Elitech EMG-20V Intelligent Digital Manifold Gauge User Manual

June 5, 2024
Elitech

Innovation Preceding Ali
Intelligent Digital Manifold
User Manual

Elitech EMG 20V Intelligent Digital Manifold Gauge

EMG – 20V| EMG – 40V

Preface and Precautions

1.1 Preface Thank you for purchasing the Elitech EMG series intelligent manifold gauge. Elitech digital manifold EMG series are not consumer products. Only qualified personnel trained in service and installation of A/C and/or refrigeration equipment shall use this product. Read and understand this user manual in its entirety before using your manifold to prevent injury or damage to you or your equipment.

12 Precautions

Descriptions

Incorrect operation may cause serious injury.
Incorrect operation may cause minor injury.
Incorrect operation may damage the device.

Caution

This product is not suitable for the maintenance of an ammonia (ammonia- containing) refrigerant system.
This product contains batteries. Do not place the product in a high- temperature environment or place it in a fire. Otherwise, it will explode.
Do not use this product during thunderstorms to avoid being struck by lightning causing life danger and product damage.
Strictly obey the safety cautions of the refrigeration system.

Please put on goggles and protective gloves while using the product. Please read the maintenance instruction of the system unit carefully before connecting the device to the system.
Please contact us in time if the product is damaged. Do not dismantle the product on your own to avoid further damage to the product that might cause battery fire or explosion.

When using other power adapters, the output voltage must not exceed 5V, otherwise, the instrument will be damaged.
The magnet embedded at the back of the product is to position the folded hook. Do not try to attach the product to any metal surface to avoid the product from falling and damage.

Environmental Protection
Please comply with local environmental protection policies. Refrigerants should not be directly discharged into the atmosphere and must be recycled with professional equipment. At the end of the product service life, please recycle it according to the local regulations. Do not dispose randomly to avoid environmental pollution.

Product Profile

2.1 Products Introduction EMG series of intelligent manifold gauges integrates the functions such as pressure and temperature measurement, pressure holding measurement, vacuum measurement, refrigerant weight measurement, and data logging. It is suitable for daily inspection and maintenance of the HVAC/R system.

  • Simple & easy operation with 5″ smart touch screen, clear data display.
  • Support App Operation by Bluetooth, data view, and analysis in real-time.
  • Support USB to read and export data.
  • Auto heat pump mode without changing the refrigerant hoses.
  • Detect the vacuum leakage, monitoring the vacuum value precisely.

The refrigerant weight measurement function work with Elitech refrigerant electronic scales. Please purchase the scale separately if necessary.

2.2 Product Overview

EMG-20V Product Details

  1. High-temperature clamp sensor interface ( with sealed plug )
  2. Low-temperature clamp sensor interface ( with sealed plug )
  3. Type-C power interface (with sealing plug)
  4. Power button
  5. High-pressure control valve
  6. Low-Pressure Control Valve
  7. Metal handles
  8. 5 inches IPS capacitive color touch screen
  9. Sight window
  10. Low-pressure refrigerant pipe interface ( 1/4 SAE female)
  11. High-pressure refrigerant pipe interface ( 1/4 SAE female)
  12. Refrigerant charging interface (1/4 SAE female)
  13. Refrigerant pipe bracket

Accessories

  1. Temperature clamps
  2. Vacuum transmitter
  3. Transmitter T-joints
  4. Transmitter bending joint

Specifications

3.1 Manifold

Pressure measurement range| -14.5-800psi/-1.0-55.2bar/-0.1-5.5MPa/-1.0-56.2kg/cm2
---|---
Accuracy| 0.5%FS
Resolution| 0.1psi/0.1bar/0.01MP3/0.1kg/cmi
Sampling frequency| 0.5s
Pressure unit| psi.   kg/cm2.   cmHg.   inHg.     bars      kPa,     MPa
Overload| 1000psi/70kg/cm2/69bar/6.8MPa
Pressure interface| 1/4SAE’3 3/8 SAE1 (EMG-20V)
Sensor interface| PS/2`2(the left interface is temperature and vacuum probe multiplexing)
USB Interface| Type-C
1(for data export and charging)
Charging parameter| SV2A
Battery capacity| S000mAh
Recording time| 500h
Screen parameter| 5″IPS capacitive touch screen
Dimensions| 25421546mm (EMG-20V) 25421571mm (EMG-40V)
Weight| 3.5Ib /1.59kg ( EMG-20V) 3.8Ib /1.73kg (EMG-40V)
Working temperature| -4-140°F/-20-60°C
Storage temperature| -40-176°F/-40-80°C

Data is exported via USB cable connected to a computer.

3.2 Vacum

Vacuum measurement range 0-19000 microns
Accuracy 0-10000 microns:10% of reading / ±10 micron 1000-19000

microns: 20% of reading
Resolution| 0-400                 1 microns
400-3000          10 microns
300010000        100 microns
10000-19000     250 microns
Vacuum unit| inHg.    Torr.    psia.    mbar.      mTorr.      micron. Pa.    kPa
Interface| 1/4SAE and 1/4SAET

3.3 Temperature Clamp

Temperature Measurement Range -40-150°C/-40-300°F
Accuracy ±01°C/±0.18°F
Resolution 0.1°C/°F
Temperature unit °C/°F/K
Interface PS/2

Quick Start Guide

4.1 Pressure and Temperature Measurement (for charging, recovery, maintenance monitoring, etc.)

  1. Press the power button to turn it on and enter the main menu.
  2. Connect the high and low-pressure temperature clamp on both sides of the mainframe and clamp the temperature sensor to measure the temperature of the corresponding system.
  3. Connect the high pressure and low-pressure interface of the system to the corresponding interface of the instrument.
  4. Click on the to enter the pressure-temperature measuring interface.
  5. Select the refrigerant by .
  6. Choose the corresponding working mode according to the current system, usually is the refrigeration mode.
  7. After the setup is done, you may check the accurate status of the system through the interface.

Only selected refrigerant scale models support the manifold gauge, please check with your local sales representatives for specific models.

4.2 Pressure Holding Measurement

  1. Fill the system with appropriate amount of nitrogen.
  2. Close the High-Pressure Side Valves.
  3. Connect the measuring system to the high-pressure side of the instrument.
  4. Click the  to enter the pressure-holding test.
  5. Click the and set the desired parameters.
  6. Press the to enter the pressure-holding test.

4.3 Vacuum Measurement

  1. Connect vacuum transmitters to the system and connect the communication cable to the manifold.

  2. Open the low-pressure side and high-pressure side valves. (applicable to EMG-20, EMG-40 series).
    Open the low-pressure side, high-pressure side valve, and vacuum valve, and close the charging valve. (applicable to EMG-40 series).

  3. Click the to then enter the vacuum interface and set the desired value and working time.

  4. Turn on the vacuum pump and pump to the set value.

  5. Click to set the alarm.

  6. Close all valves.

  7. Click the to enter the leak test.

Interface Details

5.1 Main interface

Elitech EMG 20V Intelligent Digital Manifold Gauge - Main
Interface

This is the main interface display once the device is turned on. There are “Pressure and Temperature Measurement”, “Pressure Holding Measurement”, “Electronic Refrigerant Scale” and “Setting” for selection. Click on the icon to enter each of the corresponding functions. The status bar on top of the page displayed the time, power/ battery indicator, wireless connection, and recording status.

Icon instructions

Bluetooth has been turned on Record function has been turned on
Bluetooth has been turned off Record function has been turned off

5.2 Setting Interface

Elitech EMG 20V Intelligent Digital Manifold Gauge - Setting
Interface

The setting interface includes “Unit Settings”, “Refrigerant Selection”, “Pressure Holding Setting”, “Leak Setting”; “System Setting”. Click the icon to enter the corresponding setting page.

5.2.1 Unit Settings

Elitech EMG 20V Intelligent Digital Manifold Gauge - Unit
setting

The unit of weight, temperature, pressure, and vacuum can be set. Click to go back to the previous page. The parameters are saved automatically.

5.2.2 Refrigerant Selection

Elitech EMG 20V Intelligent Digital Manifold Gauge - Refrigerant
Selection

User may select the desired refrigerant from the refrigerant selection box. The selected refrigerant will be added to Favourites automatically. A maximum of 20 refrigerants can be added.
If the number exceeds 20, the earliest refrigerant will be replaced with the latest refrigerant that has been selected.

5.2.3 Pressure Holding Settings

Pressure decay ratio, pressure holding time and temperature compensation can be set on this page. Click to go back to the previous page. The parameters are saved automatically.

5.2.4 Leak Setting

Elitech EMG 20V Intelligent Digital Manifold Gauge - Leak
settings

5.2.5 Record settings

Elitech EMG 20V Intelligent Digital Manifold Gauge - Record
Settings

User may enable/disable recording, recording intervals,s and clear record history on this page. Press the “Clear” button to clear the recorded history.
  The recording will stop automatically when it reaches the maximum capacity (500hrs). Please export the data in time and clear the recorded history.

5.2.6 System settings

Elitech EMG 20V Intelligent Digital Manifold Gauge - System
settings

Users may set the backlight brightness, backlight time, system auto-shutoff, and system language on this page.
Press to enter the next page to enable/disable Bluetooth and other wireless functions. Press to zero off the high and low pressure. Press to factory reset.

Please place the product in the atmospheric environment to calibrate zero.

5.3 Pressure and temperature measurement

Icon Instruction

Icon display status|

Instruction

---|---
Selected refrigerant| Refrigerant scale setting
refrigeration mode| Heat pump mode
Automatic mode|

The timer on the status bar on top starts timing automatically once the user enters this page. The purpose is to record the time user spend on this page.
Choose the right refrigerant first to avoid affecting the temperature calculation. Click to select the desired refrigerant. The selected refrigerant will be shown on the icon.
The pressure and temperature measurement interface to measure and display the pressure for the low-pressure side, the corresponding evaporation saturation temperature, low-pressure pipeline temperature and superheat as well as the pressure for the high-pressure side, the corresponding condensation saturation temperature, high-pressure pipeline temperature, and supercooling. Other than these, the different temperature of the low-pressure pipe and high-pressure pipe, and charging/recovery weight value can be measured and displayed as well. There are three measurement modes in the page: refrigeration mode, heat pump mode, and automatic mode.
Refrigeration mode : This is the regular mode.
Heat pump mode: high-pressure parameters and low-pressure parameters will be switching display positions.
Automatic mode : The display position of the corresponding parameters will be switched automatically when the pressure of the low-pressure side is 1 bar higher than the high-pressure side.

Switching between dial mode and curve mode.

Elitech EMG 20V Intelligent Digital Manifold Gauge - Curve
mode

Simply click on the middle of the dial meter to switch to curve mode. Click • to switch back to dial mode.

Charging and recovery function

Shows the current status and weight, press to enter the charging and recovery settings page. After the setting is done, click  to save the setting and return to the pressure-temperature measurement page.

There is no weight display if the current device is not connected to the refrigerant scale.

5.4 Pressure Holding Measurement

  • The timer on the status bar on top starts timing automatically once the user enters this page. The purpose is to record the time user spend on this page.

  • indicate the temperature compensation has been enabled or disabled. It can be set in the pressure-holding settings interface.
    Temperature compensation enabled: The device will monitor the current ambient temperature in real-time to reduce the pressure variation error caused by the change in the ambient temperature.

  • Temperature compensation disabled: Device calculate based on the measured pressure.

  • Click to set decay ratio and pressure-holding time and choose if to enable or disable the temperature compensation based on the actual situation.

  • Click to start the pressure-holding test. The countdown timer starts to elapse according to the duration that has been set. During the process, the device calculates the pressure variants and the deflation rate automatically based on the current and initial value. The test failed if the current value is less than the alarm value; the test passed if the current value is greater than the alarm value and exceeds the pressure-holding duration.

Switching between dial mode and curve mode

Elitech EMG 20V Intelligent Digital Manifold Gauge -
Dial

Simply click on the middle of the dial meter to switch to curve mode. Click to switch back to dial mode.

5.5 Vacuum Measurement

Elitech EMG 20V Intelligent Digital Manifold Gauge - Vacuum
Measurement

  • The timer on the status bar on top starts timing automatically once the user enters this page. The purpose is to record the time user spend on this page. The “Start” and “Alarm Setting” button is not displayed yet.
  • Click to select the preset vacuum target value. The device calculates the remaining time based on the targeted value and rate.

The remaining time rest is for reference only.

