Goodman M9S80-U Ultra Low NOx Gas Furnace Instruction Manual
- June 10, 2024
- Goodman
Table of Contents
M9S80-U Ultra Low NOx Gas Furnace
Installation Instructions forM9S80U Ultra Low NOx Gas Furnace CATEGORY I
CATÉGORIE I
These furnaces comply with requirements embodied in the American National
Standard/National Standard of Canada ANSI Z21.47·CSA-2.3 Gas Fired Central
Furnaces.
Installer: Affix all manuals adjacent to the unit.
ATTENTION INSTALLING PERSONNEL
TABLE OF CONTENTS
SAFETY CONSIDERATIONS ……………………………………. 2 Additional Safety Considerations
………………………..5 Shipping Inspection ………………………………………………..5 Electrostatic Discharge
(ESD) Precautions…………5 To The Installer……………………………………………………..6 PRODUCT
APPLICATION………………………………………….6 LOCATION REQUIREMENTS AND CONSIDERATIONS .7
Clearances and Accessibility ……………………………….8 Installation Positions
……………………………………………8 Venting for Horizontal Left or Right Installation … 8
Furnace Suspension……………………………………………….9 Existing Furnace
Removal……………………………………..9 Thermostat Location ……………………………………………..9 COMBUSTION
AND VENTILATION AIR
REQUIREMENTS ……………………………………………….. 10 CATEGORY I VENTING (VERTICAL VENTING)
…………10 MASONRY CHIMNEYS …………………………………………… 11 Masonry Chimney
Termination…………………………….. 11 ELECTRICAL CONNECTIONS ………………………………… 11 Wiring
Harness……………………………………………………. 11 120 Volt Line Connections ………………………………….. 11
Junction Box Relocation…………………………………….. 11
As a professional installer, you have an obligation to know the product better
than the customer. This includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this
Instruction Manual. Pay special attention to all safety warnings. Often during
installation or repair, it is possible to place yourself in a position which
is more hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know
it well enough to be able to instruct a customer in its safe use.
Safety is a matter of common sense…a matter of thinking before acting. Most
dealers have a list of specific, good safety practices…follow them.
The precautions listed in this Installation Manual are intended as
supplemental to existing practices. However, if there is a direct conflict
between existing practices and the content of this manual, the precautions
listed here take precedence.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION
WARNING
Only personnel that have been trained to install, adjust, service or
repair(hereinafter, “service”) the equipment specified in this manual should
service the equipment. The manufacturer will not be responsible for any injury
or property damage arising from improper service or service procedures. If you
service this unit, you assume responsibility for any injury or property damage
which may result. In addition, in jurisdictions that require one or more
licenses to service the equipment specified in this manual, only licensed
personnel should service the equipment. Improper installation, adjustment,
servicing or repair of the equipment specified in this manual, or attempting
to install, adjust, service or repair the equipment specified in this manual
without proper training may result in product damage, property damage,
personal injury or death.
WARNING
Do not bypass safety devices.
NOTE: Please contact your distributor or our website listed
below for the applicable Specification Sheet referred to in this manual.
IOG-2031A 04/2022
19001 Kermier Rd. Waller, Tx 77484
www.goodmanmfg.com · www.amana-
hac.com © 2021-2022 Goodman Manufacturing Company,
L.P.
is a registered trademark of Maytag Corporation or its related companies and
is used under license. All rights reserved.
SAFETY CONSIDERATIONS
IMPORTANT NOTE: This unit is designed to meet the NOX requirement of 14Ng/J
maximum as required by the South Coast Air Quality Management District and the
San Joaquin Valley Air Pollution Control District, both in the State of
California, and is intended for installation in those districts only.
This unit has a Control System that compensates for certain installation and
environmental conditions. This unit must:
· Be properly installed, operated, and maintained per the instructions.
· Be serviced only by properly trained Service Technicians.
This unit is not approved for use with gases other than Natural Gas.
Units that are not installed, maintained, or operated properly may result in
“noisy” operation during the Heating Cycle. If this unit is making unusual or
objectionable noises during the Heating Cycle, turn the heat off at the
thermostat and contact a qualified Service organization right away.
Adhere to the following warnings and cautions when installing, adjusting,
altering, servicing, or operating the furnace. To ensure proper installation
and operation, thoroughly read this manual for specifics pertaining to the
installation and application of this product.
This furnace is manufactured for use with natural gas only.
Install this furnace only in a location and position as specified in LOCATION
REQUIREMENTS & CONSIDERATIONS section and INSTALLATION POSITIONS section of
this manual.
Provide adequate combustion and ventilation air to the furnace as specified in
COMBUSTION & VENTILATION AIR REQUIREMENTS section of this manual.
Combustion products must be discharged to the outdoors. Connect this furnace
to an approved vent system only, as specified in CATEGORY 1 VENTING section of
this manual.
2
Never test for gas leaks with an open flame. Use a commercially available soap
solution made specifically for the detection of leaks to check all
connections, as specified in GAS SUPPLY AND PIPING section of this manual.
Always install a furnace to operate within the furnace’s intended temperature-
rise range with a duct system which has external static pressure within the
allowable range, as specified on the furnace rating plate and OPERATIONAL
CHECKS section of these instructions.
When a furnace is installed so that supply ducts carry air circulated by the
furnace to areas outside the space containing the furnace, the return air
shall also be handled by duct(s) sealed to the furnace casing and terminating
outside the space containing the furnace.
A gas-fired furnace for installation in a residential garage must be installed
as specified in the LOCATION REQUIREMENTS AND CONSIDERATIONS section of this
manual.
This furnace may be used as a construction site heater only if certain
conditions are met. These conditions are listed in the PRODUCT APPLICATION
section of this manual.
WARNING
To prevent personal injury or death due to improper installation, adjustment,
alteration, service or maintenance, refer to this manual. For additional
assistance or information, consult a qualified installer, servicer agency or
the gas supplier.
WARNING
If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance. WHAT TO DO IF
YOU SMELL GAS:
· Do not try to light any appliance. · Do not touch any electrical switch; do
not use any
phone in your building. · Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions. · If you cannot reach your gas
supplier, call the fire
department. Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
WARNING
Heating unit should not be utilized without reasonable, routine, inspection,
maintenance and supervision. If the building in which any such device is
located will be vacant, care should be taken that such device is routinely
inspected, maintained, and monitored. In the event that the building maybe
exposed to freezing temperatures and will be vacant, all water-bearing pipes
should be drained, the building should be properly winterized, and the water
source closed. In the event that the building may be exposed to freezing
temperatures and will be vacant, any hydronic coil units should be drained as
well and, in such case, alternative heat sources should be utilized.
WARNING
Should overheating occur or the gas supply fail to shut off, turn off the
manual gas shutoff valve external to the furnace before turning off the
electrical supply.
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury,
death or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap
solution made specifically for the detection of leaks to check all
connections. A fire or explosion may result causing property damage, personal
injury or loss of life.
AVERTISSEMENT
RISQUE D’INCENDIE OU D’EXPLOSION
Si les consignes de sécurité ne sont pas suivies à la lettre, cela peut
entraîner la mort, de graves blessures ou des dommages matériels.
Ne jamais vérifier la présence de fuites de gaz au moyen d’une flamme nue.
Vérifier tous les raccords en utilisant une solution savonneuse commerciale
conçue spécialement pour la détection de fuites. Un incendie ou une explosion
risque de se produire, ce qui peut entraîner la mort, des blessures ou des
dommages matériels.
WARNING
Possible property damage, personal injury or death due to fire, explosion,
smoke, soot, condensation, electrical shock or carbon monoxide may result from
improper installation, repair operation, or maintenance of this product.
WARNING
To prevent personal injury or death due to asphyxiation, this furnace must be
Category I vented. Do not vent using Category III venting. Provisions must be
made for venting combustion products outdoors through a proper venting system.
The length of flue pipe could be a limiting factor in locating the furnace.
3
WARNING
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below
for each appliance connected to the venting system being placed into operation
could result in carbon monoxide poisoning or death.
The following steps shall be followed with each appliance connected to the
venting system placed in operation, while any other appliances connected to
the venting system are not in operation:
1. Seal any unused openings in the venting system. 2. Inspect the venting
system for proper size and horizon-
tal pitch, as required by the National Fuel Gas Code, ANSI Z223.1 or the
Natural Gas and Propane Installation Code, CSA B149.1-15 and these
instructions. Determine that there is no blockage or restriction, leakage,
corrosion and other deficiencies which could cause an unsafe condition. 3. As
far as practical, close all building doors and windows and all doors between
the space in which the appliance(s) connected to the venting system are
located and other spaces of the building. 4. Close fireplace dampers. 5. Turn
on clothes dryers and any appliance not connected to the venting system. Turn
on any exhaust fans, such as range hoods and bathroom exhausts, so they shall
operate at maximum speed. Do not operate a summer exhaust fan. 6. Follow the
lighting instructions. Place the appliance being inspected in operation.
Adjust thermostat so appliance shall operate continuously. 7. Test for
spillage from draft hood appliances at the draft hood relief opening after 5
minutes of main burner operation. Use the flame of a match or candle. 8. If
improper venting is observed during any of the above tests, the venting system
must be corrected in accordance with the National Fuel Gas Code ANSI Z223.1/
NFPA 54 and/or National Gas and Propane Installation Code CSA B149.1-15. 9.
After it has been determined that each appliance connected to the venting
system properly vents when tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas burning appliance to their
previous conditions of use.
Additional Safety Considerations · This furnace is approved for Category I
Venting only.
· Provisions must be made for venting combustion
products outdoors through a proper venting system.
The length of flue pipe could be a limiting factor in locating the furnace.
The carrier is responsible for making prompt inspection of damage and for a
thorough investigation of each claim. The distributor or manufacturer will not
accept claims from dealers for transportation damage.
Keep this literature in a safe place for future reference.
Shipping Inspection All units are securely packed in shipping containers
tested according to International Safe Transit Association specifications. The
carton must be checked upon arrival for external damage. If damage is found, a
request for inspection by carrier’s agent must be made in writing immediately.
The furnace must be carefully inspected on arrival for damage and bolts or
screws which may have come loose in transit. In the event of damage the
consignee should:
1. Make a notation on delivery receipt of any visible damage to shipment or
container.
2. Notify carrier promptly and request an inspection. 3. With concealed
damage, carrier must be notified as
soon as possible – preferably within five days. 4. File the claim with the
following support documents
within a nine month statute of limitations. · Original or certified copy of
the Bill of Lading, or
indemnity bond. · Original paid freight bill or indemnity in lieu
thereof. · Original or certified copy of the invoice, showing
trade and other discounts or reductions. · Copy of the inspection report
issued by carrier’s
representative at the time damage is reported to carrier.
Electrostatic Discharge (ESD) Precautions NOTE: Discharge your body’s static
electricity before touching unit. An electrostatic discharge can adversely
affect electrical components.
Use the following precautions during furnace installation and servicing to
protect the integrated control module from damage. By putting the furnace, the
control, and the person at the same electrostatic potential, these steps will
help avoid exposing the integrated control module to electrostatic discharge.
This procedure is applicable to both installed and non-installed (ungrounded)
furnaces.
1. Disconnect all power to the furnace. Do not touch the integrated control
module or any wire connected to the control prior to discharging your body’s
electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the furnaces near the
control. Any tools held in a person’s hand during grounding will be
discharged.
3. Service integrated control module or connecting wiring following the
discharge process in step 2. Use caution not to recharge your body with static
electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded
objects, etc.). If you come in contact with an ungrounded object, repeat step
2 before touching control or wires.
4. Discharge your body to ground before removing a new control from its
container. Follow steps 1 through 3 if installing the control on a furnace.
Return any old or new controls to their containers before touching any
ungrounded object.
5
To The Installer Before installing this unit, please read this manual
thoroughly to familiarize yourself with specific items which must be adhered
to, including but not limited to: unit maximum external static pressure, gas
pressures, BTU input rating, proper electrical connections, circulating air
temperature rise, minimum or maximum CFM, and motor speed connections, and
venting. These furnaces are designed for Category I venting only.
WARNING
To prevent property damage, personal injury or death due to fire, do not
install this furnace in a mobile home, trailer, or recreational vehicle.
PRODUCT APPLICATION
This furnace is primarily designed for residential homeheating applications.
It is not designed or certified for use in mobile homes, trailers or
recreational vehicles. Neither is it designed or certified for outdoor
applications. The furnace must be installed indoors (i.e., attic space, crawl
space, or garage area provided the garage area is enclosed with an operating
door).
This furnace can be used in the following non-industrial commercial
applications:
Schools, Office buildings, Churches, Retail stores, Nursing homes,
Hotels/motels, Common or office
areas
In such applications, the furnace must be installed with the following
stipulations:
· It must be installed per the installation instructions provided and per
local and national codes.
· It must be installed indoors in a building constructed on site.
· It must be part of a ducted system and not used in a free air delivery
application.
· It must not be used as a “make-up” air unit. · All other warranty exclusions
and restrictions apply.
This furnace may be used as a construction site heater ONLY if the following
conditions are met:
· The vent system is permanently installed per these installation
instructions.
· A room thermostat is used to control the furnace. Fixed jumpers that provide
continuous heating CANNOT be used and can cause long term equipment damage.
Bi-metal thermostats, or any thermostat affected by vibration must not be used
during construction.
· Return air ducts are provided and sealed to the furnace.
· A return air temperature range between 60°F (16°C) and 80°F (27°C) is
maintained.
· Air filters are installed in the system and replaced daily during
construction and upon completion of construction.
· The input rate and temperature rise are set per the furnace rating plate.
· 100% outside air must be used for combustion during construction. Temporary
ducting may be used to supply outside air to the furnace for combustion do
not connect this duct directly to the furnace. Size this duct according to
NFPA 54/ANSI Z223.1 section for Combustion and Ventilation Air.
· The furnace heat exchanger, components, duct system, air filters and
evaporator coils are thoroughly cleaned following final construction clean up
by a qualified person.
· All furnace operating conditions (including ignition, input rate,
temperature rise and venting) are verified by a qualified person according to
these installation instructions.
· Furnace doors must be in place on the furnace while the furnace is operating
in any mode.
Damage or repairs due to failure to comply with these requirements are not
covered under the warranty. To ensure proper furnace operation, install,
operate and maintain the furnace in accordance with these installation and
operation instructions, all local building codes and ordinances. In their
absence, follow the latest edition of the National Fuel Gas Code (NFPA 54/
ANSI Z223.1), local plumbing or waste water codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI Z223.1) can be obtained
from any of the following:
American National Standards Institute 25 West 43rd Street, 4th Floor New York,
NY 10036
National Fire Protection Association 1 Batterymarch Park
Quincy, MA 02169-7471
CSA International 8501 East Pleasant Valley
Cleveland, OH 44131
Additional helpful publications available from the NFPA are, NFPA 90A –
Installation of Air Conditioning and Ventilating System and NFPA 90B – Warm
Air Heating and Air Conditioning System.
The rated heating capacity of the furnace should be greater than or equal to
the total heat loss of the area to be heated. The total heat loss should be
calculated by an approved method or in accordance with “ASHRAE Guide” or
“Manual J-Load Calculations” published by the Air Conditioning Contractors of
America.
6
LOCATION REQUIREMENTS AND CONSIDERATIONS
WARNING
To prevent possible equipment damage, property damage, personal injury or
death, the following bullet points must be observed when installing this unit.
Follow the instructions listed below when selecting a furnace location. Refer
also to the guidelines provided in Combustion and Ventilation Air
Requirements.
· Centrally locate the furnace with respect to the proposed or existing air
distribution system.
· Ensure the temperature of the return air entering the furnace is between
55°F and 100°F when the furnace is heating.
· Provisions must be made for venting combustion products outdoors through a
proper venting system. The length of flue pipe could be a limiting factor in
locating the furnace.
· Ensure adequate combustion air is available for the furnace. Improper or
insufficient combustion air can expose building occupants to gas combustion
products that could include carbon monoxide. Refer to Combustion and
Ventilation Air Requirements.
· The furnace must be level. If the furnace is to be set on a floor that may
become wet or damp at times, the furnace should be supported above the floor
on a concrete base sized approximately 1-1/2″ larger than the base of the
furnace.
· Ensure upflow or horizontal furnaces are not installed directly on
carpeting, or any other combustible material. The only combustible material
allowed is wood.
· Exposure to contaminated combustion air will result in safety and
performance-related problems. Do not install the furnace where the combustion
air is exposed to the following substances: permanent wave solutions
chlorinated waxes or cleaners chlorine-based swimming pool chemicals carbon
tetrachloride water softening chemicals swimming pool chemicals deicing salts
or chemicals halogen type refrigerants printing inks cleaning solutions (such
as perchloroethylene) paint removers varnishes hydrochloric acid cements and
glues antistatic fabric softeners for clothes dryers masonry acid washing
materials
· If the furnace is used in connection with a cooling unit, install the
furnace upstream or in parallel with the cooling unit coil. Premature heat
exchanger failure will result if the cooling unit coil is placed ahead of the
furnace. For vertical (upflow) applications, the minimum cooling coil width
shall not be less than furnace width minus 1″. Additionally, a coil installed
above an upflow furnace may be the same width as the furnace or may be one
size larger than the furnace. EXAMPLE: A “C” width coil may be installed with
a “B” width furnace. For upflow applications, the front of the coil and
furnace must face the same direction.
· If the furnace is installed in a residential garage, position the furnace so
that the burners and ignition source are located not less than 18 inches above
the floor. Protect the furnace from physical damage by vehicles.
· If the furnace is installed horizontally, ensure access doors are not on the
“up/top” or “down/bottom” side of the furnace.
· Do not connect this furnace to a chimney flue that serves a separate
appliance designed to burn solid fuel.
Vent Pipe Clearance to Combustibles6″ using Single Wall Connector or 1″ using B1 vent.
Top – 1″
Back – 0″
Side Clearance – 1″
Front Clearance – 3″
Figure 1
· Adequate combustion/ventilation air must be supplied to the closet. Improper
or insufficient combustion air can expose building occupants to gas combustion
products that could include carbon monoxide.
· Furnace must be completely sealed to floor or base. Combustion/ventilation
air supply pipes must terminate 12″ from top of closet and 12″ from floor of
closet. DO NOT remove solid base plate for side return.
· Return air ducts must be completely sealed to the furnace and terminate
outside the enclosure surfaces.
7
Clearances and Accessibility NOTE: For servicing or cleaning, a 24″ front clearance is required. Unit connections (electrical, flue and drain) may necessitate greater clearances than the minimum clearances listed above. In all cases, accessibility clearance must take precedence over clearances from the enclosure where accessibility clearances are greater.
Clearance in accordance with local installation codes, the requirements of the gas supplier and the manufacturer’s installation instructions.
Dégaugement conforme aux codes d’installation locaux, aux exigences du fournisseur de gaz et aux instructions d’installation du fabricant.
VENT B1-VENT SINGLE
1″
6″
SIDES 1″
FRONT 3″
BACK 0″
TOP (PLENUM)
1″
Top clearance for horizontal configuration – 1″ Table 1
Figure 2
Horizontal Installation
Installations must adhere to the clearances to combustible materials to which this furnace has been design certified. The minimum clearance information for this furnace is provided on the unit’s clearance label. These clearances must be permanently maintained. Clearances must also accommodate an installation’s gas, electrical, and drain line connections.
NOTE: In addition to the required clearances to combustible materials, a
minimum of 24″ service clearance must be available in front of the unit.
Installation Positions An upflow furnace may be installed in an upright
position or horizontal on either the left or right side panel. Do not install
this furnace on its back. For vertically installed upflow furnaces, return air
ductwork may be attached to the side panel(s) and/or basepan. For horizontally
installed upflow furnaces, return air ductwork must be attached to the
basepan. Contact your distributor for proper airflow requirements and number
of required ductwork connections. Refer to, “Recommended Installation
Positions” for appropriate installation positions, ductwork connections, and
resulting airflow arrangements.
NOTE: Ductwork must never be attached to the back of the furnace.
Venting for Horizontal Left or Right Installations Always use a B-vent elbow
to vent the flue from the top of the furnace. The inducer cannot be turned due
to limited space in the cabinet. Do not attempt to do this.
Recommended Installation Positions Figure 3
For horizontal installations,
insert the #8 x 5/8 screw
from the literature package.
Figure 4
8
Line contact to framing is permitted when installed in the horizontal
configuration. Line contact is defined as the portion of the cabinet that is
formed by the intersection of the top and side. ACCESSIBILITY CLEARANCE, WHERE
GREATER, SHOULD TAKE PRECEDENCE OVER MINIMUM FIRE PROTECTION CLEARANCE. A
gasfired furnace for installation in a residential garage must be installed so
that the ignition source and burners are located not less than eighteen inches
(18″) above the floor and is protected or located to prevent physical damage
by vehicles. A gas furnace must not be installed directly on carpeting, tile,
or other combustible materials other than wood flooring.
Furnace Suspension If suspending the furnace from rafters or joist, use 3/8″
threaded rod and 2″x2″x3/8″ angle iron as shown below. The length of rod will
depend on the application and the clearances necessary.
c. In so far as practical, close all building doors and windows and all doors
between the space in which the appliance(s) connected to the venting system
are located and other spaces of the building. Turn on clothes dryers and any
appliance not connected to the venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they shall operate at maximum speed.
Do not operate a summer exhaust fan. Close fireplace dampers;
d. Follow the lighting instructions. Place the appliance being inspected in
operation. Adjust thermostat so appliance shall operate continuously;
e. Test for draft hood equipped appliance spillage at the draft hood relief
opening after 5 minutes of main burner operation. Use the flame of a match or
candle;
f. After it has been determined that each appliance connected to the venting
system properly vents when tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas burning appliance to their
previous conditions of use;
g. If improper venting is observed during any of the above tests, the common
venting system must be corrected.
Corrections must be in accordance with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1.
Suspended Furnace Figure 5
Existing Furnace Removal NOTE: When an existing furnace is removed from a
venting system serving other appliances, the venting system may be too large
to properly vent the remaining attached appliances.
The following vent testing procedure is reproduced from the American National
Standard/National Standard of Canada for Gas-Fired Central Furnaces ANSI
Z21.47Latest Edition, CSA-2.3-Latest Edition Section 1.23.1. The following
steps shall be followed with each appliance connected to the venting system
placed in operation, while any other appliances connected to the venting
system are not in operation:
a. Seal any unused openings in the venting system; b. Inspect the venting
system for proper size
and horizontal pitch, as required by the National Fuel Gas Code, ANSI Z223.1
and these instructions. Determine that there is no blockage or restriction,
leakage, corrosion and other deficiencies which could cause an unsafe
condition;
If resizing is required on any portion of the venting system, use the
appropriate table in the latest edition of the National Fuel Gas Code ANSI
Z223.1.
Thermostat Location The thermostat should be placed approximately five feet
from the floor on a vibration-free, inside wall in an area having good air
circulation. Do not install the thermostat where it may be influenced by any
of the following:
· Drafts, or dead spots behind doors, in corners, or under cabinets.
· Hot or cold air from registers. · Radiant heat from the sun. · Light
fixtures or other appliances. · Radiant heat from a fireplace. · Concealed hot
or cold water pipes, or chimneys. · Unconditioned areas behind the thermostat,
such as
an outside wall.
Consult the instructions packaged with the thermostat for mounting
instructions and further precautions.
9
COMBUSTION AND VENTILATION AIR REQUIREMENTS
CATEGORY I VENTING (VERTICAL VENTING)
WARNING
To avoid property damage, personal injury or death, sufficient fresh air for
proper combustion and ventilation of flue gases must be supplied. Most homes
require outside air be supplied into the furnace area.
Improved construction and additional insulation in buildings have reduced heat
loss by reducing air infiltration and escape around doors and windows. These
changes have helped in reducing heating/cooling costs but have created a
problem supplying combustion and ventilation air for gas fired and other fuel
burning appliances. Appliances that pull air out of the house (clothes dryers,
exhaust fans, fireplaces, etc.) increase the problem by starving appliances
for air.
House depressurization can cause back drafting or improper combustion of gas-
fired appliances, thereby exposing building occupants to gas combustion
products that could include carbon monoxide.
WARNING
To prevent possible personal injury or death doe to asphyxiation, this furnace
must be Category I vented. Do not vent using Category III venting.
Category I Venting is venting at a non-positive pressure. A furnace vented as
Category I is considered a fan-assisted appliance and the vent system does not
have to be “gas tight”. NOTE: Single stage gas furnaces with induced draft
blowers draw products of combustion through a heat exchanger allowing, in some
instances, common venting with natural draft appliances (i.e. water heaters).
All installations must be vented in accordance with the latest edition of the
National Fuel Gas Code NFPA 54/ANSI Z223.1.
NOTE: The vertical height of the category 1 venting system must be at least as
great as the horizontal length of the vertical system.
If this furnace is to be installed in the same space with other gas
appliances, such as a water heater, ensure there is an adequate supply of
combustion and ventilation air for all appliances. Refer to the latest edition
of the National Fuel Gas Code NFPA 54/ANSI Z223.1 or applicable provisions of
the local building codes for determining the combustion air requirements for
the appliances.
This furnace must use indoor air for combustion. It cannot be installed as a
direct vent (i.e., sealed combustion) furnace.
Most homes will require outside air be supplied to the furnace area by means
of ventilation grilles or ducts connecting directly to the outdoors or spaces
open to the outdoors such as attics or crawl spaces. A furnace installed in a
confined space (i.e., a closet or utility room) must have two ventilation
openings with a total minimum free area of 0.25 square inches per 1,000 BTU/hr
of furnace input rating. Refer to Specification Sheet applicable to your model
for minimum clearances to combustible surfaces. One of the ventilation
openings must be within 12″ of the top; the other opening must be within 12″
of the bottom of the confined space. In a typical construction, the clearance
between the door and door frame is usually adequate to satisfy this
ventilation requirement.
WARNING
To prevent possible personal injury or death doe to asphyxiation, common
venting with other manufacturer’s induced draft appliances is not allowed.
The minimum vent diameter for the Category I venting system is as shown:
MODEL
40 60 80
MINIMUM VENT UPFLOW 4 Inch 4 Inch 4 Inch
Table 2
Under some conditions, larger vents than those shown above may be required or allowed. When an existing furnace is removed from a venting system serving other appliances, the venting system may be too large to properly vent the remaining attached appliances.
10
MASONRY CHIMNEYS
WARNING
Possibility of property damage, personal injury or death damaging condensation
can occur inside masonry chimneys when a single fan-assisted Category I
appliance (80% AFUE Furnace) is vented without adequate dilution air. Do not
connect an 80% furnace to a masonry chimney unless the furnace is common
vented with a draft hood equipped appliance or the chimney is lined with a
metal liner or type B metal vent. All installations using masonry chimneys
must be sized in accordance with the appropriate venting tables. If an 80%
furnace is common vented with a draft hood equipped appliance, the potential
for condensation damage may still exist with extremely cold conditions, long
vent connectors, exterior chimneys, or any combination of these conditions.
The risk of condensation damage is best avoided by using masonry chimney as a
pathway for properly sized metal liner or type B metal vent.
Masonry Chimney Termination A masonry chimney used as a vent for gas fired
equipment must extend at least three feet above the highest point where it
passes through the roof. It must extend at least two feet higher than any
portion of a building within a horizontal distance of 10 feet. In addition,
the chimney must terminate at least 3 feet above any forced air inlet located
within 10 feet. The chimney must extend at least five feet above the highest
connected equipment draft hood outlet or flue collar.
ELECTRICAL CONNECTIONS
Wiring Harness The wiring harness is an integral part of this furnace. Field
alteration to comply with electrical codes should not be required. Wires are
color coded for identification purposes. Refer to the wiring diagram for wire
routings. If any of the original wire as supplied with the furnace must be
replaced, it must be replaced with wiring material having a temperature rating
of at least 105°C. Any replacement wiring must be a copper conductor.
120 Volt Line Connections Before proceeding with electrical connections,
ensure that the supply voltage, frequency, and phase correspond to that
specified on the unit rating plate. Power supply to the furnace must be NEC
Class 1, and must comply with all applicable codes. The furnace must be
electrically grounded in accordance with local codes or, in their absence,
with the latest edition of The National Electric Code, ANSI NFPA 70.
Use a separate fused branch electrical circuit containing properly sized wire,
and fuse or circuit breaker. The fuse or circuit breaker must be sized in
accordance with the maximum overcurrent protection specified on the unit
rating plate. An electrical disconnect must be provided at the furnace
location.
Line voltage wiring must enter into the junction box provided with the
furnace. Connect hot neutral and ground wires as shown in the wiring diagram
located on the unit’s blower door. Metal conduit is not considered a
substitute for an actual ground wire to the unit.
WARNING
HIGH VOLTAGE! To avoid personal injury or death due to electrical shock,
disconnect electrical power before servicing or changing any electrical
wiring.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors
can cause improper and dangerous operation. Verify proper operation after
servicing.
WARNING
HIGH VOLTAGE! To avoid risk of injury, electrical shock or death, the furnace
must be electrically polarized and grounded in accordance with local codes or
their absence, with the latest edition of the National Electric Code.
Line polarity must be observed when making field connections. Line voltage
connections can be made through either the right or left side panel. To
relocate the junction box, follow the steps shown in the Junction Box
Relocation section.
Junction Box Relocation
WARNING
Edges of sheet metal holes may be sharp. Use gloves as a precaution when
removing hole plugs.
Line voltage connections can be made through either the right or left side
panel. The furnace is shipped configured for a right side electrical
connection. To make electrical connections through the opposite side of the
furnace, the junction box must be relocated to the left side prior to making
electrical connections. To relocate the junction box, perform the following
steps.
WARNING
To prevent personal injury or death due to electric shock, disconnect
electrical power before installing or servicing this unit.
11
1. Remove both doors from the furnace. 2. Remove and save the screws holding
the junction
box to the right side of the furnace. 3. Models that have the junction box
located in the
burner compartment will need to move the junction box directly over. 4. Attach
the junction box to the left side of the furnace, using the screws removed in
step 2. 5. Check the location of the wiring. Confirm that it will not be
damaged by heat from the burners or by the rotation of the fan. Also confirm
that wiring location will not interfere with filter removal or other
maintenance.
Low voltage connections can be made through either the right or left side panel. Thermostat wiring entrance holes are located in the blower compartment. The following figure shows connections for a “heat only” system and “heat/cool system”.
24 VAC Thermostat
R
INDOOR BOARD TERMINAL
CONNECTIONS
R
C
Optional
C
G
Optional
G
Y
Y1
Remote Condensing Unit (Single-Stage Cooling)
C Y
24 VAC Thermost
After the junction box is in the desired location, use
washers to connect field-supplied conduit to the junction box in accordance
with NEC and local codes. Connect hot,
24 VAC Thermostat
INDOOR
Y2
BOARD TERMINAL
Non-cCOoNmNEmCTuIOnNiScating Single Stage A/C
Figure 6ACondensing Unit
24 VAC
B
Thermostat
neutral, and ground diagram. The wires
awnidregsTrh2aeo4rmsuVAonsCstadht oswcrnewiBnOCAOatRNIhNDrNDeEeTOCEOTRlfIRoMOuINcNrSAnaLatecde
wiring in the
24 VAC Thermostat
INDOOR BOARD TERMINAL
CONNECTIONS
furnace junction box.
Condensing Unit
Low voltage wires may be connected to the terminal strip.
IMPORTANT NOTE: To avoid possible equipment
malfunction, route the low voltage wires to
avoid interfe2r4 VeACnce maintenanceTh.ermostat
with IfNDilOOtRer removal BOARD TERMINAL CONNECTIONS
or
other
Condensing Unit
24 VAC Thermostat
R
R
Remote Condensing Unit
C
Optional
C
(Two-Stage Cooling)
INDOOR
G
TOh2pe4trimoVnAoasCl tat
G BOARD TERMINAL CONNECTIONS
C Heat Pump
Y
Y
Y1
Y2
Y2
INDOOR
BONCAOoRNDnNET-CEcTRoIMOmINNSAmLunicating Two Stage A/C Figure 6B
Condensing Unit
WARNING
24 VAC Thermostat
INDOOR BOARD TERMINAL
CONNECTIONS
Heat Pump
HIGH VOLTAGE!
To avoid risk of injury, electrical s24hVoACck death, the furnace must be electrTihceramlosltayt
or
INDOOR BOARD TERMINAL
polar-CONNECTIONS
ized and grounded in accordance with local
codes or their absence, with the latest edition
of the National Electric Code.
Heat Pump
R
R
C
C 24 VAC
OptionalThermostat
G
Optional
G
R C INDOOR
BOARD TERMINAL CONNECTIONS
Y
Y1
Y
Two Stage Heat Pump
To ensure proper unit grounding, the ground wire should
run from the furnace ground screw located inside the
furnace junction box all the way back to the electrical
INDOOR
panel.
NOTE:
Do
not u24sVeACgas Thermostat
piping as an BOARD TERMINAL CONNECTIONS
electrHiecataPlump
ground. To confirm proper unit grounding, turn off the
electrical power and perform the following check.
1. Measure resistance between the neutral (white) connection and the
unpainted surface on the furnace.
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock switch which interrupts unit voltage when the blower door is opened for servicing. Do not defeat this switch.
24 Volt Thermostat Wiring NOTE: Wire routing must not interfere with circulator blower operation, filter removal, or routine maintenance.
Non-Communicating Single Stage Heat Pump Figure 6C
24 VAC Thermostat
INDOOR BOARD TERMINAL
CONNECTIONS
R
R
C
Optional
C
G
Optional
G
Two Stage Heat Pump
R C
Y
Y1
Y
Y2
Y2
Y2
Non-Communicating Two Stage Heat Pump Figure 6D
NOTE: Equipment type (Single-stage cooling, Twostage cooling, Single-stage
heat pump, Two-stage heat pump) MUST be setup through the OdS menu by the
installer for proper system operation. See Using Push-Button Switches for
instructions on how to navigate the control menu.
12
This furnace is equipped with a 40 VA transformer to facilitate use with most
cooling equipment. Consult the wiring diagram, located on the blower
compartment door, for further details of 120 Volt and 24 Volt wiring.
A single-stage thermostat with only one heating stage is needed to control
this furnace.
120 Volt Line Connection of Accessories Humidifier and Electronic Air Cleaner
WARNING
GAS SUPPLY AND PIPING
The furnace rating plate includes the approved furnace gas input rating and
gas types. The furnace must be equipped to operate on the type of gas applied.
CAUTION
To prevent unreliable operation or equipment damage, the inlet gas supply
pressure must be as specified on the unit rating plate with all other
household gas fired appliances operating.
HIGH VOLTAGE! To avoid personal injury or death due to electrical shock,
disconnect electrical power before servicing or changing any electrical
wiring.
The furnace integrated control module is equipped with dedicated ¼ inch EAC
and HUM relay terminals for controlling external power to an optional field-
supplied humidifier and/or electronic air cleaner. Additional line voltage
wiring to the inside of the furnace must conform to all local codes and have a
minimum temperature rating of 105°C. All line voltage wire splices must be
made inside the furnace.
Inlet gas supply pressures must be maintained within the ranges specified in
the following table. The supply pressure must be constant and available with
all other household gas fired appliances operating. The minimum gas supply
pressure must be maintained to prevent unreliable ignition. The maximum must
not be exceeded to prevent unit overfiring and damage to gas valve.
NOTE: Do not remove the gas valve inlet plug before the gas line is installed.
Replace if water or debris has been introduced.
INLET GAS SUPPLY PRESSURE
When utilized, the HUM relay will be closed during normal heating operation and the EAC relay will be closed during fan operation. 115VAC must be present on the one terminal from HUM or EAC to take advantage of the second terminal.
E AC
HUM
Line Neutral
E AC Figure 7
Line Neutral
Fossil Fuel Applications This furnace can be used in conjunction with a heat
pump in a fossil fuel application. A fossil fuel application refers to a
combined gas furnace and heat pump installation which uses an outdoor
temperature sensor to determine the most cost efficient means of heating heat
pump or gas furnace.
A heat pump thermostat with two stages of heat is required to properly use a
furnace in conjunction with a heat pump. Refer to the fossil fuel kit
installation instructions for additional thermostat requirements.
Strictly follow the wiring guidelines in the fossil fuel kit installation instructions. All furnace connections must be made to the furnace integrated control module and the FURNACE terminal strip on the fossil fuel control board.
Natural Gas Minimum: 4.5″ w.c. Maximum: 10.0″ w.c.
Table 4
High Altitude Derate IMPORTANT NOTE: The furnace, as shipped, requires no
change to run between 0-4500 feet. Manifold pressure adjustments and
combustion analysis are required for all installations above 4500 ft. Refer to
“Gas Supply Pressure Measurement” section for instruction on how to properly
measure and adjust manifold “outlet” pressure. The furnace should operate for
a minimum of 15 minutes before taking a combustion sample. Combustion samples
should be taken from beyond the furnace exhaust and must be within provided
CO2% range. See Table 5 for recommended manifold pressure adjustments and
proper CO2% range. Gas heating values can vary; further pressure adjustment
may be necessary to ensure furnace operates within acceptable CO2 range. At
all altitudes the air temperature rise must be within the range listed on the
Specification Sheet applicable to your model for the fuel used.
80% Model
040 060
Manifold Pressure at
5000 ft
Manifold Pressure at
7500 ft
CO2% Natural Gas
2.5″ w.c. 2.4″ w.c. 5.5 – 7.0
2.5″ w.c. 2.4″ w.c. 5.7 – 7.2
080
2.5″ w.c. 2.4″ w.c. 6.0 – 7.5
Table 5
13
Gas Piping Connections
WARNING
To avoid possible unsatisfactory operation or equipment damage due to
underfiring of equipment, use the proper size of natural gas piping needed
when running pipe from the meter to the furnace.
When sizing gas lines, be sure to include all appliances on the same gas supply line and which will operate simultaneously.
The gas piping supplying the furnace must be properly sized based on the gas flow required, specific gravity of the gas, and length of the run. The gas line installation must comply with local codes, or in their absence, with the latest edition of the National Fuel Gas Code, NFPA 54/ANSI Z223.1.
Natural Gas Capacity of Pipe
In Cubic Feet of Gas Per Hour (CFH)
Length of
Nominal Black Pipe Size
Pipe in Feet
1/2″
3/4″
1″
1 1/4″
10
132
278
520
1050
20
92
190
350
730
30
73
152
285
590
40
63
130
245
500
50
56
115
215
440
60
50
105
195
400
70
46
96
180
370
80
43
90
170
350
90
40
84
160
320
100
38
79
150
305
(Pressure 0.5 psig or less and pressure drop of 0.3″ W.C.; Based on
0.60 Specific Gravity Gas)
CFH = BTUH Furnace Input Heating Value of Gas (BTU/Cubic Foot)
Table 6
1 1/2″ 1600 1100 980 760 670 610 560 530 490 460
To connect the furnace to the building’s gas piping, the installer must supply a ground joint union, drip leg, manual shutoff valve, and line and fittings to connect to gas valve. In some cases, the installer may also need to supply a transition piece from 1/2″ pipe to a larger pipe size. The following stipulations apply when connecting gas piping.
· Gas piping must be supported external to the furnace cabinet so that the
weight of the gas line does not distort the burner rack, manifold or gas
valve.
· Use black iron or steel pipe and fittings for the building piping. Where
possible, use new pipe that is properly chamfered, reamed, and free of burrs
and chips. If old pipe is used, be sure it is clean and free of rust, scale,
burrs, chips, and old pipe joint compound.
· Use pipe joint compound on male threads ONLY. Always use pipe joint compound
(pipe dope) that is APPROVED FOR ALL GASES. DO NOT apply compound to the first
two threads.
· Use ground joint unions.
· Install a drip leg to trap dirt and moisture before it can enter the gas
valve. The drip leg must be a minimum of three inches long.
· Install a 1/8″ NPT pipe plug fitting, accessible for test gage connection,
immediately upstream of the gas supply connection to the furnace.
· Always use a back-up wrench when making the connection to the gas valve to
keep it from turning. The orientation of the gas valve connection is 374
inlbs; excessive over-tightening may damage the gas valve and/or gas manifold
assembly.
· Install a manual shutoff valve between the gas meter and unit within six
feet of the unit. If a union is installed, the union must be downstream of the
manual shutoff valve, between the shutoff valve and the furnace.
· Tighten all joints securely. · Protect connectors and semi-rigid tubing
against
physical and thermal damage when installed. Ensure aluminum-alloy tubing and
connectors are coated to protect against external corrosion when in contact
with masonry, plaster, or insulation, or subjected to repeated wetting by
liquids such as water (except rain water), detergents, or sewage. The gas
piping may enter the left or right side of the furnace cabinet. The installer
must supply rigid pipe long enough to reach the outside of the cabinet to seal
the grommet cabinet penetration. A semi-rigid connector to the gas piping can
be used outside the cabinet per local codes. 1/2″ NPT pipe and fittings are
required. Model requires one 90 deg elbow, one 2″ nipple and additional nipple
to reach outside the cabinet. A semi-rigid connector to the gas piping can be
used outside the cabinet per local codes. From the elbow, the length of pipe
and the fittings required will vary by the side chosen, location of union and
cabinet width. The union may be placed inside or outside of the cabinet.
Location of Manual Valve (Installed Ahead of
Ground Joint Pipe Union) Height Required By Local Code
Ground Joint Pipe Union To Be Installed
Ahead of Gas Valve
Drip Leg
OPTIONAL: Reducing Coupling 1/2″ x 1/8″ with 1/8″ Pipe Plug to Measure Line
Gas Pressure
General Furnace Layout Figure 8
14
Upflow Installations A ground joint union, drip leg, and manual shutoff valve
must also be supplied by the installer. In some cases, the
installer may also need to supply a transition piece from 1/2″ to another pipe
size.
CIRCULATING AIR AND FILTERS
Ductwork – Air Flow
WARNING
When the gas piping enters through the side of the furnace,
the installer must supply the following fittings (starting from the gas valve
nipple elbow):
Never allow the products of combustion, including carbon monoxide, to enter the return ductwork or circulation air supply.
· Straight pipe to reach the exterior of the furnace. · A ground joint union,
drip leg, and manual shutoff
valve must also be supplied by the installer.
Gas Piping Checks Before placing unit in operation, leak test the unit and gas
connections.
WARNING
Duct systems and register sizes must be properly designed for the CFM and
external static pressure rating of the furnace. Ductwork should be designed in
accordance with the recommended methods of “Air Conditioning Contractors of
America” Manual D.
A duct system must be installed in accordance with Standards of the National
Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air
Heating and Ventilating Systems. Pamphlets No. 90A and 90B.
To avoid the possibility of explosion or fire, never use a match or open flame
to test for leaks.
Check for leaks using an approved chloride-free soap and water solution, an
electronic combustible gas detector, or other approved testing methods.
CAUTION
To prevent property damage or personal injury due to fire, the following
instructions must be performed regarding gas connections, pressure testing,
location of shutoff valve and installation of gas piping.
NOTE: Never exceed specified pressures for testing. Higher pressure may damage
the gas valve and cause subsequent overfiring, resulting in heat exchanger
failure.
Disconnect this unit and shutoff valve from the gas supply piping system
before pressure testing the supply piping system with pressures in excess of
1/2 psig (3.48 kPa).
A closed return duct system must be used, with the return duct connected to
the furnace. NOTE: Ductwork must never be attached to the back of the furnace.
For installations requiring more than 1800 CFM, use a bottom return or two
sided return. Supply and return connections to the furnace may be made with
flexible joints to reduce noise transmission. To prevent the blower from
interfering with combustion air or draft when a central return is used, a
connecting duct must be installed between the unit and the utility room wall.
Furnace is shipped with the top flanges in the flat position. Before
installing a coil or ducts, the flanges must be bent 90°. A room, closet, or
alcove must not be used as a return air chamber.
When the furnace is used in connection with a cooling unit, the furnace should
be installed in parallel with or on the upstream side of the cooling unit to
avoid condensation in the heating element. With a parallel flow arrangement,
the dampers or other means used to control the flow of air must be adequate to
prevent chilled air from entering the furnace and, if manually operated, must
be equipped with means to prevent operation of either unit unless the damper
is in the full heat or cool position.
This unit must be isolated from the gas supply system by closing its manual
shutoff valve before pressure testing of gas supply piping system with test
pressures equal to or less than 1/2 psig (3.48 kPa).
WARNING
If the gas furnace is installed in a basement, an excavated area or confined
space, it is strongly recommended to contact a certified contractor to install
a gas detecting warning device in case of a gas leak.
Damper must be in open position when appliance main burner is operating.
When the furnace is installed without a cooling coil, it is recommended that a
removable access panel be provided in the outlet air duct. This opening shall
be accessible when the furnace is installed and shall be of such a size that
the heat exchanger can be viewed for visual light inspection or such that a
sampling probe can be inserted into the airstream. The access panel must be
made to prevent air leaks when the furnace is in operation.
15
NOTE: In a horizontal installation the air conditioning coil must be
adequately supported by proper brackets and supports. Inadequate coil support
can result in furnace cabinet distortion and air leakage.
When the furnace is heating, the temperature of the return air entering the
furnace must be between 55°F and 100°F.
When a furnace is installed so that supply ducts carry air circulated by the
furnace to areas outside the space containing the furnace, the return air
shall also be handled by a duct sealed to the furnace casing and terminating
outside the space containing the furnace.
FILTER FILTER
CENTRAL RETURN GRILLE
SIDE RETURN EXTERNAL FILTER
RACK KIT (EITHER SIDE)
AIR FLOW
WARNING
Edges of sheet metal holes may be sharp. Use gloves as a precaution when
removing sheet metal from return air openings.
Filters – Read This Section Before Installing The Return Air Ductwork Filters
must be used with this furnace. Discuss filter maintenance with the building
owner. Filters do not ship with this furnace, but must be provided by the
installer.
Filters must comply with UL900 or CAN/ULCS111 standards. Damage or repairs due
to failure to install filters in the furnace are not covered under the
warranty.
NOTE: An undersized opening will cause reduced airflow. Refer to the Filter
Sizing Chart to determine filter area requirements.
Upright Installations Depending on the installation and/or customer
preference, differing filter arrangements can be applied. Filters can be
installed in the central return register or a side panel external filter rack
kit (upflows). As an alternative, a media air filter or electronic air cleaner
can be used as the primary filter. The following figure shows possible filter
locations.
Upright Upflow Figure 9
Circulation Air Filters One of the most common causes of a problem in a forced
air heating system is a blocked or dirty filter. Circulating air filters must
be inspected monthly for dirt accumulation and replaced if necessary. Failure
to maintain clean filters can cause premature heat exchanger failure.
A new home may require more frequent replacement until all construction dust and dirt is removed. Circulating air filters are to be installed in the return air duct external to the furnace cabinet.
Upflow / Horizontal Models
Minimum Recommended Filter Size^
*M9S8000403AU 1 – 16 X 25 Side or 1 -14 X 24 Bottom Return
*M9S800603AU 1 – 16 X 25 Side or 1 -14 X 24 Bottom Return
*M9S800604BU 1 – 16 X 25 Side or 1 – 16 X 25 Bottom Return
*M9S800804BU 1 – 16 X 25 Side or 1 – 16 X 25 Bottom Return
*M9S800805CU
2 – 16 X 25 Side Return or 1 – 20 X 25 Bottom Return
^Larger filters may be used, filters may also be centrally located Table 7
Horizontal Installations Filters must be installed in either the central
return register
or in the return air duct work.
NORMAL SEQUENCE OF OPERATION
Power Up · 120 VAC power applied to furnace. · Integrated ignition control performs internal checks. · Upon power-up of the control board, all Seven segments will be illuminated displaying “8 8 8”. After power-up the displays will show “I d L”, idle, or standby mode.
16
· The control is now ready to receive demands from the room thermostat. Refer
to Status Menu in this manual for interpretation of items displayed in the
status menu.
Gas Heating Mode The normal operational sequence in gas heating mode is as
follows:
· R and W thermostat contacts close, initiating a call for heat. The control
will display heat mode in status menu: – g h
· Integrated control module performs safety circuit checks.
· Induced draft blower is energized for 30 second prepurge period causing
pressure sensor contacts to close.
· Igniter warm up begins after 30 second prepurge expires.
· Gas valve opens at end of igniter warm up period, delivering gas to burners
and establishing flame.
· Integrated control module monitors flame presence. Gas valve will remain
open only if flame is detected.
· Circulator blower is energized on user selected heat speed following a fixed
thirty second blower on delay. Electronic air cleaner and humidifier terminal
relays are energized with circulator blower.
· Furnace operates; integrated control module monitors safety circuits
continuously.
· R and W thermostat contacts open, completing the call for heat.
· Gas valve closes, extinguishing flame. · Induced draft blower is de-
energized following a
thirty second post purge. · HUM terminal relay is de-energized. · Circulator
blower continues running for selected heat
off delay. If required this can be changed in the field. · Electronic air
cleaner is de-energized. · Furnace awaits the next call from thermostat.
Cooling Mode The control board support two stages of cooling. If this furnace
is installed with a single stage cooling unit or heat pump, the Y1 terminal of
the control board must be used. A Y2 call on the control board will be ignored
if a Y1 call is not present.
· After the thermostat is satisfied, the compressor is de-energized and the
Cool Mode Fan Off Delay period begins.
· Following the Cool Mode Fan Off Delay period, the indoor fan and air cleaner
relays are de-energized
2nd Stage Cooling Mode Sequence: NOTE: A Y1 call must be present or a Y2 call
will be ignored.
· On a call for 2nd stage cooling, the Y2 or Y2 and G thermostat contacts
close signaling the furnace control board with 24 vac. on Y2 or Y2 and G
terminals.
· The 7-Segment will display: 2 A C · The compressor and condenser fan are
energized. · The circulator fan is energized at cool speed after a
cool on delay. The electronic air cleaner EAC relay will close the EAC
contacts. · After the thermostat is satisfied, the compressor is de-energized
and the Cool Mode Fan Off Delay period begins. · Following the Cool Mode Fan
Off Delay period, the indoor fan and air cleaner relays are de-energized
HEAT PUMP MODE
1st Stage HP Heating Mode Sequence: · On a call for low stage HP Heating, the
Y1 or Y1 and G thermostat contacts close signaling the furnace control board
with 24 vac. on Y1 or Y1 and G terminals. · The 7-Segment will display: 1 H P
· The compressor and condenser fan are energized. · The circulator fan is
energized at HP1 fan speed after the HP on delay period. The electronic air
cleaner, EAC, and humidifier, HUM, relays will close the contacts. · After the
thermostat is satisfied, the compressor is de-energized and the electronic air
cleaner EAC and humidifier HUM relays de-energize. The HP Heat Mode Fan Off
Delay period begins. · Following the HP Heat Mode Fan Off Delay period, the
indoor fan, EAC, & HUM relays are de-energized.
COOLING MODE SEQUENCE OF OPERATION
2nd Stage HP Heating Mode Sequence: NOTE: A Y1 call must be present or a Y2 call will be ignored.
1st Stage Cooling Mode Sequence: · On a call for low stage cooling, the Y1 or Y1 and G thermostat contacts close signaling the furnace control board with 24 vac. on Y1 or Y1 and G terminals. · The 7-Segment will display: 1 A C · The compressor and condenser fan are energized. · The circulator fan is energized at low cool speed after the cool on delay period. The electronic air cleaner EAC relay will close the EAC contacts.
· On a call for 2nd stage HP Heating, the Y2 or Y2 and G thermostat contacts
close signaling the furnace control board with 24 vac. on Y2 or Y2 and G
terminals.
· The 7-Segment will display: 2 H P · The compressor and condenser fan are
energized. · The circulator fan is energized at HP2 fan speed
after the HP on delay period. The electronic air cleaner EAC and humidifier
HUM relays will close the contacts.
17
· After the thermostat is satisfied, the compressor is de-energized and the
electronic air cleaner EAC and humidifier HUM relays de-energize. The HP Heat
Mode Fan Off Delay period begins.
· Following the HP Heat Mode Fan Off Delay period, the indoor fan, EAC, & HUM
relays are de-energized.
Fan Only Mode The normal operational sequence in fan only mode is as follows:
· R and G thermostat contacts close, initiating a call for fan.
· Integrated control module performs safety circuit checks.
· Circulator blower is energized on user selected fan speed. Electronic air
cleaner terminal relay is energized.
· Circulator blower runs, integrated control module monitors safety circuits
continuously.
· R and G thermostat contacts open, completing the call for fan.
· Circulator blower is de-energized. Electronic air cleaner terminal relay is
de-energized.
· Furnace awaits the next call from thermostat.
The integrated furnace control board is equipped with two push-button switches
used to access & navigate menus for furnace setup & settings. The 3 x Seven
Segment Displays on the control board will show the current selection.
Upon power-up of the control board, all Seven segments will be illuminated
displaying “8 8 8”. After power-up the displays will show “I d L”, idle, or
stand-by mode. The control is now ready to receive demands from the room
thermostat. Refer to Status Menu in this manual for interpretation of items
displayed in the status menu.
Quick Start Initial set up of outdoor systems are required to be configured
through the control board. Navigate to OdS menu using the push buttons to
properly configure the outdoor system. Selections for AC1, AC2, HP1, HP2 must
be made to enable specific fan speeds and thermostat signals to function.
NOTE: Equipment type (Single-stage cooling, Twostage cooling, Single-stage
heat pump, Two-stage heat pump) MUST be setup through the OdS menu by the
installer for proper system operation.
Defrost Mode Defrost call can only be generated with heat pump outdoor unit
properly configured in the OdS menu.
· On a call for Defrost, the Y1 or Y1 with Y2 with/ without O contacts and W
thermostat contacts close signaling the furnace control board to enter
defrost.
· If Y with O and W are present simultaneously, the blower shall be energized
at Cooling Speed after COOL on delay, then, switch the blower speed to the
Greater of (Cooling Speed or Gas Heat speed) after Gas Heat On Delay expired.
· If Y without O and W are present simultaneously, the blower shall be
energized at HP Heat Speed after HP Heat On Delay, then, switch the blower
speed to the Greater of (HP Heat Speed or Gas Heat speed) after Gas Heat On
Delay expired.
· The 7-Segment will display: d F t · The electronic air cleaner EAC and
humidifier HUM
relays will close the contacts. · After the thermostat is satisfied, the gas
valve will de-
energize. The Gas Heat Mode Fan Off Delay period begins. · Following the Gas
Heat Mode Fan Off Delay period, the indoor fan, EAC, & HUM relays are de-
energized.
START-UP PROCEDURE AND ADJUSTMENT
Furnace must have a 120 VAC power supply properly connected and grounded.
Proper polarity must be maintained for correct operation. An interlock switch
prevents furnace operation if the blower door is not in place. Keep the blower
access door in place except for inspection and maintenance.
Using Push-Button Switches All user settings may be accessed by two push-
button switches on the control board. The switches are identified as “menu” &
“option”. To enter the main menu, press the “menu” switch. Each time the menu
switch is pressed the display will show the next available item in the main
menu.
While in the main menu, press the “option” switch to scroll through available
options corresponding to the main menu item displayed. In the option menu, the
default option will be displayed first. If the default option has been changed
to another option, the current option selection will be displayed first.
The option menu will display both adjustable & nonadjustable options. When an
adjustable option is displayed, the display will flash continuously until a
switch is pressed. If a non-adjustable option is displayed (such as Code
Release Number) the display will not flash.
While navigating the option menus, press the menu switch to select the
displayed option. The displayed selection will stop flashing indicating the
selection was made. Press the menu button again to finalize the selection and
return to the corresponding main menu.
In the option menu, after the last option has been displayed, the display will
revert to the corresponding main menu & display the default (or selected)
option. If switches are inactive for 30 seconds the display will revert to the
status menu.
18
Control Board Main Menu
Description
Main Menu LED
Display
Option Menu LED Display
Idle – system awaiting i dl
input
ng
Display Active Alarm Er r
chart for alarm code
Display Last 6 Faults L6F
definition
Code Release Number Cr None
Shared Data Revision
Sr
None
Reset to Factory
r Fd
Default
Yes / No
OdS AC1 / AC2 / HP1 /
Outdoor Setting Menu
HP2 / OFF
Blower Speed for
FSd
Continuous Fan Mode
F01 – F09
Blower Speed for 1st
AC1
Stage Compressor
Mode
F01 – F09
Blower Speed for 2nd AC2
Stage Compressor
Mode
F01 – F09
CFd
Cooling Fan Off Delay
Cooling Fan On Delay Blower Speed for Gas
Heat Mode
Gas Heat Off Delay Gas Heat On Delay –
locked Blower Speed for 1st Stage HP Heat Mode Blower Speed for 2nd Stage HP
Heat Mode
0 – 120 seconds Cnd
0 – 35 seconds gAF
Allowable speeds Fxx gFd
30 – 120 seconds gnd
None HP1
F01 – F09 HP2
F01 – F09 HFd
HP Heat Off Delay HP Heat On Delay
30 – 120 seconds Hnd
5 – 30 seconds
Default
OFF
F01
Model specific
Model specific
65 seconds
7 seconds
Model specific
90 seconds
30 seconds
Model specific Model specific
60 seconds
5 seconds
Control Board Status Menu LED Description of System Status Display
888
All segments illuminated = control powering up
I DL Idle
FAn Constant Fan
1AC Low Stage Cooling
2AC High Stage Cooling
1AC Compressor Heat, Low Stage
2AC Compressor Heat, High Stage
gH Gas Heat
1HP Low Stage HP
2HP High Stage HP
dFt Defrost
Furnace operation Purge gas lines of air prior to start-up. Do not purge lines
into an enclosed burner compartment. Follow NFPA 54, National Fuel Gas Code
8.1 for proper purging methods. Check for leaks using an approved chloride-
free soap and water solution, an electronic combustible gas detector, or other
approved method.
NOTE: An interlock switch prevents furnace operation if the blower door is not
in place. Keep the blower access doors in place except for inspection and
maintenance.
Furnace Start-up 1. Close the manual gas shutoff valve external to the
furnace. 2. Turn off the electrical power to the furnace. 3. Set the room
thermostat to the lowest possible setting. 4. Remove the burner compartment
door.
NOTE: This furnace is equipped with an ignition device which automatically
lights the burner. Do not try to light the burner by hand.
5. White-Rodgers valves: Push the switch to the OFF position.
6. Wait five minutes then smell for gas. Be sure to check near the floor, as
some types of gas are heavier than air.
7. If gas can be smelled following the five minute waiting period in Step 6,
immediately follow the instructions on Page 3 of this manual. If you do not
smell gas after five minutes: White-Rodgers valves: Push the switch to the ON
position.
8. Replace the door on the front of the furnace. 9. Open the manual gas valve
external to the furnace. 10. Turn on the electrical power supply to the
furnace. 11. Adjust the thermostat to a setting above room
temperature. 12. After the burners are lit, set the room thermostat to
the desired temperature.
NOTE: There will be a delay between thermostat energizing and burner firing.
Furnace Shutdown 1. Set the thermostat to lowest setting. The integrated
control will close the gas valve and extinguish flame. Following a 30 second
delay, the induced draft blower will be de-energized. The circulation blower
will shut down when the time delay expires. Time delay is selectable on all
models. 2. Turn off the electrical power supply to the furnace. 3. Remove the
burner compartment door. 4. White-Rodgers valve: Push switch to the OFF
position.
19
5. Close manual gas shutoff valve external to the furnace.
6. Replace the door on the unit.
Gas Supply Pressure Measurement
CAUTION
To prevent unreliable operation or equipment damage, the inlet gas supply
pressure must be as specified on the unit rating plate with all other
household gas fired appliances operating.
The line pressure supplied to the gas valve must be within the range specified
on Table 9. The supply pressure can be measured at the gas valve inlet
pressure tap or at a hose fitting installed in the gas piping drip leg. The
supply pressure must be measured with the unit OFF. To measure inlet pressure,
use the following procedure.
7. Using a leak detection solution or soap suds, check for leaks at screw
(White-Rodgers valve). Bubbles forming indicate a leak. SHUT OFF GAS AND
REPAIR ALL LEAKS IMMEDIATELY!
8. Measure the gas supply pressure with burners firing. Adjust supply
pressure using the Inlet Gas Supply Pressure table shown below. If supply
pressure reading differs from the table, make necessary adjustments to
pressure regulator, gas piping size, etc., and/or consult with local gas
utility.
INLET GAS SUPPLY PRESSURE
Natural Gas Minimum: 4.5″ w.c. Maximum: 10.0″ w.c.
Table 9
9. Turn OFF all electrical power and gas supply to the system.
10. Remove the manometer hose from the hose barb fitting or inlet pressure
tap.
11. Replace inlet pressure tap: a. White-Rodgers valve: Turn inlet pressure
test screw in to seal pressure port (clockwise, 7 in-lb minimum).
12. Retest for leaks. If bubbles form, shut down gas and repair leaks
immediately.
13. If there are no leaks, turn ON electrical power and gas supply to the
system.
14. Turn valve switch ON.
White-Rodgers Model 36J22Y-204 Figure 10
1. Turn OFF gas to furnace at the manual gas shutoff valve external to the
furnace.
2. Turn OFF all electrical power to the system. 3. Inlet pressure tap
connections:
a. White-Rodgers valve: Back inlet pressure test screw (inlet pressure tap out
one turn (counterclockwise, not more than one turn).
4. Connect calibrated manometer (or appropriate pressure gauge) at either the
gas valve inlet pressure tap or the gas piping drip leg. See WhiteRodgers
36J22Y-204 gas valve Figure 13 for location of inlet pressure tap.
5. Turn ON the gas supply. 6. Turn On power and operate the furnace and all
other
gas consuming appliances on the same gas supply line.
NOTE: If measuring gas pressure at the drip leg, a field-supplied hose barb
fitting must be installed prior to making the hose connection. If using the
inlet pressure Tap on the White-Rodgers gas valve, then use the 36G/J Valve
Pressure Check Kit, Goodman Part No. 0151K00000S.
.
Measuring Inlet Gas Pressure (Alt. Method) Figure 11
20
Gas Manifold Pressure Measurement and Adjustment
CAUTION
To prevent unreliable operation or equipment damage, the gas manifold pressure
must be as specified on the unit rating plate. Only minor adjustments should
be made by adjusting the gas valve pressure regulator.
Only small variations in gas pressure should be made by adjusting the gas
valve pressure regulator. The manifold pressure must be measured with the
burners operating. To measure and adjust the manifold pressure, use the
following procedure.
1. Turn OFF gas to furnace at the manual gas shutoff valve external to the
furnace.
2. Turn OFF all electrical power to the system. 3. Outlet pressure tap
connections:
a. White-Rodgers valve: Back outlet pressure test screw (outlet pressure Tap)
out one turn (counterclockwise, not more than one turn).
4. Connect calibrated manometer (or appropriate pressure gauge) at the gas
valve outlet pressure tap. See White-Rodgers 36J22Y-204 gas valve Figure 13
for location of outlet pressure tap.
5. Turn ON the gas supply. 6. Turn ON power and close thermostat “R” and “W”
contacts to provide a call for heat. 7. Using a leak detection solution or
soap suds, check
for leaks at outlet pressure tap screw (White-Rodgers valve). Bubbles forming
indicate a leak. SHUT OFF GAS AND REPAIR ALL LEAKS IMMEDIATELY! 8. Measure the
gas manifold pressure with burners firing. Adjust manifold pressure using the
following Manifold Gas Pressure table.
Manifold Gas Pressure
Natural Gas
2.8″ – 3.2″ w.c.
Table 10
9. Remove regulator cover screw from the outlet pressure regulator and turn
screw clockwise to increase pressure or counterclockwise to decrease pressure.
Replace regulator cover screw.
10. Turn OFF all electrical power and gas supply to the system.
11. Remove the manometer hose from the hose barb fitting or outlet pressure
tap.
12. Replace outlet pressure tap: a. White-Rodgers valve: Turn outlet pressure
test screw in to seal pressure port (clockwise, 7 in-lb minimum).
13. Turn ON electrical power and gas supply to the system.
14. Close thermostat contacts to provide a call for heat. 15. Retest for
leaks. If bubbles form, SHUT OFF GAS
AND REPAIR ALL LEAKS IMMEDIATELY!
Gas Input Rate Measurement (Natural Gas Only) The gas input rate to the
furnace must never be greater than that specified on the unit rating plate. To
measure natural gas input using the gas meter, use the following procedure.
1. Turn OFF the gas supply to all other gas-burning appliances except the
furnace.
2. While the furnace is operating at high fire rate, time and record one
complete revolution of the gas meter dial, measuring the smallest quantity,
usually the dial that indicates 1/2 cu. ft. per revolution. You will use this
number to calculate the quantity of gas in cubic ft. if the furnace would
consume if it ran steadily for one hour (3600 seconds).
3. If the 1/2 cu. ft. dial was used, multiply your number X 2. EXAMPLE: If it
took 23 seconds to complete one revolution of the 1/2 ft. dial (23 x 2 = 46).
This tells us that at this rate, it would take 46 seconds to consume one cu.
ft. of gas. This tells us that in one hour, the furnace would consume 78 cu.
ft. of gas. (3600/46 = 78) The typical value range for 1 cu. ft. of natural
gas is around 1025 BTU. Check with your gas utility, if possible. In this
example, the furnace is consuming 80,000 BTUH. NOTE: The final manifold
pressure cannot vary by more than ± 0.2″ w.c. for Natural from the specified
setting. Consult your local gas supplier if additional input rate adjustment
is required.
4. Turn ON gas and relight appliances turned off in step 1. Ensure all the
appliances are functioning properly and that all pilot burners (if applicable)
are operating.
Temperature Rise Air temperature rise is the temperature difference between
supply and return air. The proper amount of temperature rise is usually
obtained when the unit is operated at the rated input with the “as shipped”
blower speed. If the correct amount of temperature rise is not obtained, it
may be necessary to change the blower speed.
Temperature rise must be within the range specified on the unit rating plate.
An incorrect temperature rise may result in condensing in or overheating of
the heat exchanger. An airflow and temperature rise table is provided in the
Specification Sheet applicable to your model. Determine and adjust temperature
rise as follows:
21
SUPPLY AIR
2. Determine the proper air flow for the cooling system. Most cooling systems
are designed to work with air
volume between 350 and 450 CFM per ton. Most
manufacturers recommend an air flow of about 400 CFM per ton.
Example: 2.5 tons X 400 CFM per ton = 1000 CFM 3. Select the heating speed for
your model from the
heating speed chart in the Specification Sheet. The selected speed must
provide a temperature rise
within the rise range listed with the particular model.
RETURN AIR
Temperature Rise Measurement Figure 12
1. Operate furnace with burners firing approximately 15 minutes. Ensure all
registers are open and all duct dampers are in their final (fully or partially
open) position.
2. Place thermometers in the return and supply ducts as close to the furnace
as possible. Thermometers must not be influenced by radiant heat by being able
to “see” the heat exchanger.
3. Subtract the return air temperature from the supply air temperature to
determine the air temperature rise. Allow adequate time for thermometer
readings to stabilize.
4. Adjust temperature rise by adjusting the circulator blower speed. Increase
blower speed to reduce temperature rise. Decrease blower speed to increase
temperature rise. Refer to the following section for speed changing details.
Circulator Blower Speed Adjustment
WARNING
To avoid personal injury or death due to electrical shock, turn OFF power to
the furnace before changing speed taps.
This furnace is equipped with a multi-speed circulator blower. This blower
provides ease in adjusting blower speeds. The Specification Sheet applicable
to your model provides an airflow table, showing the relationship between
airflow (CFM) and external static pressure (E.S.P.), for the proper selection
of heating and cooling speeds.
1. Determine the tonnage of the cooling system installed with the furnace. If
the cooling capacity is in BTU/hr divide it by 12,000 to convert capacity to
tons. Example: Cooling Capacity of 30,000 BTU/hr. 30,000/12,000 = 2.5 Tons
Continuous Fan Mode Speed Selection To change the main blower speed in
circulation mode, see the following steps:
1. Press menu button until LED displays “FSd”. Press option button and LED
will display the currently selected speed number as Fxx (xx: Blower speed
number from 1 to 9).
2. The control shall cycle through available fan speeds every time the option
button is pressed. All 9 speeds are available for circulation.
3. When the menu button is pressed, the current displayed speed shall stop
flashing. Press the menu button again to select the option and the control
shall immediately apply that blower setting and return to the corresponding
main menu.
THERMOSTAT CALL
AVAILABLE SPEEDS (FSd menu)
F01
F02
F03
F04
G
F05
F06
F07
F08
F09
Circulation Speed Table
Cooling Mode Speed Selection To change the main blower speed in COOLING mode,
follow the following steps:
NOTE: If Heat Pump system is configured in OdS menu (HP1 or HP2) COOLING thermostat calls will include “Y1″/Y2” + “O” terminals energized.
1. Press menu button until LED displays “AC1” (for single stage COOLING) or
“AC2” (for Two stage COOLING). Press option button and the LED will display
the currently selected speed number as Fxx (xx: Blower speed number from 1 to
9).
2. The control shall cycle through available fan speeds every time the option
button is pressed. All 9 speeds are available for both Single and Two Stage
cooling.
22
3. When the menu button is pressed, the current displayed speed shall stop flashing. Press the menu button again to select the option and the control shall immediately apply that blower setting and return to the corresponding main menu.
THERMOSTAT CALL AVAILABLE SPEEDS
(OdS: Terminal)
(AC1 menu)
F01
F02
F03
F04
1AC: Y1
1HP: Y1 + O
F05
F06
F07
F08
F09
Single Stage Cooling Speed Table
THERMOSTAT CALL AVAILABLE SPEEDS
(OdS: Terminal)
(AC2 menu)
F01
F02
F03
F04
2AC: Y1 + Y2
2HP: Y1 + Y2 + O
F05
F06
F07
F08
F09
Two Stage Cooling Speed Table
Gas Heating Mode Speed Selection To change the main blower speed in GAS
HEATING mode, see the following steps:
1. Press menu button until LED displays “gAF”. Press option button and LED
will display the currently selected fan speed as Fxx (xx: Blower speed
number).
2. The control shall cycle through available speed number every time the
option button is pressed.
3. When the menu button is pressed, the current displayed speed shall stop
flashing. Press the menu button again to select the option and the control
shall immediately apply that blower setting and return to the corresponding
main menu.
NOTE: Each furnace model contains different allowable gas heating speeds. Allowable gas heating speeds will be visible within gAF fan speed menu.
Heat Pump Heating Mode Speed Selection To change the main blower speed in Heat
Pump HEATING mode, follow the following steps:
1. Press menu button until LED displays “HP1” (for single stage HP HEATING)
or “HP2″ (for Two stage HP HEATING). Press option button and the LED will
display the currently selected speed number as Fxx (xx: Blower speed number
from 1 to 9).
2. The control shall cycle through available fan speeds every time the option
button is pressed. All 9 speeds are available for both Single and Two Stage HP
HEATING.
3. When the menu button is pressed, the current displayed speed shall be
selected, and control shall apply the newly selected speed in next HP HEATING
call.
THERMOSTAT CALL AVAILABLE SPEEDS
(OdS: Terminal)
(HP1 menu)
F01
F02
F03
F04
1HP: Y1
F05
F06
F07 F08
F09
Single Stage HP Heating Speed Table
THERMOSTAT CALL AVAILABLE SPEEDS
(OdS: Terminal)
(HP2 menu)
F01
F02
F03
F04
2HP: Y1 + Y2
F05
F06
F07
F08
F09
Two Stage HP Heating Speed Table
Circulator Blower Fan Timing Adjustment NOTE: Items in this section refer to the air circulator blower fan, NOT to the induced draft blower. The induced draft blower timing sequence is not adjustable.
The integrated control module on all models provides selectable fan on/off delay adjustments.
23
On/Off Fan Delay Selection To change the fan on or off delay for COOLING, HP
HEATING & GAS HEATING modes, see the following steps:
1. Press menu button until LED displays the desired on/ off setting (See MAIN
MENU section for selectable blower on/off delay options). Press option button
and LED will display the selected on/off delay time in seconds.
2. The control shall cycle through available on/off delay times every time
the option button is pressed.
3. When the menu button is pressed, the current displayed on/off delay shall
stop flashing. Press the menu button again to select the option and the
control shall immediately apply that delay setting and return to the
corresponding main menu.
OPERATIONAL CHECKS
WARNING
EXAMPLE: static reading from return duct = -.1″ w.c. static reading from
supply duct = .3″ w.c. total external static pressure on this system = .4”
w.c.
NOTE: Both readings may be taken simultaneously and read directly on the
manometer if so desired. If an air conditioner coil or Electronic Air Cleaner
is used in conjunction with the furnace, the readings must also include theses
components, as shown in the following drawing.
4. Consult proper tables for the quantity of air.
If the total external static pressure exceeds the maximum listed on the
furnace rating plate, check for closed dampers, registers, undersized and/or
oversized poorly laid out duct work. The temperature rise of the furnace must
be within the temperature rise range listed on the furnace rating plate.
To avoid personal injury or death, do not remove any internal compartment covers or attempt any adjustment. Electrical components are contained in both compartments. Contact a qualified service agent at once if an abnormal operation should develop.
Checking Duct Static Refer to your furnace rating plate for the maximum ESP
(external duct static) rating.
Total external static refers to everything external to the furnace cabinet. Cooling coils, filters, ducts, grilles, registers must all be considered when reading your total external static pressure. The supply duct pressure must be read between the furnace and the cooling coil. This reading is usually taken by removing the “A” shaped block off plate from the end on the coil; drilling a test hole in it and reinstalling the block off plate. Take a duct static reading at the test hole. Tape up the test hole after your test is complete. The negative pressure must be read between the filter and the furnace blower.
.
Checking Static Pressure (80% Furnace Shown) Figure 13
SAFETY CIRCUIT DESCRIPTION
Too much external static pressure will result in insufficient air that can
cause excessive temperature rise. This can cause limit switch tripping and
heat exchanger failure. To determine total external duct static pressure,
proceed as follows:
1. With clean filters in the furnace, use a manometer to measure the static
pressure of the return duct at the inlet of the furnace. (Negative Pressure)
2. Measure the static pressure of the supply duct. (Positive Pressure)
3. The difference between the two numbers is .4″ w.c.
General
WARNING
To avoid personal injury or death, do not remove any internal compartment
covers or attempt any adjustment. Electrical components are contained in both
compartments. Contact a qualified service agent at once if an abnormal
operation should develop.
WARNING
Do not bypass safety devices.
24
A number of safety circuits are employed to ensure safe and proper furnace
operation. These circuits serve to control any potential safety hazards and
serve as inputs in the monitoring and diagnosis of abnormal function. These
circuits are continuously monitored during furnace operation by the integrated
control module.
Integrated Control Module The integrated control module is an electronic
device which controls all furnace operations. Responding to the thermostat,
the module initiates and controls normal furnace operation, and monitors and
addresses all safety circuits. If a potential safety concern is detected, the
module will take the necessary precautions and provide diagnostic information
through an LED.
Primary Limit The primary limit control is located on the partition panel and
monitors heat exchanger compartment temperatures. It is a normally closed
(electrically), automatic reset, temperature activated sensor. The limit
guards against the overheating resulting from insufficient air passing over
the heat exchanger.
Auxiliary Limit The auxiliary limit control is located either on or near the
circulator blower and monitors heat exchanger compartment temperatures. The
control is a normally closed (electrically), automatic reset, temperature
activated sensor. It guards against overheating resulting from insufficient
air passing over the heat exchanger. The auxiliary limit control is suitable
for both horizontal right and horizontal left installations. Regardless of
airflow direction, it does not need to be relocated.
Burner Temperature Switch The burner temperature switch is mounted on the
burner assembly to monitor the burner box temperature. It is normally closed
(electrically), auto-reset sensor. This switch guards against the burner
flames not being properly drawn into the heat exchanger.
Pressure Sensor The pressure sensor is mounted near induced draft blower. Its
function is to regulate the induced draft blower’s speed in order to maintain
proper air-fuel ratio for clean and reliable combustion. The pressure sensor
also guards against insufficient airflow (combustion air and flue products)
through the heat exchanger.
Flame Sensor The flame sensor is a probe mounted near the burner assembly
which uses the principle of flame rectification to determine the presence or
absence of flame.
TROUBLESHOOTING
Diagnostic Chart Refer to the troubleshooting chart in the Appendix for
assistance in determining the source of unit operational problems. The 3 digit
diagnostic display provides alarm codes to assist in troubleshooting the unit.
Fault Code Retrieval The ignition control is equipped with push buttons that
can be used to the last five faults detected by the control. Navigate the L6F
by pressing the menu button 2 times, then select the option button.
Clear Fault Memory To clear all alarm codes, navigate to the last six faults
menu, L6F, and hold the option button down for 5 seconds.
Resetting From Lockout Furnace lockout results when a furnace is unable to
achieve ignition after three attempts. It is characterized by a non-
functioning furnace and a fault code will be displayed. If the furnace is in
“lockout”, it will (or can be) reset in any of the following ways.
1. Automatic reset. The integrated control module will automatically reset
itself and attempt to resume normal operations following a one hour lockout
period.
2. Manual power interruption. Interrupt 120 volt power to the furnace.
NOTE: If the condition which originally caused the lockout still exists, the
control will return to lockout. Refer to the Diagnostic Chart for aid in
determining the cause.
MAINTENANCE
WARNING
To avoid electrical shock, injury or death, disconnect electrical power before
performing any service or maintenance. Only a qualified servicer should
service or perform maintenance.
Annual inspection The furnace should be inspected by a qualified installer, or
service agency at least once per year. This check should be performed at the
beginning of the heating season. This will ensure that all furnace components
are in proper working order and that the heating system functions
appropriately. Pay particular attention to the following items. Repair or
service as necessary.
25
· Flue pipe system: Check for blockage and/or leakage. Check the outside
termination and the connections at and internal to the furnace.
· Heat exchanger: Check for corrosion and/or buildup within the heat exchanger
passageways.
· Burners: Check for proper ignition, and flame sense. · Wiring: Check
electrical connections for tightness
and/or corrosion. Check wires for damage. · Filters: Check filters and
determine if any need to be
replaced.
Filters
WARNING
To avoid property damage, personal injury or death, disconnect electrical power before removing filters. Never operate furnace without a filter installed because dust and lint will build up on internal parts resulting in loss of efficiency, equipment damage and possible fire.
A return air filter is not supplied with this furnace; however, there must be a means of filtering all of the return air. The installer will supply filter(s) at the time of installation.
Induced Draft and Circulator Blower Motors The bearings in the induced draft blower and circulator blower motors are permanently lubricated by the manufacturer. No further lubrication is required. Check motor windings for accumulation of dust which may cause overheating. Clean as necessary.
Flame Sensor (Qualified Servicer Only) Under some conditions, the fuel or air
supply can create a
nearly invisible coating on the flame sensor. This coating acts as an
insulator causing a drop in the flame sense signal. If the flame sense signal
drops too low the furnace will not sense flame and will lock out. The flame
sensor should be carefully cleaned by a qualified servicer using steel wool.
The flame sense signal should be 1 to 3 microamps.
Igniter (Qualified Servicer Only) At room temperature, the igniter ohm reading
should be
from 20 – 100 ohms.
Burner
WARNING
To prevent personal injury or death, do not remove any internal compartment covers or attempt any adjustment. Electrical components are contained in both compartments. Contact a qualified service agent at once if an abnormal operation should develop.
The Ultra low NOx furnace uses a premix burner. The burner box is sealed to achieve safe and reliable operation.
CLEANING (QUALIFIED SERVICER ONLY)
1. Shut off electric power and gas supply to the furnace. 2. Disconnect the
rollout limit wires, flame sensor wire,
and disconnect the igniter plug.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors
can cause improper and dangerous operation. Verify proper operation after
servicing.
3. Do not remove burner or other components. 4. Clean cabinet and around the
inducer blower, motor
and burner box. 5. Reconnect wiring. 6. Turn on electric power and gas supply
to the furnace. 7. Check furnace for proper operation. Refer to
“Operational Checks” section to verify burner flame characteristics.
BEFORE LEAVING AN INSTALLATION
· Cycle the furnace with the thermostat at least three times. Verify cooling
and fan only operation.
· Review the Owner’s Manual with the homeowner and discuss proper furnace
operation and maintenance.
· Leave literature packet near furnace.
REPAIR AND REPLACEMENT PARTS
· When ordering any of the listed functional parts, be sure to provide the
furnace model, manufacturing, and serial numbers with the order.
· Although only functional parts are shown in the parts list, all sheet metal
parts, doors, etc. may be ordered by description.
· Parts are available from your distributor.
Functional Parts ListGas Valve Natural Gas Orifice Burner Assembly Hot Surface Igniter Flame Sensor Gas Manifold Ignition Control Blower Mounting Bracket Pressure Sensor Pressure Sensor Hose Induced Draft Blower Integrated Control Module Burner Box Gasket
Blower/Collector Box Gasket Primary Limit Switch Burner Temperature Switch Auxiliary Limit Switch Heat Exchanger Door Switch Transformer Blower Wheel Blower Housing Blower Cutoff Blower Motor Motor Mount Bracket
26
COMPONENT ID
2 Pressure Sensor Assembly
3 Flue Pipe Connection
4 Gas Line Entrance 5 Gas Valve 6 Inducer
7 Gas Manifold Assembly
8 Burner Assembly
1 Tubular Heat Exchanger
Integrated 9 Control Module 10 Transformer
11
Blower Door Interlock Switch
12 Circulator Blower
1 Tubular Heat Exchanger 2 Pressure Switch 3 4 Gas Line Entrance 5 Gas Valve 6 Inducer 7 Gas Manifold Assembly
8 Burner Assembly 9 Integrated Control Module 10 Transformer 11 Blower Door
Interlock Switch 12 Circulator Blower
27
TROUBLESHOOTING CHART
Symptom
LED Status
Normal Operation
Furnace fails to operate
Fault Description Stand-by Mode
Normal Operation Internal Control Fault
Corrective Actions
None Replace control board Locate and correct gas interruption
Furnace fails to operate
Furnace lockout due to an excessive number of ignition “retries” (3 total)
Failure to establish flame
Loss of flame after establishment
Replace or realign igniter
Check flame sense signal, clean sensor if coated or oxidized
Check flue piping for blockage, proper length, elbows, and termination
Furnace fails to operate
Induced draft blower runs
continuously with no
operation
Draft Inducer pressure switch circuit is closed at start of heating cycle Draft Inducer pressure switch contacts sticking Short in pressure switch circuit wiring
Verify proper induced draft blower performance Replace Draft Inducer pressure switch Repair short in wiring
Draft Inducer pressure switch circuit is not closed Pressure switch hose
blocked pinched, or connected improperly
Blocked flue and/or inlet air or weak induced draft blower Incorrect pressure
switch set point or malfunctioning switch contacts
Loose or improperly connected wiring in high limit circuit
Inspect pressure switch hose, repair/replace if necessary Inspect flue and/or
inlet air for blockage, proper length, elbows,
and termination Check induced draft blower performance, correct as neccesary
Check pressure switch operation, replace as needed Tighten or correct wiring
connection
Primary limit circuit is open
Check filters and ductwork for blockage
Circulator blower runs continuously
No furnace operation
Induced draft blower and circulator blower runs continuously No furnace
operation
No furnace operation
Insufficient conditioned air over the heat exchanger
Blocked filters, restrictive ductwork, improper circulator blower speed, or
failed circulator blower motor
Loose or improperly connected wiring in high limit circuit
Flame sensed with no call for heat
Short to ground in flame sense circuit
Lingering burner flame
Slow closing gas valve Open fuse
Short in low voltage wiring
Flame sense micro amp signal is minimal
Clean filters or remove obstruction Check circulator blower speed and
performance Correct speed or replace blower motor if necessary
Tighten or correct wiring connection Correct short at flame sensor or in flame
sensor wiring
Check for lingering or lazy flame Verify proper operation of gas valve
Replace fuse Locate and correct short in low voltage wiring
Clean flame sensor if coated or oxidized
Furnace operates but shows weak flame signal
fault
Flame sensor is coated/oxidized Flame sensor incorrectly positioned in burner flame
Inspect for proper flame sensor alignment Check inlet air for blockage
Furnace fails to operate
Lazy burner flame due to improper gas pressure or combustion air Problem with
igniter circuit
Improperly connected or shorted igniter Poor unit ground
Igniter relay fault on integrated control module
Compare current gas pressure to rating plate and adjust as needed Check and
correct wiring from integrated control module to igniter
Diagnose and replace shorted igniter as needed
Verify and correct unit ground wiring if needed
Check igniter output from control, replace if necessary
28
TROUBLESHOOTING CHART
Symptom Furnace fails to operate Furnace fails to operate Furnace fails to
operate Furnace fails to operate Furnace fails to operate
Furnace fails to operate
Furnace fails to operate Furnace fails to operate Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate Furnace fails to operate Furnace fails to operate
LED Status
Fault Description Polarity of 115 volt AC is reversed
Poor unit ground Gas valve is energized when it should not be
Internal gas valve error Gas valve is not energized when it should be
External Gas Valve Error Auxiliary limit switch (blower compartment)
circuit is open Grounding Error
Burner limit switch circuit is open
Redundant relay open alarm Redundant relay stuck closed alarm
Inducer communication alarm APS reference error
APS null error
APS span error
APS pressure error
APS input error Twinning error Low circulator current Circulator current
unexpected No shared data
Corrective Actions Correct polarity, check and correct wiring if necessary
Verify proper ground, correct if necessary Check wiring in gas valve circuit
Replace integrated control board Check wiring in gas valve circuit
Replace integrated control board Furnace power was turned off during heat
cycle
Blower not operating during heat
Faulty aux limit or wiring Check grounding
Check and correct gas supply pressure
Check flue and air inlet for blockage, proper length, elbows, and termination
Check wiring connection in limit circuit
Check burner temperature switch, replace if necessary Replace integrated
control board Replace integrated control board
Check Red, Black, White harness & connections to inducer & control board
Check Red, Black, Green harness & connections to pressure sensor & control
board
Replace pressure sensor Check Red, Black, Green harness & connections to
pressure
sensor & control board
