AVANTCO 178MC34HC Commercial School Milk Cooler User Manual
- June 5, 2024
- AVANTCO
Table of Contents
AVANTCO 178MC34HC Commercial School Milk Cooler
Warning
DANGER – RISK OF FIRE OR EXPLOSION. FLAMMABLE REFRIGERANT USED. TO BE REPAIRED
ONLY BY
TRAINED SERVICE PERSONNEL. DO NOT PUNCTURE REFRIGERANT TUBING.
CAUTION – RISK OF FIRE OR EXPLOSION. FLAMMABLE REFRIGERANT USED. CONSULT
REPAIR
MANUAL/OWNER’S GUIDE BEFORE ATTEMPTING TO SERVICE THIS PRODUCT. ALL SAFETY
PRECAUTIONS MUST BE FOLLOWED.
CAUTION – RISK OF FIRE OR EXPLOSION DUE TO PUNCTURE OF REFRIGERANT TUBING;
FOLLOW
HANDLING INSTRUCTIONS CAREFULLY. FLAMMABLE REFRIGERANT USED.
CAUTION – RISK OF FIRE OR EXPLOSION DUE TO FLAMMABLE REFRIGERANT USED. FOLLOW
HANDLING INSTRUCTIONS CAREFULLY IN COMPLIANCE WITH LOCAL GOVERNMENT
REGULATIONS.
Please read this manual thoroughly prior to equipment set-up, operation and maintenance.
Inspection
When the equipment is received, all items should be carefully checked against the bill of landing to insure all crates and cartons have been received. All units should be inspected for concealed damage by uncrating the units immediately. If any damage is found, it should be reported to the carrier at once, and a claim should be filed with the carrier. This equipment has been inspected and tested in the Avantco Refrigeration. Facility and has been crated in accordance with transportation rules and guidelines. Manufacturer is not responsible for freight loss or damage.
Installation
GENERAL
Take care when removing the skid, so that it will not damage the cooler’s finish. Do not tip cabinet to install casters or legs. Insure that the casters or legs are screwed all the way into the base.
LOCATION
The self contained refrigeration system located at the bottom of the cabinet requires free air access for proper operation. The back of the cabinet may be positioned against a wall, however, there must be a minimum four inch clearance between the sides and a wall. It is necessary to properly level cooler to provide adequate drainage and efficient functioning of the unit.
ELECTRICAL
Check the proposed outlet to be used to insure that the voltage, phase, and current carrying capacity of the circuit from the electrical panel correspond to the requirements of the cabinet. Plug all standard models into a 110 volts A.C.60 cycle outlet. NEVER use an extension cord to power any unit. All wiring between the electrical panel and the unit must be done in accordance with the National Electric Code and all state and local codes. Refer to the Serial Tag for all pertinent electrical information.
General Operation
The milk coolers are cooled entirely by convection as a result of copper coils
completely encircling the perimeter of the storage compartment. During the
refrigeration process, heat is removed through the evaporator tubing and
expelled through the condensing unit. It is important that the flow of air
through the side louvers is not restricted in order to ensure the condensing
unit operates properly.
Under normal operating conditions, any frost that might accumulate on the
walls during the “on” cycle of the condensing unit may melt during the “off”
cycle. Drains are installed in all milk coolers to accommodate melting frost.
Adjusting the Temperature
Your new refrigerator or freezer is already factory-set to run at optimum
temperatures for food safety and should require no adjustments.
Refrigerators are set to cycle between a minimum temperature of 33 degrees Fahrenheit and a maximum temperature of 40 degrees Fahrenheit.
Freezers are set to cycle between a minimum temperature of -5 degrees Fahrenheit and a maximum temperature of 2 degrees Fahrenheit.
Adjusting the temperature changes the minimum temperature your unit will run at. Your unit will not run constantly at this setting. To change it, follow these instructions:
Digital Control Units
- Hold “SET” for 1 sec. The display will flash the current minimum temperature.
- Use the arrow buttons to adjust the minimum temperature you want it to run at.
- Press “SET” again to save your settings
Running a Manual Defrost Cycle
Units are pre-programmed to run automatic defrost cycles at preset intervals. However, if you would like to run a manual defrost cycle at any time, please follow the steps below:
- Press the defrost button (snowflake symbol and down arrow) for approximately 3 seconds.
- Repeat to stop the defrost cycle.
General Maintenance
PERIODIC CLEANING
Beginning with the initial installation, the interior surfaces of the cabinet should be periodically wiped down with a solution of warm water and baking soda. This solution will remove any odors from spillage that has occurred. The exterior of the cabinet should also be cleaned frequently with a commercial grade glass cleaner or with mild soap and water. Never, under any circumstances, use an abrasive cleaner or alkaline solution.
Monthly cleaning of the condenser will aid the heat transfer characteristics of the refrigeration system and increase its efficiency. To accomplish this, remove the louvered panel from the cabinet and use a wire brush to loosen any dirt particles that are attached to the fins. After this is accomplished, use a vacuum cleaner to remove the loosened particles.
Troubleshooting
Compressor Will Not Start, No Hum
Service cord unplugged | Plug in service cord |
---|---|
Fuse blown or removed | Determine reasons and correct |
Control stuck open | Repair or replace |
Wiring incorrect | Check wiring against the diagram |
Compressor Will Not Start, Hums but Trips Overload Protector
Improperly wired | Check against the wiring diagram |
---|---|
Low voltage to unit | Determine the reason and correct |
Starting capacitor defective | Determine the reason and replace |
Relay failing to close | Determine the reason, correct or replace |
Compressor Starts & Runs **but Short Cycles on Overload Protector**
Low voltage to unit | Determine the reason and correct |
---|---|
Overload defective | Check current, replace overload protector |
Excessive head pressure | Check ventilation or restriction in refrigeration |
system
Compressor hot-return gas hot| Check refrigeration charge, fix leak if
necessary
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>