct sunlight, rain, snow, ponding on the inverter, it is suggested to mount the inverter in places with a top protective roof.
    Do not completely cover the top of the inverter.

  4. The mounting condition must be suitable for the weight and size of the inverter. The inverter is suitable to be mounted on solid wall that is vertical or tilted backwards(Max. 15°).
    It is not recommended to install the inverter on wall made of plasterboards or similar materials.
    The inverter may make noise when working.Solplanet-
ASW-1-3K-S-S-Series-02

  5. To ensure adequate heat dissipation, the clearances between the inverter and other objects are recommended as follows:Solplanet-ASW-1-3K-S-S-Series-03

Scope of delivery

Solplanet-ASW-1-3K-S-S-Series-04

  1. Insert the adapter to the socket element, stuff the seal ring into the adapter and tighten the swivel nut.
    Solplanet-ASW-1-3K-S-S-Series-16

  2. Plug the AC connector into the socket for the AC connection.

  3. If required, you can connect a second protective conductor as equipotential bonding.

Inverter’s mounting
  1. Use a Φ10mm bit to drill 3 holes at a depth of about 70mm according to the location of the wall mounting bracket.
  2. Hang the inverter to the wall mounting bracketSolplanet-ASW-1-3K-S-S-Series-06
  3. Insert wall plugs into the wall and fix the wall mounting bracket to the wall by screwing three self-tapping screws(SW10).
  4. Secure the inverter to the wall mounting bracket on both sides using M4 screws.
    Screwdriver type: PH2, torque: 1.6Nm.Solplanet-
ASW-1-3K-S-S-Series-05

AC connection

DANGER:

  • All electrical installations must be done in accordance with all local and national rules.
  • Make sure that all DC switches and AC circuit breakers have been disconnected before establishing electrical connection. Otherwise, the high voltage within the inverte may lead to electrical shock.
  • In accordance with safety regulations, the inverter need be grounded firmly. When poor ground connection(PE) occurs, the inverter will report PE grounding error. Please check and ensure that the inverter is grounded firmly or contact AISWEI service.
  1. AC cable requirements are as follows. Insert the conductor into a suitable ferrule acc to DIN 46228-4 and crimp the contact .
    Object| Description| Value
    ---|---|---
    A| External diameter| 10-16mm
    B| Copper conductor cross-section| 4-6mm2
    C| Stripping length of the insulated conductors| 13mm
    D| Stripping length of the cable outer sheath| 53mm
    The PE conductor must be 2 mm longer than the L and N conductors.
  2. Loosen the swivel nut of AC connector. Insert the crimped conductors into corresponding terminals and tighten screws with the accompanied Allen key. Torque: 2.0NmSolplanet-ASW-1-3K-S-S-Series-08

DC connection

  • Make sure PV modules have good insulation against ground.
  • On the coldest day based on statistical records, the Max. open-circuit voltage of the PV modules must not exceed the Max. input voltage of the inverter.
  • Check the polarity of DC cables.
  • Ensure that DC switch has been disconnected.
  • Do not disconnect DC connectors under load.
  1. Please refer to“ DC Connector Installation Guide”.
  2. Before DC connection, insert the DC plug connectors with sealing plugs into DC input connectors of the inverter to ensure protection degree.Solplanet-ASW-1-3K-S-S-Series-19
Communication setup

DANGER:

  • Separate communication cables from power cables and serious interference sources.
  • The communication cables must be CAT-5E or higher-level shield cables. Pin assignment complies with EIA/TIA 568B standard. For outdoor use, the communication cables must be UV-resistant. The total length of communication cable cannot exceed 1000m.
  • If only one communication cable is connected, insert a sealing plug into the unused hole of sealing ring of the cable gland.
  • Before connecting communication cables, ensure the protective film or communication plate attached to the communication opening on the inverter is sealed tightly.

Commissioning

DANGER:

  • Check that the inverter is grounded reliably.
  • Check that the ventilation condition surrounding the inverter is good.
  • Check that the grid voltage at the point of connection of the inverter is within the permitted range.
  • Check that the sealing plugs in DC connectors and the communication cable gland are sealed tightly.
  • Check that grid connection regulations and other parameter settings meet safety requirements.
  1. Switch on AC circuit breaker between the inverter and the grid.

  2. Switch on DC switch.

  3. When there is sufficient DC power applied and the grid conditions are met, the inverter will start to operate automatically.

  4. COM1: RS485(optional)

  5. RS485 cable pin assignment as below.
    Solplanet-ASW-1-3K-S-S-Series-09

  6. Loosen the swivel nut of the cable gland on the communication cover, remove sealing plugs and lead the cable through the swivel nut, sealing ring, communication cover and magnetic ring.

  7. Insert the cable into the socket, attach the communication cover to inverter with M4 screws , and tighten the swivel nut. Screwdriver type: PH2, torque: 1.6NmSolplanet-ASW-1-3K-S-S-Series-12

  8. **COM2: GPRS/WiFi(optional)

** The connection refers to“ GPRS/WiFi-stick User Manual”.

  1. COM1: Smart meter(optional)

  2. Remove the communication plate from the inverter.

  3. Loosen the swivel nut of the cable gland on the communication plate, remove the sealing plug and lead the stripped cable through the cable gland and communication plate, press the latch of the smart meter terminal and insert the stripped cable accordingly. Make sure the cable is connected firmly.
    Solplanet-ASW-1-3K-S-S-Series-14

  4. Insert the smart meter terminal to the socket, attach communication plate to the inverter with M4 screws, and tighten the swivel nut. Screwdriver type: PH2, torque: 1.6Nm.
    Solplanet-ASW-1-3K-S-S-Series-15

  5. If communication cover used, remove only one sealing plug of the cable gland to thread the cable. Detailed installation process follows above steps.

EU Declaration of Conformity

Within the scope of the EU directives:

  • Electromagnetic compatibility 2014/30/EU (L 96/79-106 ,March 29, 2014)(EMC)
  • Low voltage directive 2014/35/EU (L 96/357-374 ,March 29, 2014)(LVD)
  • Radio equipment directive 2014/53/EU (L 153/62-106 ,May 22, 2014)(RED)

AISWEI Technology (Shanghai) Co., Ltd. confirms herewith that the inverters mentioned in this document are in compliance with the fundamental requirements and other relevant provisions of the above mentioned directives.
The entire EU Declaration of Conformity can be found at www.aiswei- tech.com.

Technical Data

Technical Data ASW3000-S ASW3680-S ASW4000-S ASW5000-S
DC Input
Max. PV modules power(STC) 4500W 5520W 58 0V 6000W 7500W
Max. DC input voltage
MPP voltage range 80-550V
Max. DC input current 2×12A
Max. DC input short current 2×18A
Max. DC input current, per MPPT 12A

Number of MPPT/strings per MPPT
AC Output| 2/1
|
Rated active power| 3000W| 3680W| 4000W| 5000W
Max. apparent power| 3000VA| 3680VA| 4000VA| 5000VA
Rated grid voltage| 220/230V
Rated grid frequency| 50/60Hz
Max. AC output current| 15A| 16A| 20A| 22.7A
Adjustable displacement power factor| 0.8 ind  0.8 cap
Harmonic distortion (THD) at Pac.r

General Data

| < 3%
|
Dimensions (W x H x D)| 376×355×145mm
Weight| 11kg
< 25dB(A)@1m
Noise emission (typical)|
DC connection| Plug-in DC connector
AC connection| Plug-in AC connector
Communication| GPRS/WiFi , RS485(Optional)
Display| LED
Mounting| Wall mounting
Cooling| Convection
Operating temperature range| -25…+60℃
Relative humidity (non-condensing)| 4000m(   0…100%  )
Max. operating altitude| Derating above 3000m
Degree of protection| IP65
Climate Category| 4K4H
Topology| Transformer less

Contact

If you have any technical problems with our products, please contact our service.
We require the following information in order to provide you with the necessary assistance:

  • Inverter device type
  • Inverter serial number
  • Type and number of connected PV modules
  • Error code
  • Mounting location
  • Warranty card

EMEA
Service email: service.EMEA@solplanet.net
APAC
Service email: service.APAC@solplanet.net
LATAM
Service email: service.LATAM@solplanet.net
Aiswei Greater China
Service email: service.china@aiswei-tech.com
Hotline: +86 400 801 9996
Taiwan
Service email: service.taiwan@aiswei-tech.com
Hotline: +886 809089212
https://solplanet.net/contact-us/

Scan QR code:

Monitoring APP

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals