superbrightleds com BRI816-B-D Fixture-Mounted Motion Sensor User Manual

June 5, 2024
superbrightleds com

superbrightleds logo User Manual
BRI816-B-Dsuperbrightleds com BRI816 B D Fixture Mounted Motion Sensor
-

Important: Read all instructions prior to installation.
Fixture-Mounted Motion Sensor

Safety and Notes

  • Product should be installed and serviced in accordance with applicable national, state, and local building and electrical codes.
  • To reduce the risk of electric shock, ensure that the main power source and circuit breakers are switched off before performing any installation or wiring procedures.

Specifications

Model BRI816-B-D
Maximum Detection Radius 26.2 ft (8 m)
Maximum Mounting Height 49.2 ft (15 m)
Operating Temperature -40°–158° F (-40°–70° C)
Dimming 0–10 V¹

¹Lights that use a 1–10 V dimming driver will not completely turn off when at the zero setting on the sensor.

Check product label for specific electrical specifications related to installation.
Improper installation will void warranty.

DIP Switch Settings

superbrightleds com BRI816 B D Fixture Mounted Motion Sensor -
1

Setting| Sensitivity| Time| Light| Standby Level| Standby Time
---|---|---|---|---|---
Switch Pair Position| 1 and 2| 3 and 4| 5 and 6| 7 and 8| 9 and 10
| 20%| 10 seconds| disabled| 0| always on
| 50%| 1 minute| 10 lx| 10| 1 minute
| 75%| 5 minute| 30 lx| 30| 30 minute
| 100%| 15 minute| 50 lx| 50| 60 minute

Sensitivity adjusts detection area.
Time adjusts the amount of time between when motion is detected and when the light enters standby mode.
Light adjusts the daylight threshold which allows the light to stay off if motion is detected and the room is already sufficiently illuminated.
Standby Level adjusts the dimming level of the light during standby mode. It should be noted that “0” setting on a 1–10 V light will result in the light being set at 10% as the driver in this case cannot dim beyond this level.
Standby Time adjusts the amount of time the light stays in standby mode before shutting off completely.

Installation

  1. Remove supply power from fixture.
  2. Remove two bolts to open access panel.
  3. Drill 1 5/16 in. hole in pre marked area.
  4. Place module through hole, then install rubber gasket and locking nut.
  5. Plug sensor into module.
  6. Wire using wiring diagram below.
  7. Close and secure panel then reapply supply power.

Sensor Coverage

Wiring Diagram

Rev Date: V1 11/04/2019
4400 Earth City Expy, St. Louis, MO 63045
866-590-3533 superbrightleds.com

superbrightleds com BRI816 B D Fixture Mounted Motion Sensor -
9

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

superbrightleds com User Manuals

Related Manuals