solplanet Single Phase Inverter Solar Installation Guide

June 7, 2024
solplanet

Solplanet Single Phase Inverter Solar Installation Guide

Solplanet Single Phase Inverter Solar

Safety Instruction

  1. The contents of this document will be updated irregularly for product version up- grade or other reasons. Unless otherwise specified,this document only works as guide. All statements, information and suggestions in this document do not constitute any guarantee.
  2. This product can only be installed, commissioned, operated and maintained by technicians who have carefully read and fully understood the user manual.
  3. This product must only be connected with PV modules of protection class II( in  accordance with IEC 61730, application class A).PV modules with a high capacitance to ground must only be used if their capacity does not exceed 1 F.Do not connect any sources of energyother than PV modules to the product.
  4. When exposed to sunlight, the PV modules generate dangerous high DC voltage which is present in the DC cable conductors and live components. Touching live DC cable conductors and live components can result in lethal injuries due to electric shock.
  5. Allcomponents must remain within their permitted operating ranges at all times.
  6. Theproduct complies with Electromagnetic compatibility 2014/30/EU, Low Voltage Directive 2014/35/EU and Radio Equipment Directive 2014/53/EU.

Mounting Environment

  1. Ensure that the inverter is installed out of the reach of children.

  2. To ensure best operating status and prolonged service life, the mounting ambient temperature of the inverter shoul dbe ≤40°C.

  3. To avoid direct sunlight, rain, snow, pounding on the inverter, it is suggested to mount the inverter in places with a top protective  roof. Do not completely cover the top of the inverter.
    a close up of a logo

  4. Themounting condition must be suitable for the weight and size of the inverter. The inverter is suitable to be mounted on solid wall that is vertical or tilted backwards
    (Max. 15°). It is not recommended to install the inverter on wall made of plaster-
    boards or similar materials. The inverter may make noise when working.

  5. To ensure adequate heat dissipation, the clearances between the inverter and other objects are recommended as follows:
    diagram

Scope of delivery

Inverter x1

Wall mounting bracket x1

DC connector x2

Communication cover x1 (optional)

Documentation x1

Screw accessory x1

GPRS/WiFi stick x1 (optional)

AC connector x1

Smart meter terminal x1

Magnetic ring x1 (optional)

Inverter’smounting

Use a Φ10mm bit to drill 3 holes at a depth  of about 70mm according to the location of the wall mounting bracket.

Insert wall plugs into the wall and fix the wall mounting bracket to the wall by screwing three self-tappingscrews(SW10).

Hang the inverter to the wall mounting bracket.

Secure the inverter to the wall mounting bracket using M4 screw.

V.ACconnection

All electrical installations must be done in accordance with all local and national rules.

  • Make sure that all DC switches and AC circuit breakers have been discon-
    nected before establishing electrical connection. Otherwise, the high
    voltage within the inverter may lead to electrical shock.

  • In accordance with safety regulations, the inverter need be grounded firmly. When poor groundconnection(PE) occurs, the inverter will report PE
    grounding error. Please check and ensure that the inverter is grounded firmly or contact AISWEI service.

  1. AC cable requirements are as follows. Insert the conductor into a suitable ferrule acc. to DIN 46228-4 and  crimp the contact .

Object

|

Description

|

 Value

---|---|---

A

|

External diameter

|

9-14mm

B

|

Copper conductor cross-section

|

2.5-6mm 2

C

|

Stripping length of the insulated conductors

|

13mm

D

|

Stripping length of the cable outer sheath

|

53mm

The PE conductor must be 2 mm longer than the Land N conductors.

  1. Loosen the swivel nut of AC connector. Insert the crimped conductors into correspondingterminalsandtighten screws  with the accompanied Allen key. Torque: 2.0Nm

  2. Insert the adapter to the socket element,  stuff the seal ring into the adapter and  tighten the swivel nut.

  3. Plug the AC connector into the socket for the AC connection.

  4. If required, you can connect a second protective conductor as potentiality bonding.

Object

|

Explanation

---|---

M4×10 screw

|

Screwdriver type: PH2,torque: 1.6Nm

OT terminal lug

|

Customer provided,type :M4

Grounding cable

|

Copper conductor cross-section: 2.5-6mm 2

VI.DC connection

  • Make sure PV modules have good insulation against ground.
  • On the coldest day based on statistical records, the Max. open-circuit volt- age of  the PV modules must not exceed the  Max. input voltage of the inverter.
  • Check the polarit of DC cables.
  • Ensure that DC switch has been disconnected.
  • Do not disconnect  DC connectors under load.
  1. Please refer to “DC Connector Installation Guide”.
  2. Before DC connection, insert the DC plug connectors with sealing plugs into DC input connectors of the inverter toensureprotectiondegree.

VI.DC connection

VII.Communication setup

  • Separate communication cables from power cables and serious interference sources.

  • The communication cables must be CAT-5E or higher-level shield cables. Pin
    assignment complies with EIA/TIA 568B standard. For outdoor use, the communication cables must be UV-resistant. The total length of communication
    cable cannot exceed 1000m.

  • If only one communication cable is connected, insert a sealing plug into the
    unused hole of sealingringofthecablegland.

  • Beforeconnecting communication cables, ensure the protective film or  communication plate attached to the communication opening on the inverter is sealed tightly.

  1. COM1: RS485(optional)
    RS485 cable pin assignment as below.

cable pin
Pin 1=TX_RS485A
Pin 2=TX_RS485B
Pin 3=NC
Pin 4=GND
Pin 5=GND
Pin 6=NC
Pin 7=+7V
Pin 8=+7V

2.Loosen the swivel nut of the cable gland
on the communication cover, remove
sealing plugs and lead the cable through
the swivel nut, sealing ring, communicationcover and magnetic ring.

VII.Communicationsetup

3.Insert the cable into the socket, attach the communication cover to inverter with M4 screws and tighten the swivel nut. Screwdriver type: PH2, torque: 1.6Nm.

COM2:GPRS/WiFi

PIN

|

PIN1

|

PIN2

|

PIN3

|

PIN4

---|---|---|---|---

Assignment

|

VCC

|

GND

|

RS485A

|

RS485B

diagram, engineering drawing

Theconnectionrefersto“GPRS/WiFi-stickUserManual”

Smart meter

  1. Remove the communication plate from the inverter.
    Smart meter

  2. Loosen the swivel nut of the cable  gland on     thecommunication plate, remove the sealing plug and lead  the strippedcable through the cable gland and communication plate, press the latch of the smart meter terminaland insert thestripped cable accordingly. Make sure the cableis connected firmly.
    Smart meter

  3. Insert the smart meter terminal to the socket, attach communication plate tithe inverter with M4 screws, and tighten the swivelnut.Screwdrivertype: PH2, torque: 1.6NmSmart meter

  4. If communication cover used, remove only one sealing plug of the cable gland to thread the cable.Detailed installation process follows above steps.

VIII.Commissioning

  • Check that the inverter is grounded reliably.

  • Check that the ventilationcondition surrounding the inverter is good.

  • Check that the grid voltage at the point of connection of the inverter is within
    thepermittedrange.

  • Check that the sealing plugs in DC connectors and the communication cable glandare sealed tightly.

  • Check that grid connection regulations and other parameter settings meet
    safety requirements.

  1. Switch on AC circuit breaker between the inverter and the grid.
  2. Switch on DC switch.
  3. When there is sufficient DC power applied and the grid conditions are met, the inverter will start to operate automatically.

IX.EU Declaration of Conformity

Within the scope of the EU directives: – Electromagnetic compatibility 2014/30/EU (L 96/79-106 ,March 29, 2014  (EMC)- Low voltagedirective 2014/35/EU (L 96/357-374 ,March 29, 2014 (LVD)- Radio equipment directive 2014/53/EU (L 153/62-106,May 22, 2014)(RED)
AISWEI New Energy Technology Jiangsu Co., Ltd. confirms here with that the

inerternmentionedin this document are in compliance with the fundamental requirements and other relevant provisions of the above mentioned directives. The entire EU Declaration of Conformity can be found at www.aiswei- tech.com.

X.Technical Data

Technical Data

|

ASW1000S-S

|

ASW1500S-S

|

ASW2000S-S

| ASW3000S-S
---|---|---|---|---

DC Input

|

Max. PV modules power(STC)

|

1500W

|

2250W

|

3000W

| 4500W

Max. DC input voltage

|

580V

MPP voltage range

|

80-550V

Max. DC input current

|

12A

Max. DC input short current

|

18A

Max. DC input current, per MPPT

|

12A

Number of MPPT/strings per MPPT

AC Output

|

1/1

|

Rated active power

| 1000W| 1500W|

2000W

| 3000W

Max. apparent power

| 1000VA| 1500VA|

2000VA

| 3000VA

Rated grid voltage

| 220/230V

Rated grid frequency

| 50/60Hz

Max. AC output current

| 5A| 7.5A|

10A

| 13.6A
Adjustable displacement power factor| 0.8 ind    0.8 cap
Harmonic distortion (THD) at Pac.r

General Data

| < 3%

|

Dimensions (W x H x D)

|

320×264×94mm

Weight|

6.5kg

< 25dB(A)@1m

Noise emission (typical)

|

DC connection

|

Plug-in DC connector

AC connection

|

Plug-in AC connector

Communication

|

GPRS/WiFi , RS485(Optional)

Display

|

LED

Mounting

|

Wall mounting

Cooling

|

Convection

Operating temperature range

|

-25…+60℃

Relative  humidity  (non-condensing)

|

4000m(           0…100%                  )

Max. operating altitude

|

Derating above 3000m

Degree of protection

|

IP65

Climate Category

|

4K4H

Topology

|

Transformerless

XI.Contact

If you have any technical problems with our products, please contact our service. We require the following information in order to provide you with the necessary  assistance:

-Inverterdevice type
-Inverterserialnumber
Type and number of connected PV modules
-Error code
-Mounting location
-Warrantycard
AISWEI New Energy Technology(Jiangsu)Co., Ltd.  Tel.: +865126937  0998Fax: +86 5126937 3159
Web: service.china@aiswei tech.com
Add.: Building 9, No. 198 Xiangyang Road, Suzhou, China

AISWEI Pty Ltd.

Tel.: +61 3909 88674 Add.: Level 40, 140 William Street, Melbourne VIC 3000

AISWEI B.V. Add.: Muiderstraat 9/G, 1011 PZ Amsterdam North Holland, Netherlands

http://www.aisweicloud.com/data/download.jsp

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

solplanet User Manuals

Related Manuals