Anern AN EVO 3600 Hybrid Inverter User Manual
- June 15, 2024
- Anern
Table of Contents
AN-SCI-EVO-3600
AN-SCI-EVO-6200
HYBRID INVERTER
ABOUT THIS MANUAL
1.1 Purpose
This manual describes the assembly, installation, operation and
troubleshooting of this unit. Please read this manual carefully before
installations and operations. Keep this manual for future reference.
1.2 Scope
This manual provides safety and installation guidelines as well as information
on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
-
Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
-
CAUTION –To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
-
Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
-
Toreduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning.
Turning off the unit will not reduce this risk. -
CAUTION — Only qualified personnel can install this device with battery.
-
NEVER charge a frozen battery.
-
For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It’s very important to correctly operate this inverter/charger.
-
Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
-
Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
-
One piece of 150A fuse is provided as over-current protection for the battery supply.
-
GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
-
NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
-
Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
INTRODUCTION
This is a multi-function inverter/charger, combining functions of inverter, solar charger and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
3.1 Features
Pure sine wave inverter
Configurable input voltage range for home appliances and personal computers
via LCD setting
Configurable battery charging current based on applications via LCD setting
Configurable AC/Solar Charger priority via LCD setting
Compatible to mains voltage or generator power
Auto restart while AC is recovering
Overload/ Over temperature/ short circuit protection
Smart battery charger design for optimized battery performance
Cold start function
3.2 Basic System Architecture
The following illustration shows basic application for this inverter/charger.
It also includes following devices to have a complete running system:
Generator or Utility.
PV modules
Consult with your system integrator for other possible system architectures
depending on your requirements.
This inverter can power all kinds of appliances in home or office environment,
including motor-type appliances such as tube light, fan, refrigerator and air
conditioner.
Figure 1 Hybrid Power System
3.3. Product Overview
- LCD display
- Status indicator
- Charging indicator
- Fault indicator
- Function buttons
- Power on/off switch
- AC input
- Main output
- Second output
- Battery input
- PV input
- Anti dust kit
- RS-232 communication port /WiFi-port
INSTALLATION
4.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged. You should have received the following items inside of
package:
The unit x 1
User manual x 1
4.2 Preparation
Before connecting all wirings, please take off bottom cover by removing two
screws as shown below.
4.3 Mounting the Unit
Consider the following points before selecting where to install:
Do not mount the inverter on flammable construction materials.
Mount on a solid surface
Install this inverter at eye level in order to allow the LCD display to be
read at all times.
For proper air circulation to dissipate heat, allow a clearance of approx. 20
om to the side and approx. 50 cm above and below the unit.
The ambient temperature should be between 0°C and 55°C to ensure optimal
operation.
The recommended installation position is to be adhered to the wall vertically.
Be sure to keep other objects and surfaces as shown in the diagram to
guarantee sufficient heat dissipation and to have enough space for removing
wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. It’s recommended to use M6 screws.
4.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it’s requested
to install a separate DC over-current protector or disconnect device between
battery and inverter. It may not be requested to have a disconnect device in
some applications, however, it’s still requested to have over-current
protection installed. Please refer to typical amperage in below table as
required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to
use appropriate cable for battery connection. To reduce risk of injury, please
use the proper recommended cable as below.
Recommended battery cable size:
Model | Wire Size | Cable (mm²) | Torque value (max) |
---|---|---|---|
3.6KW/6.2KW | 1 x 2AWG | 25 | 2 Nm |
Please follow below steps to implement battery connection:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as below chart.
- Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in
series.
CAUTION!! Before making the final DC connection or closing DC
breaker/disconnector, be sure positive (+) must be connected to positive (+)
and negative (-) must be connected to negative (-).
4.5 AC Input/Output Connection
CAUTION! Before connecting to AC input power source, please install a
separate AC breaker between inverter and AC input power source. This will
ensure the inverter can be securely disconnected during maintenance and fully
protected from over current of AC input. The recommended spec of AC breaker is
32A for 3.6KW and SOA for 6.2KW .
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings.
Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to
use appropriate cable for AC input connection. To reduce risk of injury,
please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model | Gauge | Cable (mm2) | Torque Value |
---|---|---|---|
3.6KW | 12 AWG | 4 | 1.2 Nm |
6.2KW | 10 AWG | 6 | 1.2 Nm |
Please follow below steps to implement AC input/output connection:
-
Before making AC input/output connection, be sure to open DC protector or disconnector first.
-
Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
-
Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. WARNING:
Be sure that AC power source is disconnected before attempting to hardwire it to the unit. -
Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
-
Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
-
Make sure the wires are securely connected.
CAUTION: Appliances such as air conditioner are required at least 2-3
minutes to restart because it’s required to have enough time to balance
refrigerant gas inside of circuits. If a power shortage occurs and recovers in
a short time, it will cause damage to your connected appliances. To prevent
this kind of damage, please check manufacturer of air conditioner if it’s
equipped with time-delay function before installation. Otherwise, this
inverter/charger will trig overload fault and cut off output to protect your
appliance but sometimes it still causes internal damage to the air
conditioner.
4.6 PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC
circuit breaker between inverter and PV modules.
WARNING! It’s very important for system safety and efficient operation to
use appropriate cable for PV module connection. To reduce risk of injury,
please use the proper recommended cable size as below.
Model | Gauge | Cable (mm2) | Torque Value |
---|---|---|---|
3.6KW/6.2KW | 1x12AWG | 4 | 1.2 Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
INVERTER MODEL | 3.6KW | 6.2KW |
---|---|---|
Max. PV Array Open Circuit Voltage | 500Vdc | |
PV Array MPPT Voltage Range | 90Vdc-450Vdc |
Take 250Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed as below table.
Solar Panel Spec. (reference)
– 250Wp
– Vmp: 30.1Vdc – Imp: 8.3A
– Voc: 37.7Vdc – Isc: 8.4A
– Cells: 60| SOLAR INPUT| Q’ty of panels| Total input
power
---|---|---|---
(Min in serial: 6 pcs, max. in serial: 13 pcs)
6 pcs in serial| 6 pcs| 1500W
8 pcs in serial| 8 pcs| 2000W
12 pcs in serial| 12 pcs| 3000W
13 pcs in serial| 13 pcs| 3250W
8 pieces in serial and 2 sets in parallel| 16 pcs| 4000W
10 pieces in serial and 2 sets in parallel| 20 pcs| 5000W
10 pieces in serial and 2 sets in parallel| 20 pcs| 6200W
12 pieces in serial and 2 sets in parallel| 24 pcs| 6500W
10 pieces in serial and 3 sets in parallel| 30 pcs| 7500W
PV Module Wire Connection
Please follow below steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Check correct polarity of wire connection from PV modules and PV input connectors. Then, connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector.
Recommended tool: 4mm blade screwdriver
4.7 Final Assembly
After connecting all wirings, please put bottom cover back by screwing two
screws as shown below.
4.8 Communication Connection
-
Wi-Fi cloud communication (option):
Please use supplied communication cable to connect to inverter and Wi-Fi module. Download APP and installed from APP store, and Refer to “Wi-Fi Plug Quick Installation Guideline” to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer. -
GPRS cloud communication (option):
Please use supplied communication cable to connect to inverter and GPRS module, and then applied external power to GPRS module. Download APP and installed from APP store, and Refer to “GPRS RTU Quick Installation Guideline” to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.
RGB Light (option )
- Battery Mode:red Light
- Utility Mode:blue Light
- PV Mode:purple Light
OPERATION
5.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch (located on the button of the case) to turn on the unit.
5.2 Operation and Display Panel
The operation and display panel, shown in below chart, is on the front
panel of the inverter. It includes three indicators, four function keys and a
LCD display, indicating the operating status and input/output power
information.
LED Indicator
LED Indicator | Messages |
---|---|
INV/AC | Green |
Flashing | Output is powered by battery or PV in battery mode. |
CHG | Green |
Flashing | Battery is charging. |
FAULT | Red |
Flashing | Warning condition occurs in the inverter. |
Function Keys
Function Key | Description |
---|---|
ESC | To exit setting mode |
UP | To go to previous selection |
DOWN | To go to next selection |
ENTER | To confirm the selection in setting mode or enter setting mode |
5.3 LCD Display Icons
Icon | Function description |
---|
Input Source Information
| Indicates the AC input.
| Indicates the PV input
| Indicate input voltage, input frequency, PV voltage, charger current (if PV
in charging for 3.6KW models), charger power, battery voltage.
Configuration Program and Fault Information
| Indicates the setting programs.
| Indicates the warning and fault codes.
Warning: flashing with warning code.
Fault: lighting with fault code
Output Information
| Indicate output voltage, output frequency, load percent, load in VA, load
in Watt and discharging current.
Battery Information
|
Load Information
| Indicates overload.
Mode Operation Information
| Indicates unit connects to the mains.
| Indicates unit connects to the PV panel.
| Indicates load is supplied by utility power.
| Indicates the utility charger circuit is working.
| Indicates the DC/AC inverter circuit is working.
Mute Operation
| Indicates unit alarm is disabled.
5.4 LCD Setting
After pressing and holding ENTER button for 3 seconds, the unit will enter
setting mode. Press “UP” or “DOWN” button to select setting programs. And
then, press “ENTER” button to confirm the selection or ESC button to exit.
Setting Programs:
Program | Description | Selectable option |
---|---|---|
0 | Exit setting mode | |
1 | Output source priority: To configure load power source priority |
will provide power to the loads as first priority.
Solar and battery energy will provide power to the loads only when utility
power is not available.
| Solar energy provides power to the loads as first priority.
If solar energy is not sufficient to power all connected loads, utility will
supply power to the loads at the same time.
Battery provides power to the loads only when any one condition happens:
– Solar energy and utility is not available.
– Solar energy is not sufficient and utility is not available.
| Solar energy provides power to the loads as first priority.
If solar energy is not sufficient to power all connected loads, battery energy
will supply power to the loads at the same time.
Utility provides power to the loads only when battery voltage drops to either
low-level warning voltage or the setting point in program 12.
| Solar energy provides power to the loads as frist priority , if solar energy
is not sufficient
to power all connected loads , utility energy will supply power to the loads
at the same time. The battery only supplies energy to the load as a backup
power.
2| Maximum charging current: To configure total charging current for solar and
utility chargers.
(Max. charging current = utility charging current + solar charging current)|
---|---|---
3| AC input voltage range| | If selected, acceptable AC input voltage range
will be within 90-280VAC.
If selected, acceptable AC input voltage range will be within 170-280VAC.
5| Battery type|
|
If “User-Defined” is selected, battery charge voltage and low DC cut-
offvoltage can be set up in program 26, 27 and 29.
When the solar energy exists,Set this item to LIB, and the lithiumbattery will
be activated for 3 second.
6| Auto restart when overload occurs|
7| Auto restart when over temperature occurs
9| Output frequency
10| Output voltage
11| Maximum utility charging current
Note: If setting value in program 02 is smaller than that in program in 11,
the inverter will apply charging current from program 02 for utility charger.|
---|---|---
12| Setting voltage point back to utility source when selecting “SBU priority”
or “Solar first” in program 01.|
13| Setting voltage point back to battery mode when selecting “SBU priority”
or
“Solar first” in program 01.|
---|---|---
16| Charger source priority: To configure charger source priority| If this
inverter/charger is working in Line, Standby or Fault mode, charger source can
be programmed as below:
---|---|---
| Solar energy will charge battery as first priority.
Utility will charge battery only when solar energy is not available.
Solar energy and utility will charge battery at the same time.
Solar energy will be the only charger source no matter utility is available or
not.
If this inverter/charger is working in Battery mode or Power saving mode, only
solar energy can charge battery. Solar energy will charge battery if it’s
available and sufficient.
18| Alarm control|
19| Auto return to default display screen| | If selected, no matter how users
switch display screen, it will automatically return to default display screen
(Input voltage /output voltage) after no button is pressed for 1 minute.
If selected, the display screen will stay at latest screen user finally
switches.
20| Backlight control|
22| Beeps while primary source is interrupted|
---|---|---
23| Overload bypass:
When enabled, the unit will transfer to line mode if overload occurs in
battery mode.
25| Record Fault code
26| Bulk charging voltage (C.V voltage)| If self-defined is selected in
program 5, this program can be set
up. Setting range is from 25.0V to 29.0V for 3.6KW model and
48.0V to 58.0v for 6.2KW model. Increment of each click is 0.IV.
27| Floating charging voltage|
If self-defined is selected in program 5, this program can be set up.Setting
range is from 25.0V to 29.0V for 3.6Kw model and 48.0V to 58.0V for 6.2KW
model. Increment of each click is 0. IV.
29| Low DC cut-off voltage|
| | If self-defined is selected in program 5, this program can be set up.
Setting range is from 20.0V to 24.0V for 3.6KW model and
40.0V to 48.0V for 6.2KW model. Increment of each click is
0.1V. Low DC cut-off voltage will be fixed to setting value no matter what
percentage of load is connected.
---|---|---
30| Battery equalization|
If “Flooded” or “User-Defined” is selected in program 05, this program can be
set up.
31| Battery equalization voltage|
Setting range is from 25.0V to 31.5V for 3.6KW model and 48.0V
to 61.0V for 6.2KW model. Increment of each click is 0.1V.
33| Battery equalized time|
| Setting range is from 5min to 900min. Increment of each click is 5min.
34| Battery equalized timeout| Setting range is from 5min to 900 min.
Increment of each click is 5 min.
35| Equalization interval| Setting range is from 0 to 90 days. Increment of
each click is 1 day
36| Equalization activated immediately|
If equalization function is enabled in program 30, this program can be set up.
If “Enable” is selected in this program, it’s to activate battery equalization
immediately and LCD main page will shows “ “. If “Disable” is selected, it
will cancel equalization function until next activated equalization time
arrives based on program 35 setting. At this time, “ ” will not be shown in
LCD main page.
37| GRID-tie operation| | Inverter operates only in off-grid mode. Solar
energy provides powerto the loadsas first priority and charging second
Inverter operates hybrid mode. Solar energy provides power to the loads as
first priority and charging second Excess energy feed to grid.
38| GRID-tie current|
---|---|---
39| Led pattern light
41| Dual output
42| Enter the dual output functional voltage point|
Setting range is from 20.0V to 23.0V for 24VDC model and 40.0V to 46.0 V for
48VDC model. Increment of each click is 0.1V.
5.5 Display Setting
The LCD display information will be switched in turns by pressing “UP” or
“DOWN” key. The selectable information is switched as below order: input
voltage, input frequency, PV voltage, charging current, charging power,
battery voltage, output voltage, output frequency, load percentage, load in
Watt, load in VA, load in Waitt, DC discharging current, main CPU Version.
Selectable information | LCD display |
---|
Charged state, and the power is less than lkw
Input voltage=222V ,
PV voltage=168V,
Battery voltage=25V, Output voltage=222V, Load in Watt=188W,
Chg(Flashing), Inv/ac(bright)|
Input voltage=223V ,
PV current=2.3A,
Battery current=20A,
Output voltage=224V, Load in VA=188VA,
Chg(Flashing), Inv/ac(bright)
Input voltage=223V ,
Pv ntc temperture=71.0°C, Battery voltage= 25V,
Inv ntc temperture=35.0°C, Load percentage=12%, Chg(Flashing), Inv/ac(bright)
Input frequency=50.0Hz , PV power=0.434KWh, Battery current=20A, Output
frequency=50.0Hz, Load in watt=188W, Chg(Flashing), Inv/ac(bright)|
---|---
Charged state, and the power is greater than 1kw
Input voltage=222V , PV voltage=168V, Battery voltage=25V, Output
voltage=222V, Load in Watt=1.18KW, Chg(Flashing), Inv/ac(bright)|
Input voltage=224V , PV current=8.6A, Battery current=12.5A, Output
voltage=222V, Load in VA=1.88KVA, Chg(Flashing), Inv/ac(bright)
Input voltage=223V , Pv ntc temperture=71.0°C, Battery voltage=25V, Inv ntc
temperture=35.0°C, Load percentage=82%, Chg(Flashing), Inv/ac(bright)
Input frequency=50.0Hz , PV power=1.434KWh, Battery current=20A, Output
frequency=50.0Hz, Load in watt=1.88KW, Chg(Flashing), Inv/ac(bright)
Discharged state, and the power is less than 1kw
Input voltage=0V ,
PV voltage=0V,
Battery voltage=25V,
Output voltage=222V,
Load in Watt=188W,
Chg(turn off), Inv/ac(Flashing)|
Input voltage=O0V ,
PV current=0A,
Battery current=12.5A,
Output voltage=222V,
Load in VA=188VA,
Chg(turn off), Inv/ac(Flashing)
Input voltage=0V ,
Pv ntc temperture=60.0°C,
Battery voltage=24V,
Inv ntc temperture=36.0°C,
Load percentage=13%,
Chg(turn off), Inv/ac(Flashing)
Input frequency=0Hz ,
PV power=0KWh,
Battery current=12A,
Output frequency=50.0Hz,
Load in watt=188W,
Chg(turn off), Inv/ac(Flashing)
Discharged state, and the power is greater than 1kw
Input voltage=0V ,
PV voltage=0V,
Battery voltage=25V,
Output voltage=222V,
Load in Watt=1.88KW,
Chg(turn off), Inv/ac(Flashing)|
Input voltage=0V ,
PV current=0A,
Battery current=111A,
Output voltage=222V,
Load in VA=1.88KVA,
Chg(turn off), Inv/ac(Flashing)
Input voltage=0V ,
Pv ntc temperture=68.0°C,
Battery voltage=24V,
Inv ate temperture=30.0°C,
Load percentage=81%,
Chg(turn off}, Inv/ac(Flashing)
Input frequency=0Hz ,
PV power=0KWh,
Battery current=111A,
Output frequency=50 .0Hz,
Load in watt=1.21KW,
Chg(turn off), Inv/ac(Flashing)
Main CPU version checking
5.6 Operating Mode Description
Operation mode | Selectable information | LCD display |
---|---|---|
Stanby mode | Input voltage=222V , PV voltage=210V, Battery voltage=25V, Output | |
voltage=0V, Load in Watt=OW, Chg(Flashing), Inv/ac(bright) | ![Anern AN EVO |
3600 Hybrid Inverter - Symbol 53](https://manuals.plus/wp-
content/uploads/2023/12/Anern-AN-EVO-3600-Hybrid-Inverter-Symbol-53.jpg)When
working in Grid-Tie mode,the will be flash 3S/times.
Input voltage=223V , PV voltage=OV, Battery voltage=25V, Output voltage=OV,
Load in Watt=OW, Chg(Flashing), Inv/ac(bright)
Input voltage=0V , PV voltage=210V, Battery voltage=25V, Output voltage=OV,
Load in Watt=0W, Chg(Flashing)
Line mode| Input voltage=224V , PV current=8.6A, Battery current=12.5A, Output
voltage=222V, Load in VA=1.88KVA, Chg(Flashing), Inv/ac(bright)
Input voltage=224V , PV voltage=OV, Battery voltage=25V, Output voltage=222V,
Load in Watt=188W, Chg(Flashing), Inv/ac(bright)
Grid-Tie Operation| Input voltage=224V , PV current=8.6A, Battery
current=12.5A, Output voltage=222V, Load in VA=1.88KVA, Chg(Flashing),
Inv/ac(bright)
Battery mode| Input voltage=OV ,
PV voltage=180V,
Battery voltage=25V,
Output voltage=230V,
Load in Watt=388w,
Inv/ac(Flashing)|
Input voltage=OV ,
PV voltage=180V,
Battery voltage=25V,
Output voltage=230V,
Load in Watt=388W,
Chg(Flashing), Inv/ac(Flashing)
5.7 Battery Equalization Description
Equalization function is added into charge controller. It reverses the buildup
of negative chemical effects like stratification, a condition where acid
concentration is greater at the bottom of the battery than at the top.
Equalization also helps to remove sulfate crystals that might have built up on
the plates. If left unchecked, this condition, called sulfation, will reduce
the overall capacity of the battery. Therefore, it’s recommended to equalize
battery periodically.
How to Apply Equalization Function
You must enable battery equalization function in monitoring LCD setting
program 30 first. Then, you may apply this function in device by either one of
following methods:
- Setting equalization interval in program 35.
- Active equalization immediately in program 36.
When to Equalize
In float stage, when the setting equalization interval (battery equalization
cycle) is arrived, or equalization is active immediately, the controller will
start to enter Equalize stage.
Equalize charging time and timeout
In Equalize stage, the controller will supply power to charge battery as
much as possible until battery voltage raises to battery equalization voltage.
Then, constant-voltage regulation is applied to maintain battery voltage at
the battery equalization voltage. The battery will remain in the Equalize
stage until setting battery equalized time is arrived.
However, in Equalize stage, when battery equalized time is expired and battery voltage doesn’t rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.
5.8 Fault Reference Code
Fault Code | Fault Event | Icon on |
---|---|---|
1 | Fan is locked when inverter is off. | ![Anern AN EVO 3600 Hybrid Inverter - |
Fig 18](https://manuals.plus/wp-content/uploads/2023/12/Anern-AN-EVO-3600
-Hybrid-Inverter-Fig-18.jpg)
2| Over temperature
3| Battery voltage is too high
4| Battery voltage is too low
5| Output short circuited or over temperature is detected by internal
converter components.
6| Output voltage is too high.
7| Overload time out
8| Bus voltage is too high
9| Bus soft start failed
51| Over current or surge
52| Bus voitage is too low|
53| Inverter soft start failed
55| Over DC voltage in AC output
57| Current sensor failed
58| Output voltage is too low
59| PV voltage is over limitation
5.9 Warning Indicator
Warning Code| Warning Event| Audible Alarm| Icon
flashing
---|---|---|---
1| Fan is locked when inverter is on.| Beep three times every second|
3| Battery is over-charged| Beep once every second
4| Low battery| Beep once every second
7| Overload| Beep once every 0.5 second
10| Output power derating| Beep twice every 3 seconds
15| PV energy is low.| Beep twice every 3 seconds
| Battery equalization| None
| Battery is not connected| None
CLEARANCE AND MAINTENANCE FOR ANTI-DUST KIT
6.1 Overview
Every inverter is already installed with anti-dusk kit from factory. Inverter
will automatically detect this kit and activate internal thermal sensor to
adjust internal temperature. This kit also keeps dusk from your inverter and
increases product reliability in harsh environment.
6.2 Clearance and Maintenance
Step 1: Please loosen the screw in counterclockwise direction on the top of
the inverter. Step 2: Then, dustproof case can be removed and take out air
filter foam as shown in below chart.