  • Working time : It is to set the current vacuum duration. The alarm goes off if the duration has exceeded without achieving the targeted value.
  • If the duration is not exceeded and the targeted value is reached, it prompts that the leak test can be performed.
  • The “Starts” and “Alarm Settings” are displayed now.
  • Click to enter the alarm setting interface
  • Click to enter the leak test based on the alarm set value. The parameters displayed in the vacuum interface will be switched to speed, test duration, and alarm value. During the leak test duration, if the leakage is greater than the set alarm value, the leak warning will be prompted. Otherwise, the test is passed.

Switching between dial mode and curve mode

Elitech EMG 20V Intelligent Digital Manifold Gauge - Dial
1

Simply click on the middle of the dial meter to switch to curve mode. Click to switch back to dial mode.

  1. This function has to work with the vacuum transmitter. Please plug the transmitter into the socket at the right of the device.
  2. The timer on the status bar will be reset if the Working Time was re-set.

5.6 Refrigerant Electronic Scale

Elitech EMG 20V Intelligent Digital Manifold Gauge - Refrigerant Elctronic
Scale

  • The timer on the status bar on top starts timing automatically once user enter this page. The purpose is to record the time user spend on this page.

This function works only if the device is connected to the refrigerant scale. It is to control and set up the scale.

  • Reset button, to reset the current weight.
  • Set to Charging mode
  • Set to Recovery Mode
  • To manually control the solenoid valve to be opened or closed. The OFF/ON button on the icon indicates the current status of the solenoid valve.
  • The solenoid valve automatically shuts off when the charging/recovery amount reaches the set target value. •
  • Displays the last set charging or recovery value.

Charging and recovery settings

Press to enter the charging/recovery setting interface The settings box will be displayed in two rows (1st row- lbs/kg; 2nd row- oz/g) according to the set weight: unit. Click on the rows one by one, key in the value with the keypad on the right. Click the “checked” to Save. Click to delete and reset the value.
Press the Return key, and the charging/ recovery setting is completed.

Min weight: 40g
Mox weight: the maximum measured weight of the current refrigerant scale.

5.7 APP QR code

https://play.google.com/store/apps/details?id=com.elitech.pgw

|

https://itunes.apple.com/cn/app/elitech-gauge/id1291636775?mt=8

---|---

Please check the APP operation instructions in Help.

5.8 Parameters

Parameter

|

Description

---|---
SH| Superheating
VSAT| Vapor saturation temperature
SLOW| Temperature of low side
SC| Sub-cooling
LSAT| Liquid saturation temperature
THIGH| Temperature of high side
T| T LOW THIGH
Factory| Factory reset

Parameter

|

Description

---|---
TCON| Temp compensation enable
TCOFF| Temp compensation disable
TC| Temp compensation
ETR| Estimated time remaining
Pc| Current pressure
Pi| Initial pressure
| Pi-Pc

Help

6.1 Troubleshooting

Problem| |

Possible causes/solutions

---|---|---
Failed to turn on the device| | Connect the device to the charger and try to turn it on after 5 minutes.
Touch screen doesn’t work| | Make sure the environment temperature is within the working temperature range (-20-60°C/-4-140°F).
The measured temperature shows ” —“| | Check if the temperature clamp is fully connected or if the
measuring temperature is out of the measurement range.
Pressure zone display “—“| | Pressure overload or uncalibrated
The pressure value shows large error| | Please place the device in the atmospheric environment to calibrate zero.
Vacuum displa y “—-“| | The system has a large leak, or the vacuum transmitter data is abnormal.
No response after clicking the interface button| | System crashes. Long press the Power button for 7s to restart the system.

6.2 Operation and Maintenance

  1. Storage: If do not use it for a long time, it is recommended to store the device with a fully charged battery or disconnect the battery from the device.
  2. Cleaning: Please wipe the device with a damp cloth. Do not wash the device directly. Do not use any corrosive solvents!
  3. Keep the thread of the connectors clean and remove the surface dirt regularly.
  4. Check the device for leaks regularly. It is recommended to check once a year.

6.3 Accessories and Spare Parts

Product and Accessories

|

Quantity

---|---
EMG-20V/EMG-40V intelligent manifold gauge| 1
Vacuum transmitter (T-joint)| 1
Temperature clamp| 2
Bent joint| 1
Refrigerant Hoses| 3(EMG-20V)
4(EMG-40V)
Power adapters| 1
Type-Cs Data line| 1
Instructions| 1

Read User Manual Online (PDF format)