Check pressure hoses to pressure sensor and pressure switch Check Red, Black,
Green harness & connections to pressure
sensor & control board
Check pressure hoses to pressure sensor and pressure switch Check Red, Black,
Green harness & connections to pressure
sensor & control board
Replace pressure sensor Check Red, Black, Green harness & connections to
pressure
sensor & control board
Replace pressure sensor
Check motor 120V line wire is connected to terminal inside current transformer
loop
Check wire connections to motor and PCB Check motor 120V line wire is
connected to terminal inside
current transformer loop Populate shared data set using memory card
29
BLOWER PERFORMANCE DATA
AM9S80-U / GM9S80-U COOLING & CIRCULATION AIRFLOW
MODEL
THERMOSTAT
CALL
TAP # 0.1 CFM
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
0.2
0.3
0.4
0.5
0.6
0.7
CFM
CFM
CFM
CFM
CFM
CFM
F01
590
540
483
429
369
311
247
F02
690
643
597
547
498
443
389
F03
750
702
660
618
572
525
477
F04
876
832
794
758
716
678
641
M9S800403AU Y1/Y2/G F05^
927
881
841
806
771
734
698
F06
1058 1015
976
945
915
881
849
F07
1116 1071 1036 1003
975
943
919
F08^^ 1238
F09
1398
1192 1357
1158 1320
1124 1293
1098 1269
1070 1239
1044 1216
F01
587
542
490
437
382
318
266
F02
685
638
590
543
498
448
392
F03
856
814
774
732
693
657
622
F04^
937
892
855
819
786
752
715
M9S800603AU Y1/Y2/G F05
1060 1017
981
950
921
886
856
F06^^ 1108 1068 1033 1003
972
942
914
F07
1274 1233 1203 1174 1146 1118 1089
F08
1374 1340 1306 1278 1254 1227 1201
F09
1437 1395 1362 1332 1305 1278 1253
F01
836
774
711
655
596
523
456
F02
1274 1228 1188 1147 1107 1064 1027
F03
1295 1256 1214 1181 1140 1100 1062
F04
1385 1337 1301 1260 1222 1186 1149
M9S800604BU Y1/Y2/G F05
1454 1407 1372 1353 1325 1291 1255
F06^ 1528 1485 1438 1409 1383 1349 1317
F07
1619 1579 1551 1523 1495 1463 1430
F08^^ 1746 1697 1667 1642 1617 1593 1570
F09
1772 1735 1698 1674 1645 1622 1598
F01
722
658
599
534
458
386
330
F02
1270 1223 1179 1139 1105 1066 1029
F03
1304 1254 1212 1173 1135 1104 1069
F04
1367 1318 1277 1236 1199 1169 1135
M9S800804BU Y1/Y2/G F05^ 1473 1429 1386 1355 1320 1289 1258
F06
1560 1518 1476 1441 1409 1382 1350
F07
1647 1605 1562 1531 1497 1467 1440
F08^^ 1720 1710 1674 1642 1611 1581 1553
F09
1796 1759 1721 1687 1655 1628 1604
F01
1280 1228 1178 1134 1086 1036
986
F02
1401 1356 1313 1273 1234 1190 1145
F03
1593 1550 1512 1475 1436 1399 1360
F04
1706 1662 1621 1586 1550 1515 1479
M9S800805CU Y1/Y2/G F05^ 1821 1775 1736 1703 1669 1636 1605
F06
1836 1793 1757 1721 1689 1659 1628
F07
1932 1888 1855 1825 1794 1762 1733
F08^^ 2184
F09
2221
2143 2178
2110 2145
2072 2109
2048 2082
2017 2053
1989 2025
Default speed is F01 for circulation for all models ^ Default Y1 speed ^^ Default Y2 speed
0.8 CFM 203 343 421 598 662 818 884 1016 1194 207 339 581 684 828 882 1065 1179 1228 397 990 1024 1114 1219 1285 1402 1540 1574 268 996 1032 1102 1224 1321 1408 1527 1578 936 1099 1319 1444 1576 1592 1701 1959 1992
30
BLOWER PERFORMANCE DATA
MODEL
THERMOSTAT TAP #
CALL
F02
F03^
M9S800403AU
W/W1
F04 F05
F06
F07
F05
M9S800603AU W/W1 F06
F07^
F02
M9S800604BU
W/W1
F03
F04^
F05
F02^
M9S800804BU W/W1 F03
F04
M9S800805CU
W/W1
F01 F02^
AM9S80-U / GM9S80 HEATING AIRFLOW
EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)
0.1
0.2
0.3
0.4
0.5
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
690
42
643
46
597
49
547
53 498 55
750
39
702
42
660
45
618
48 572 52
876
34
832
36
794
37
758
39 716 41
927
32
881
34
841
35
806
37 771 38
1058 28 1015 29
976
30
945
31 915 32
1116 27 1071 28 1036
29
1003
30
975 30
1060 42 1017 44
981
45
950
47 921 48
1108 40 1068 42 1033
43
1003
44
972 46
1274 35 1233 36 1203
37
1174
38 1146 39
1274 35 1228 36 1188
37
1147
39 1107 40
1295 34 1256 35 1214
37
1181
38 1140 39
1385 32 1337 33 1301
34
1260
35 1222 36
1454 31 1407 32 1372
32
1353
33 1325 34
1270 47 1223 48 1179
50
1139
52 1105 54
1304 45 1254 47 1212
49
1173
51 1135 52
1367 43 1318 45 1277
46
1236
48 1199 49
1280 46 1228 48 1178
50
1134
52 1086 55
1401 42 1356 44 1313
45
1273
47 1234 48
0.6 CFM 443 525 678 734 881 943 886 942 1118 1064 1100 1186 1291 1066 1104 1169 1036 1190
^ Default Heat Speed
0.7 CFM 389 477 641 698 849 919 856 914 1089 1027 1062 1149 1255 1029 1069 1135 986 1145
0.8 CFM 343 421 598 662 818 884 828 882 1065 990 1024 1114 1219 996 1032 1102 936 1099
TEMP RANGE
25 – 55
20 – 50 20 – 50 35 – 65 35 – 65
31
WIRING DIAGRAM
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
INTEGRATED CONTROL MODULE LINE NEUTRALS
GN
PRESSURE TRANSDUCER
RD
1 5V
2 UNUSED
GN
3 GND
4 PI
BK
BR ID BLOWER
PRESSURE
SWITCH
OR
C
NO
C 2 BR
M1
BL
GAS VALVE
GND
WH WH
HOT SURFACE
AUTO RESET PRIMARY LIMIT CONTROL
IGNITER
BL 1 2 2 CIRCUIT
CONNECTOR
PU AUTO RESET
BURNER BOX LIMIT
BL
BR
BK 1 BK RD 2 RD WH 3 WH
BURNER COMPARTMENT
BLOWER COMPARTMENT
INDUCED DRAFT (ID) BLOWER
GND
PU
YL
SENSOR
FLAME
WH
BK JUNCTION BOX
GND
TO 115 VAC/ 1 Ø /60 HZ POWER SUPPLY WITH OVERCURRENT PROTECTION DEVICE
L
DISCONNECT
WARNING:DISCONNECT POWER BEFORE N SERVICING. WIRING TO UNIT MUST BE
PROPERLY POLARIZED AND GROUNDED.
TR (2)
INTEGRATED CONTROL MODULE
GN GND
TO MICRO TO R
INDOOR AIR
CIRCULATOR BLWR
C
MVC (5) C
MVC (8)
G
Y TO MICRO
M MVL(9)
E
1 8
(4)
PS1 (3) ID BLOWER
PRESSURE SWITCH C
PSO (12)
GAS VALVE
(3)
NO
PRESSURE TRANSDUCER
(1)
W
HLO (4)
AUTO RESET AUTO RESET
AUXILIARY
PRIMARY
LIMIT
LIMIT
ALI (1)
CONTROL
CONTROL
YL
WH RD BK
OR BR BR GR BL
BL PK BR
PU
FUSE
PK
AUTO RESET AUXILIARY LIMIT CONTROL
WH RD
GND
E41
U V W
E47 E19 NEUTRAL
FP
BLW E22
E23
LINE E46 E25 E26
W11 W12
E5
N H
PSO
BLI MVH
MVL GND
E18
HLI
GND
TH MVC
PI 5V
HLO
PS1
TR
ALI
HUM
EAC
E42
E35
E44
E43
E4
TAP1 TAP2 TAP3 TAP4 TAP5 GND
TWIN O W1 R G BCY1 Y2
WH BK
WH BK
BLOWER COMPARTMENT DOOR-SWITCH (OPEN WHEN DOOR OPEN)
ECM MTR HARNESS
WH BK
BK
BLI (11)
TH (6)
HLI (7)
40 VA TRANSFORMER
XFMR-H
24 VAC 120 VAC
AUTO RESET BURNER BOX LIMIT
FLAME SENSOR
FS HSI(1)
HOT SURFACE IGNITER
IDB(2)
ID BLOWER
GND
CIRCULATOR BLOWER
GND
LINE-H
DOOR SWITCH
JUNCTION BOX
GND
GN BK RD
NOTE 6
BL RD OR BKYL
NOTE 5
BL RD
5 4321
24 VAC
RD BL BKOR YL
115 VAC 40 VA
TRANSFORMER WH BK
Status & Fault (see installation manual for complete list of faults)
Idle Continuous fan Low Stage Cooling High Stage Cooling
Gas Heat HP Heat, Low Stage HP Heat, High Stage
Defrost Lockout Due to Excessive Retries Recycle Pressure Switch Closed When
Expected To Be Open Pressure Switch Open When Expected To Be Closed
Open High Limit Switch Flame Detected When No Flame Should Be Present
Open Fuse Low Flame Signal Ignitor Fault Or Ignitor Relay Fault Reversed Line
Polarity Grounding Error Inernal Gas Valve Error External Gas Valve Error Aux
Limit Switch Open Burner Limit Switch Open
CIRCULATOR BLOWER
4 WH
3
GN
2
BK
1 RD
WARNING:
DISCONNECT POWER BEFORE SERVICING.
DISCONNECT
WIRING TO UNIT
MUST BE
PROPERLY
POLARIZED
AND GROUNDED.
L GND
N
TO 120VAC/ 1 Ø /60 HZ POWER SUPPLY WITH
OVERCURRENT PROTECTION DEVICE
Seven Segment Display
Seg. 1 Seg. 2 Seg. 3
1
d
L
F
A
n
1
A
C
2
A
C
g
H
1
H
P
2
H
P
d
F
t
E
E
0
E
E
1
E
E
2
E
E
3
E
E
4
E
E
5
E
E
6
E
E
7
E
E
A
E
1
0
E
E
b
E
E
C
E
E
d
E
1
I
NOTES:
1. MANUFACTUR’S SPECIFIED REPLACEMENT
EQUIPMENT GND
PARTS MUST BE USED WHEN SERVICING. 2. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED
WITH THE FURNACE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL
FIELD GND FIELD SPLICE SWITCH (TEMP.)
HAVING A TEMPERATURE RATING OF AT LEAST
IGNITER
105°C. USE COPPER CONDUCTORS ONLY. 3. BLOWER SPEEDS SHOULD BE ADJUSTED BY
INSTALLER TO MATCH THE INSTALLATION REQUIREMENTS SO AS TO PROVIDE
SWITCH (PRESS.) OVERCURRENT PROT. DEVICE
THE CORRECT HEATING TEMPRATURE
LOW VOLTAGE (24V)
RISE AND THE CORRECT COOLING CFM. 4. UNIT MUST BE PERMANENTLY GROUNDED
AND CONFORM TO N.E.C. AND LOCAL CODES. 5. EAC. NORMALLY OPEN CONTACTS FOR
OPTIONAL
LOW VOLTAGE FIELD HI VOLTAGE (120V) HI VOLTAGE FIELD
ELECTRONIC AIR CLEANER USE. CONTACTS
INTERNAL TO
CLOSE
INTEGRATED CONTROL
WHEN INDOOR BLOWER IS RUNNING. TERMINALS
PLUG CONNECTION
ARE NOT INTERNALLY POWERED 6. HUM. NORMALLY OPEN CONTACTS FOR OPTIONAL JUNCTION
TERMINAL
HUMIDIFIER USE. CONTACTS CLOSE WHEN DRAFT INDUCER IS RUNNING. TERMINALS ARE NOT
OUTPUT
INTERNALLY POWERED
COLOR CODES:
BK BLACK BL BLUE BR BROWN GR GREEN
GY GRAY OR ORANGE PK PINK PU PURPLE
RD RED WH WHITE YL YELLOW
0140F02646-A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 32
START-UP CHECKLIST
Furnace
ELECTRICAL Line Voltage (Measure L1 to N and N to Ground Voltage)
Secondary Voltage (Measure Transformer Output Voltage) Blower Amps
Model Number Serial Number
L – N N – G R – C
BLOWER EXTERNAL STATIC PRESSURE Return Air Static Pressure Supply Air Static
Pressure Total External Static Pressure (Ignoring +/- from the reading above,
add total here)
TEMPERATURES Return Air Temperature (Dry bulb / Wet bulb) Cooling Supply Air
Temperature (Dry bulb / Wet bulb) Heating Supply Air Temperature Temperature
Rise Delta T (Difference between Supply and Return Temperatures)
GAS PRESSURES Gas Inlet Pressure Gas Manifold Pressure (Low Fire) Gas Manifold
Pressure (High Fire)
Gas Type (NG) = Natural Gas / (LP) = Liquid Propane
Additional Checks Check wire routings for any rubbing Check for kinked pressure switch tubing. Check flue elbow for alignment and clamp tightness. Check screw tightness on blower wheel. Check factory wiring and wire connections. Check product for proper clearances as noted by installtion instructions
°F to °C formula: (°F – 32) divided by 1.8 = °C
°C to °F formula: (°C multiplied by 1.8) + 32 = °F
IN. W.C. IN. W.C. IN. W.C.
DB °F DB °F DB °F DB °F DB °F
IN. W.C. IN. W.C. IN. W.C.
WB °F WB °F
33
THIS PAGE INTENTIONALLY LEFT BLANK
34
THIS PAGE INTENTIONALLY LEFT BLANK
35
CUSTOMER FEEDBACK We are very interested in all product comments. Please fill
out the feedback form on one of the following links: Goodman® Brand Products:
(http://www.goodmanmfg.com/about/contact-us). Amana® Brand Products:
(http://www.amana-hac.com/about-us/contact-us).
You can also scan the QR code on the right for the product brand you purchased
to be directed to the feedback page.
GOODMAN® BRAND
AMANA® BRAND
PRODUCT REGISTRATION Thank you for your recent purchase. Though not required
to get the protection of the standard warranty, registering your product is a
relatively short process, and entitles you to additional warranty protection,
except that failure by California and Quebec residents to register their
product does not diminish their warranty rights.
For Product Registration, please register as follows: Goodman® Brand products:
(https://www.goodmanmfg.com/product-registration). Amana® Brand products:
(http://www.amana-hac.com/product-registration). You can also scan the QR
code on the right for the product brand you purchased to be directed to the
Product Registration page.
GOODMAN® BRAND
AMANA® BRAND
19001 Kermier Rd. Waller, Tx 77484
www.goodmanmfg.com · www.amana-
hac.com © 2021-2022 Goodman Manufacturing Company,
L.P.
is a registered trademark of Maytag Corporation or its related companies and
is used under license. All rights reserved. 36
References
- Quality, Durable Heating & Air Conditioning Systems From Amana
- Contact Amana Heating & Air Conditioning
- Register Your Amana Heating And Cooling Equipment Here
- Air Conditioning and Heating Systems| HVAC | Goodman
- Contact Us | Goodman Manufacturing
- Warranty Registration | Register Your Goodman HVAC Product
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>