Step 3: Clean air filter foam and dustproof case. After clearance, re-assemble
the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL | 3.6KW | 6.2 KW |
---|---|---|
Input Voltage Waveform | Sinusoidal (WM ty or generator) | |
Nominal Input Voltage | 230Vac | |
Low Loss Voltage | 170Vact7V (UPS); |
90Vac:k7V (Appliances)
Low Loss Return Voltage| 180Vact7V (UPS);
100Vac±7V (Appliances)
High Loss Voltage| 280Vaci7V
High Loss Return Voltage| 270Vac:k7V
Max AC Input Voltage| 300Vac
Nominal Input Frequency| 50Hz / 60Hz (Auto detection)
Low Loss Frequency| 4011Hz
Low Loss Return Frequency| 42±1Hz
High Loss Frequency| 65±1Hz
High Loss Return Frequency| 63e1Hz
Output Short grant Protection| arcuit Breaker
Efficiency (Line Mode)| >95% ( Rated R load, battery full charged )
Transfer Time| 10ms typical (UPS);
20ms typical (Appliances)
Output power derating:
When AC input voltage drops to 170V, the output power will be derated.|
Table 2 Inverter Mode Specifications
INVERTER MODEL | 3.6KW | 6.2KW |
---|---|---|
Rated Output Power | 3.6KW | 6.2KW |
Output Voltage Waveform | Pure Sine Wave | |
Output Voltage Regulation | 230Vac:t5% | |
Output Frequency | 50Hz | |
Peak Efficiency | 93% | |
Overload Protection | 3s@2150% load; 5s@101%-150% load | |
Surge Capacity | r rated power for 5 seconds | |
Nominal DC Input Voltage | 24Vdc | 48Vdc |
Cold Start Voltage | 23.0Vdc | 46.0Vdc |
Low DC Warning Voltage @ load < 50%
@ load a 50%| 22.0Vdc
21.0Vdc| 44.0Vdc
42.0Vdc
Low DC Warning Return Voltage @ load < 50%
@ load ? 50%| 22 5Vdc
22.0Vdc| 45.0Vdc
44.0Vdc
Low DC Cut-off Voltage @ load < 50%
@ load a 50%| 20.5Vdc
20.0Vdc| 41.0Vdc
40.0Vdc
High DC Recovery Voltage| 32Vdc| 62Vdc
High DC Cut-off Voltage| 33Vdc| 63Vdc
No Load Power Consumption| 30W| 50W
Table 3 Two Load Output Power
INVERTER MODEL | 3.6KW | 6.2KW |
---|---|---|
Full Load | 3600W | 6200W |
Maximum Main Load | 3600W | 6200W |
Maximum Second Load(battery model) | 1200W | 2066W |
Main Load Cut Off Voltage | 22VDC | 44VDC |
Main Load Return Voltage | 26VDC | 52VDC |
Table 4 Charging Mode Specifications
Utility Charging Mode|
---|---
INVERTER MODEL| 3.6KW| | 6.2KW
Charging Algorithm| | 3-Step
AC Charging Current (Max)| 100Amp (@Vup=230Vac)| 100Amp (@Vup=230Vac)
Bulk Charging Voltage| Flooded Battery| 29.| | 58.
AGM / Gel Battery| 28.| | 56.
Floating Charging Voltage| 27Vdc| | 54Vdc
Charging Curve|
MPPT Solar Charging Mode|
INVERTER MODEL| 3.6KW| | 6.2KW
Max. PV Array Power| 6200W| | 6500W
Nominal PV Voltage| 240Vdc| | 360Vdc
PV Array MPPT Voltage Range| | 90Vdc-450Vdc
Max. PV Array Open Circuit Voltage| | 500Vdc
Max Charging Current
(AC charger plus solar charger)| 120Amp| | 120Amp
Table 5 Grid – Tie Operation
INVERTER MODEL | 3.6KW | 6.2KW |
---|---|---|
Nominal Output Voltage | 220/230/240VAC | |
Feed-in Grid Voltage Range | 195 -253VAC | |
Feed-in Grid Frequency Range | 49-51+1Hz/59-61±1Hz | |
Nominal Output Current | 15.7A | 26.9A |
Power Factor Range | >0.99 | |
Maximum Conversion Efficiency (DC/AC) | 97% |
Table 6 General Specifications
INVERTER MODEL | 3.6KW | 6.2KW |
---|---|---|
Safety Certification | CE | |
Operating Temperature Range | -10°C to 50°C | |
Storage temperature | -15°C- 60°C | |
Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
Dimension (DWH), mm | 420350110mm | 450`350*110mm |
Net Weight, kg | 9 | 10 |
TROUBLE SHOOTING
Problem| LCD/LED/Buzzer| Explanation / Possible cause| What
to do
---|---|---|---
Unit shuts down automatically
during startup process.| LCD/LEDs and buzzer will be active for 3 seconds and
then complete off.| The battery voltage is too low (<1.91V/Cell)| 1.Re-charge
battery.
2.Replace battery.
No response after power on.| No indication,| 1.The battery voltage is far too
low. (<1.4V/Cell)
2.Internal fuse tripped.| 1.Contact repair center for replacing the fuse.
2.Re-charge battery.
3.Replace battery.
Mains exist but the
unit works in mode. battery| Input voltage is displayed as 0 on the LCD and
green LED is flashing.| Input protector is tripped| Check if AC breaker is
tripped and AC wiring is connected well
Green LED is flashing.| Insufficient quality of AC power. (Shore or
Generator)| 1.Check if AC wires are too thin and/or too long.
2.Check if generator (if applied) is working well or if input voltage range
setting is correct. (UPSOAppliance)
Green LED is flashing.| Set “Solar First” as the priority of output source.|
Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.|
LCD display and LEDs are flashing| Battery is di nnected.| Check if battery
wires are connected well.
Buzzer beeps continuously and red LED is on.| Fault code 07| Overload error.
The inverter is overload 110% and time is up.| Reduce the connected load by
switching off some
equipment
Fault code 05| Output short drcuited.| Check if wiring is connected well and
remove abnormal load.
Temperature of internal converter component is over 120°C.| Check whether the
air flow of the unit is blocked or whether the ambient temperature is too
high.
Fault code 02| Internal temperature of inverter component is over 100°C.
Fault code 03| Battery is over-charged.| Return to repair center.
The battery voltage is too high.| Check if spec and quantity of batteries are
meet requirements.
Fault code 01| Fan fault| Replace the fan.
Fault code 06/58| Output abnormal (Inverter voltage below than 190Vac or is
higher than 260Vac)| 1.Reduce the connected load.
2.Return to repair center
Fault code
08/09/53/57| Internal components failed.| Return to repair center.
Fault code 51| Over current or surge.| Restart the unit, if the error happens
again, please return to repair center.
Fault code 52| Bus voltage is too low.
Fault code 55| Output voltage is unbalanced.
Appendix: Approximate Back-up Time Table
Model| Load (W)| Backup Time @ 24Vdc 100Ah (min)| Backup
Time @ 24Vdc 200Ah (min)
---|---|---|---
3.6KW| 300| 449| 1100
600| 222| 525
900| 124| 303
1200| 95| 227
1500| 68| 164
1800| 56| 126
2100| 48| 108
2400| 35| 94
2700| 31| 74
3200| 28| 67
3600| 25| 60
4200| 22| 53
Model| Load (W)| Backup Time @ 48Vdc 100Ah (min)| Backup
Time @ 48Vdc 200Ah (min)
---|---|---|---
6.2KW| 500| 613| 1288
1000| 268| 613
1500| 158| 402
2000| 111| 271
2500| 90| 215
3200| 76| 182
3500| 65| 141
4000| 50| 112
4500| 44| 100
5000| 40| 90
6200| 36| 80
7200| 30| 65
Note:
-
Backup time depends on the quality of the battery, age of battery and type of battery.
Specifications of batteries may vary depending on different manufacturers. -
The final interpretation right of this product belongs to the company.
Web:anern-group.com
Email: group@anern.com
WhatsApp: +86 13570048098
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>