Carrier IIK-90INDHSG-01 Inducer Housing Kit Instruction Manual
- June 5, 2024
- Carrier
Table of Contents
INDUCER HOUSING KIT
For Single-Stage, Two-Stage, and Modulating Gas Furnaces
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use
can cause an explosion, fire, electrical shock, or other conditions which may
cause death, personal injury, or property damage. Consult a qualified
installer, service agency, or your distributor or branch for information or
assistance. The qualified installer or agency must use factory-authorized kits
or accessories when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work
gloves. Have a fire extinguisher available. Read these instructions thoroughly
and follow all warnings or cautions included in the literature and attached to
the unit. Consult local building codes, the current editions of the National
Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1, and the National Electrical Code
(NEC) NFPA 70.
In Canada, refer to the current editions of the National Standards of Canada
CAN/CSA-B149.1 and .2 Natural Gas and Propane Installation Codes, and
Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety alert symbol. When you see
this symbol on the unit and in instructions or manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION.
These words are used with the safety alert symbol. DANGER identifies the most
serious hazards which will result in severe personal injury or death. WARNING
signifies hazards that could result in personal injury or death. CAUTION is
used to identify unsafe practices which may result in minor personal injury or
product and property damage.
NOTE is used to highlight suggestions that will result in enhanced
installation, reliability, or operation.
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death and/or
property damage.
The ability to properly perform maintenance on this equipment requires certain
knowledge, mechanical skills, tools, and equipment. If you do not possess
these, do not attempt o perform any maintenance on this equipment other than
those procedures recommended in the Owner’s Manual.
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow instructions could result in personal injury, death or
property damage.
Improper installation, adjustment, alteration, service, maintenance, or use
can cause carbon monoxide poisoning, explosion, fire, electrical shock, or
other conditions, which could result in personal injury or death. Consult your
distributor or branch for information or assistance. The qualified installer
or agency must use only factory-authorized kits or accessories when servicing
this product.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing the system, the main electrical
disconnect switch must be in the OFF position and install a lockout tag. There
may be more than one electrical supply to the furnace. Check accessories and
cooling unit for additional electrical supplies that must be shut off during
furnace servicing. Lockout and tag switch with a suitable warning label.
Verify proper operation after servicing.
INTRODUCTION
Fig. 1 – ECM Inducers
A13034
This instruction covers the installation of the single-speed, two-speed, and
modulating inducer assemblies on condensing 35-in. (889 mm) tall, high-
efficiency units.
The inducer should be replaced when the motor is seized, open, shorted or
grounded. The PSC motor is equipped with an internal thermal overload. If the
overload is open, allow time (several minutes) for the overload to reset.
ECM inducer motors do not have an internal overload and are internally
protected through the electronics in the motor controller. There are four (4)
different PSC inducer assemblies to service all single-stage and 2-stage
furnaces with PSC inducers.
Each of the four (4) PSC motors has a different horsepower and/or rpm range
required for the various size furnaces.
The motor supplied in the kit for furnaces with PSC inducers is a two-speed
inducer motor. Single-stage operation is achieved through the use of an
adapter harness included with the kit.
There is one (1) kit for modulating furnaces. The replacement assembly may
look different from the assembly installed on the furnace, but operates the
same as the original motor. The new modulating furnace inducer kit does not
require an adapter harness, see Fig. 1.
Refer to Table 2 for the correct furnace and kit combination.
DESCRIPTION AND USAGE
Use this inducer assembly kit to replace a failed inducer assembly. The
assembly cannot be disassembled to remove or repair individual components. The
kit contains the following items shown in Table 1.
NOTE: Inducer assembly consists of motor, wheel, inducer housing, inlet
gasket, inlet choke plate and condensate drain gasket. It will be necessary to
reuse some components from the old inducer assembly.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
Using the incorrect inducer motor assembly could result in no pressure switch
operation, poor ignition, poor combustion, erratic burner operation/burner
pulsations, flame roll-out or noise.
Table 1 – Kit Contents
Description
|
Quantity
---|---
Inducer Assembly| 1
Installation Instructions| 1
Inlet Choke Plate (PSC and Ultra Low NOx only)| 1-2
Inducer Outlet Restrictor (40,000 input only)| 1
Two-stage to Single-stage Adapter Harness (PSC only except 140,000 input)| 1
1/2-in.. # 8 Hex Head Screws 1 /2-in.| 5
3/8-in. # 8 Hex Head Screws| 2
Table 2 – Model Numbers
INSTALLATION
SINGLE-SPEED PSC INDUCER MODELS
INPUT| KIT NUMBER’
26.000| 1193418
40.000
60.000| 1193419
80.000
100.000| 1193420
120.000
140.000| 1193421
TWO SPEED PSC INDUCER MODELS
INPUT| KIT NUMBER”
40.000| 1193418
60.000| 1193419
80.000
100.000| 1193420
120.000
MODULATING MODELS
INPUT| KIT NUMBER”
60.000| 1193424
80.000
100.000
120.000
ULTRA-LOW NOX MODELS
INPUT| KIT NUMBER”
40.000| 1193425
60.000
80.000
100.000
SINGLE SPEED export Models (220 VOLT, 50 Hz ONLY)
INPUT| KIT NUMBER
100.000| 1185902
120.000
140.000
Unit Shut Down
WARNING
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or
property damage.
Turn off the gas and electrical supplies to the furnace and install a lockout
tag before performing any maintenance or service. Follow the operating
instructions on the label attached to the furnace.
- Set room thermostat to lowest setting or “OFF.”
- Disconnect power at external disconnect, fuse, or circuit breaker.
- Turn off gas at external shut-off or gas meter.
- Remove outer doors and set them aside.
- Turn the gas valve electric switch to “OFF.”
Vent Pipe Removal
NOTE: The vent pipe may be connected to the furnace at the rubber vent
pipe support. Before cutting the vent pipe, loosen the clamps around the vent
pipe coupling and move the vent pipe away from the furnace. Support the vent
pipe as close to the furnace as possible to prevent damage to the vent system.
NOTE: If the vent pipe passes through the vent pipe coupling into the
vent elbow on the inducer, it may be necessary to cut the vent pipe external
to the casing, then re- ement the vent pipe with a field-supplied coupling.
INDUCER HOUSING KIT: Installation Instructions
- Support the vent pipe as close to the furnace as possible to prevent damage to the vent system.
- Cut the vent pipe with a hacksaw and move the remaining vent pipe out of the way. Secure the vent pipe if necessary.
- Loosen both clamps at the vent pipe support attached to the furnace casing.
- Loosen clamp for the vent pipe at vent elbow on the inducer assembly.
- Remove the remaining vent pipe through the top of the furnace casing and set it aside.
CAUTION
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in improper furnace operation or
failure of the furnace.
Label all wires prior to disconnection when servicing controls. Wiring errors
can cause improper and dangerous operations.
Pressure Switch or Pressure Transducer Tube Removal
Fig. 2 – Inducer Assembly with Pressure Switches(Modulating/Ultra-Low NOx
model is similar)
A11361
NOTE: There are two types of pressure switches. The modulating pressure
switch assembly has three pressure switches. Two are side-by-side with the
third switch mounted to the back of one of the switches.
The Ultra-Low NOx furnace uses a pressure transducer attached to the inducer
wire harness or mounted to a panel instead of a pressure switch.It is not
necessary to remove the pressure transducer when replacing the inducer
assembly.
All other furnaces have two pressure switches mounted back-to-back. Pressure
switches for PSC inducers have a tube on the back pressure switch that
connects to the port on the inducer assembly. Pressure switches for the
modulating inducers only have one pressure switch tube. The pressure
transducer for the Ultra-Low NOx model is not connected to the inducer
assembly.
- Remove the front pressure switch or pressure transducer tube from the port on the collector box, see Fig. 2. For Utlra Low NOx models, go to Step 7. for all other models, and continue with Step 2.
- Disconnect the pressure switch harness (modulating only) from the main wiring harness or remove the individual wires from the front pressure switch (non-modulating). Note the location of the wires for reassembly.
- Remove the screws that attach the pressure switch assembly to the inducer.
- Remove the back pressure switch tube that connects to the inducer assembly (PSC only).
- Remove the wires from the back pressure switch. Note the location of the wires for reassembly. (PSC only).
- Set the pressure switches aside.
- If the relief tube for the condensate trap or pressure transducer tube is routed across the inducer assembly, remove the tube from the port on the collector box and from the stand-offs on the inducer and move the tube aside
Inducer Assembly Removal
-
Remove the door bracket from the front edge of the lower shelf.
-
Remove the wires that connect the main wiring harness to the inducer motor harness. On the furnace using an old-style ECM inducer, remove the adapter harness between the inducer motor and the main furnace wiring harness and discard it, see Fig. 1 and Fig. 3
Fig. 3 – ECM Adapter Harness
A12001 -
Remove the screws from the tabs on inducer assembly that secures the inducer to the collector box. Note there is one mounting tab directly under the vent elbow.
-
Remove the inducer assembly and set it aside.
-
To avoid double gaskets and leakage, check to make sure the drain gaskets for the inducer and the inducer gasket are not still attached to the collector box.
-
Remove any adhered gaskets from the front of the collector box.
-
Remove the vent elbow from the inducer assembly and set it aside.
Inducer Inlet Choke Plate (PSC and Ultra-Low NOx inducers only)
NOTE: Some PSC and Ultra-Low NOx inducers have a factory-installed Inducer
Inlet Choke. The Inlet Choke snaps into the inlet of the Inducer Assembly. A
new Choke Plate is included in the loose parts bag of the inducer kit. If a
new Choke Plate is required as shown in Table 3 and is not included in the
loose parts bag, the choke plate from the old inducer assembly can be re-used
in the new assembly. Modulating inducer assemblies do not use an Inlet Choke
Plate, see Fig. 4.
Fig. 4 – Inlet
Choke
A200257
- Un-snap the Inlet Choke from the old inducer assembly.
- Align the tabs on the Inlet Choke collector box with the slots on the inlet of the replacement inducer assembly and snap them into place.
Table 3 – Inlet Choke Plate Required
Inducer Assembly Installation
SINGLE-SPEED PSC INDUCER MODELS
Input BTUH| Choke Plate Used| Inside diameter
26,000| 1188169| (3) 9.7 mm
diameter holes
40,000| 1185620| 44.45 mm
60,000| 1185619| 31.75 mm
80,000| No| N/A
100.000| 1185620| 44.45 mm
120.000| No| N/A
140.000| No| N/A
TWO SPEED PSC INDUCER MODELS
Input BTUH| Choke Plate Required| Inside diameter
40,000| 1185620| 44.45 mm
60,000| 1185619| 31.75 mm
80,000| No| N/A
100.000| 1185620| 44.45 mm
120.000| No| N/A
ULTRA LOW NOx MODELS
Input BTUH| Choke Plate Required| Inside diameter
40.000| 1188169| (3) 9.7 mm
diameter holes
60,000| No| N/A
80,000| No| N/A
100.000| 1185620| 44.45 mm
MODULATING MODELS – No Choke Plate Required
SINGLE-SPEED EXPORT MODELS
(220 VOLT, 50 HZ ONLY)
Input BTUH| Choke Plate Required| Inside diameter
100.000| 1185620| 44.45 mm
120.000| No| N/A
140.000| No| N/A
-
Verify any remaining gaskets on the front of the collector box are removed.
-
Verify the inducer assembly has gaskets on the drain stubs and at the inducer inlet.
-
Verify the Inlet Choke Plate (when used) is installed on the inlet opening of the inducer.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death. Missing gaskets can increase the risk of increased levels of carbon monoxide. -
Align the tabs on the inducer assembly to the brass inserts on the collector box.
-
Insert the mounting screws by hand through the tabs to secure the inducer to the collector box. Remember there is a mounting tab located under the vent elbow.
-
Tighten the screws in an alternating pattern by hand. Do not use a screw gun or over-tighten the mounting screws.
-
Connect the inducer leads from the main wiring harness to the inducer motor harness.
On Variable Speed furnaces with old-style ECM inducers, verify adapter harness has been removed before connecting the harness to the new ECM motor, see Fig. 3. Otherwise, connect the furnace wiring harness directly to the motor.
On 2-stage furnaces, connect furnace wiring harness directly to harness on inducer motor.
On single-stage furnaces (except 140,000 input), attach adapter harness included in kit to harness on inducer motor. Connect the other end of the adapter harness to the main furnace wiring harness, see Fig. 5. On 140,000 input single-stage furnaces, connect furnace wiring harness directly to harness on inducer motor. -
Attach the vent elbow to the inducer outlet. Torque the vent elbow clamp 15 lb-in.
Fig. 5 – Single to Two-Stage PSC Adapter Harness
A12002
Pressure Switch or Pressure Transducer Tube Installation
NOTE: There are two types of pressure switches. The modulating pressure
switch assembly has three pressure switches. Two are side-by-side with the
third switch mounted to the back of one of the switches.
The Ultra-Low NOx furnace uses a pressure transducer mounted to the heat
exchanger cell panel instead of a pressure switch. It is not necessary to
remove the pressure transducer when replacing the inducer assembly. All other
furnaces have two pressure switches mounted back-to-back. The tube for the
front pressure switch connects the switch to the port on the collector box.
The tube for the switch mounted on the back connects the switch to the port on
the inducer assembly. The pressure transducer for the Ultra-Low NOx model is
not connected to the inducer assembly.
- Connect the wires to the back pressure switch (PSC only). For Ultra-Low NOx models, go to Step 3. and Step 7. all other models, and continue with Step 3.
- Connect the tube for the back pressure switch to the inducer assembly (PSC only).
- Connect the tube for the front pressure switch or pressure transducer to the port on the collector box (PSC only).
- Attach the pressure switch assembly to the inducer.
- Connect the pressure switch harness (modulating only) to the main wiring harness or attach the individual wires to the pressure switch (non-modulating).
- If necessary, route the pressure switch tubing for the front pressure switch through the stand-off on the inducer assembly.
- If necessary, route the condensate trap relief tubing through the stand-off on the inducer assembly. Reconnect tubing to the ports on the condensate trap and collector box.
Inducer Outlet Restrictor (PSC models only)
Fig. 6 – Outlet Choke Installation
A150624
On 40,000 BTUH input models on vent systems under 10 ft. in length, an inducer
outlet restrictor is required at altitudes under 2000-ft (610 M). The outlet
restrictor snaps into the outlet of the inducer assembly. If the Outlet
restrictor was installed in the old inducer, remove it and re-install it in
the replacement inducer.
To install the outlet restrictor:
- Align the lock tabs on the outlet restrictor with the slots on the inside outlet of the inducer assembly.
- Snap the outlet restrictor in place.
- Install the vent elbow in the required orientation.
- Torque vent elbow clamp 15 lb-in.
Vent Pipe Installation
- Orient the vent elbow in the required location. Torque the vent elbow clamp 15 lb-in.
- Insert the vent pipe through the furnace casing and into the outlet of the inducer vent elbow.
- Tighten the clamp for the vent pipe at the vent elbow on the inducer assembly.
- Align the remaining vent pipe system to the vent pipe in the furnace casing.
- Solvent cement the pipes as required for the type of material used.
- Tighten both clamps at the vent pipe support attached to the furnace casing.
Unit Checkout
-
Set the thermostat to “OFF”.
-
Turn on power at external disconnect, fuse or circuit breaker.
-
Turn on gas at external shut-off or gas meter.
WARNING
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in a fire, explosion, personal injury, or death.
NEVER purge a gas line into a combustion chamber. NEVER test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result in causing property damage, personal injury, or loss of life. -
Check for gas leaks with a commercially available soap solution made specifically for the detection of leaks.
-
Manually close blower door switch.
-
Turn the gas valve electric switch to “ON.”
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death. The blower door switch opens 115-v power to control. No component operation can occur unless the switch s closed. Caution must be taken when manually closing this switch for service purposes. -
Initiate component test through circuit board by referring to “Component Test” on status code label on blower access door for
complete test sequence information. -
If any status codes are flashed, refer to the status code label on the unit blower door.
-
Turn the thermostat fan switch to “ON”, “Continuous” or jumper R to G terminals at the furnace control board.
-
Check for air leakage around the cell panel.
-
Remove jumper(s) or set thermostat fan to “Auto” or “OFF”
-
Release blower door switch
-
Install blower access door
-
Set the thermostat to call for heat.
-
Allow unit to initiate a complete call for heat cycle.
-
Check for air leakage around the collector box. A whistling noise may indicate an air leak in the collector box seal.
NOTE: If there is a severe air leak in the collector box seal, the pressure switch may not close or will re-open, resulting in no ignition or erratic burner operation.
NOTE: As part of the system check-out, verify that the following conditions are not affecting the operation of the furnace:
• Short Cycling-Defective thermostat: Incorrect thermostat anticipation setting, dirty filter or oversized furnace.
• Under firing/low BTU input: Set manifold pressure and verify firing rate as shown on the rating plate by clocking the gas meter.
• Over firing/high BTU input: Set manifold pressure and verify firing rate as shown on the rating plate by clocking the gas meter.
• Low-temperature rise: Set unit for correct temperature rise range as shown on the unit rating plate.
• Contaminated combustion air: Remove contaminates or provides ample fresh air for combustion.
• Excessive amounts of outside ventilation air: Return air temperature cannot be below 60 degrees F for extended periods of time.
• Incorrect venting or termination: Recirculation of products of combustion into the combustion air pipe can damage the furnace. Verify proper venting and vent termination per installation instructions. For additional information, and a complete sequence of furnace operations, refer to furnace Installation, Start-Up and Operating Instructions. -
After System Check-out is complete, set the thermostat below room temperature.
-
Verify that burner shuts down and the blower completes the selected off delay time.
-
Verify furnace operates properly and set the thermostat to desired room temperature.
-
Re-install the outer door.
© 2022 Carrier. All rights reserved.
Edition Date: 03/22
Catalog No: IIK-90INDHSG-01
A Carrier Company
Replaces: 443 06 5605 00
The manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations.