AJAX FireProtect Plus Intruder Detector User Manual
- June 5, 2024
- ajax
Table of Contents
- AJAX FireProtect Plus Intruder Detector
- Functional Elements
- Operating Principle
- Connecting the Detector to the Ajax Security System
- Connecting to Third-Party Security Systems
- Interconnected FireProtect Alarms Setup
- Setting the Residential re-alarm system
- Performance testing
- Installation
- Maintenance and Battery Replacement
- Tech Specs
- Warranty
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
AJAX FireProtect Plus Intruder Detector
FireProtect (FireProtect Plus) is a wireless indoor detector with an in-built
buzzer and a battery, ensuring up to 4 years of autonomous operation.
FireProtect can detect smoke and rapid temperature increase.
Aside from these functions, FireProtect Plus additionally can alert of
dangerous CO level. Both detectors can function independently from the hub.
Connecting to the Ajax security system via a secured Jeweller radio protocol,
FireProtect (FireProtect Plus) communicates with hub the at a distance of up
to 1,300 m in line of sight.
The detector can be a part of third-party security systems, connecting to them
via the Ajax cartridge or Ajax Oxbridge Plus integration module. Buy re
detector with carbon monoxide sensor Fire Protect PlusThe detector is set up
via the Ajax apps for iOS, Android, macOS, and Windows. The system notifies
the user of all events through push notifications, SMS, and calls (if
activated).
The Ajax security system can be connected to a central monitoring station of a
security company. Buy re detector FireProtect
Functional Elements
- Siren hole
- Light indicator (acts as the sensor and Test button)
- Smoke chamber hole with the temperature detector behind the net
- SmartBracket attachment panel
- Power button
- Tamper button
- QR code
Operating Principle
When smoke penetrates the detector chamber, it distorts infrared light between the emitter and the photoelectric receiver. This distortion triggers a smoke alarm. When the temperature exceeds 60°С or rises by 30°С during 30 minutes (not necessary to reach 60°С), the detector registers a temperature to increase, which triggers a re alarm.
The life span of the FireProtect Plus detector lasts up to 7 years (up to 10
years for the FireProtect ). In the event of a detector failure, you will
receive a corresponding notication —it will need to be replaced or submitted
for comprehensive diagnostics
FireProtect Plus has an additional sensor to detect a dangerous CO level. If
the concentration of CO in the air exceeds a certain level, the detector
generates an alarm.
The detector is triggered:
- within 60–90 min at carbon oxide concentration 50 ppm / 0.005%
- within 10–40 min at CO concentration 100 ppm / 0.01%
- within 3 min at carbon oxide concentration 300 ppm / 0.03%.
In case of alarm, the detector activates the built-in buzzer (the siren sound can be heard from afar) and blinks with the light indicator. When connected to a security system, both the user and the security company are notied of the alarm. The siren of the device can be turned off using three ways:
- By pressing the Ajax logo on the device lid (there is a touch button under the logo).
- Through the Ajax app. In case of re-alarm, you will see a pop-up message in Ajax app suggesting to turn off the built-in sirens.
- Using the KeyPad/KeyPad Plus (if the Interconnected FireProtect Alarms feature is enabled). To turn off the built-in sirens in case of re-alarm, press the “*” button on the KeyPad/KeyPad Plus.
Please note that for this to work you need to priorly select Mute
Interconnected Fire Alarm command for this button in the KeyPad/KeyPad Plus
settings.
If smoke and/or temperature levels do not restore to normal values, in 10
minutes, the FireProtect/FireProtect Plus turns on the siren again.
Connecting the Detector to the Ajax Security System
Connecting to the hub
Before starting the connection:
- Following the hub user guide, install the Ajax app . Create the account, add the hub, and create at least one room.
- Switch on the hub and check the internet connection (via Ethernet cable and/or GSM network).
- Make sure that the hub is disarmed and does not update by checking its status in the Ajax app.
Pairing the detector with hub:
- Select Add Device in the Ajax app.
- Name the device, scan or type the QR Code (located on the detector body and packaging), and select the location room.
- Tap Add — the countdown will start.
- Switch on the device.
To make sure that the detector is on, press the on/off button — the logo will
light up red for a second.
For detection and pairing to occur, the detector should be located within the
coverage area of the wireless network of the hub (at a single protected
object). The connection request is transmitted for a short time: at the moment
of switching on the device. If pairing with the hub fails, the detector
operates autonomously; switch off the detector for 5 seconds and retry.
The detector connected to the hub is displayed in the list of devices in the
app. The update of the detector status in the list depends on the device
inquiry time set in the hub settings (the default value is 36 seconds).
Connecting to Third-Party Security Systems
To connect the detector to a third-party security central unit using the
cartridge or Ajax Oxbridge Plus integration module, follow the recommendations
in the manual of the respective device.
The smoke detector always operates in active mode. When connecting FireProtect
to third-party security systems, it is appropriate to place it in a
permanently active protection zone.
States
- Devices
- FireProtect | FireProtect Plus
Parameter | State |
---|
Temperature
| Temperature of the device. Measures on the device processor and changes
gradually
Jeweller Signal Strength| Signal strength between the hub and the detector
|
Connection| Connection status between the hub and the device|
---|---|---
Battery level of the device. Two states available:
ОК
Battery discharged
How battery charge is displayed in Ajax apps
|
Battery Charge
|
Lid
| The tamper state of the device — reacts to the detachment|
ReX
| Displays the status of using the ReX range extender|
Smoke| Shows if smoke is detected|
Temperature Threshold Exceeded
| The state of temperature threshold exceeded alarm|
Rapid Temperature Rise| The state of rapid temperature increase alarm|
High CO Level (FireProtect Plus only)| The state of dangerous CO level alarm|
Backup Battery Charge| Backup battery level of the device|
Smoke sensor| The state of the smoke detector|
Smoke Sensor Dust Level| The dust level in the smoke chamber|
Temporary Deactivation
| Shows the status of the device: active, completely disabled by the user, or
only notifications about triggering of the device tamper button are disabled|
Firmware| Detector firmware version|
Device ID| Device identifier|
Settings
- Devices
- FireProtect | FireProtect Plus
- Settings
Setting | Value |
---|---|
First field | Device name, can be edited |
Room
| Selecting the virtual room to which the device is assigned
Dangerous CO Level Alarm (FireProtect Plus only)
| If active, the detector alerts of exceeding the limits of carbon monoxide concentration
High-Temperature Alarm
| If active, the detector reacts when the temperature is 60°C and higher
Rapid Temperature Rise Alarm
| If active, the detector reacts to rapid temperature increase (30°С for 30 minutes or less)
Alert with a siren if smoke is detected
| If active, sirens added to the system are activated in case of smoke alarm
Alert with a siren if the temperature threshold exceeded
| If active, sirens added to the system are activated in case if temperature threshold exceeded
Alert with a siren if rapid temperature rise detected
| If active, sirens added to the system are activated in case if rapid temperature rise detected
Alert with a siren if CO is detected (FireProtect Plus only)
| If active, sirens added to the system are activated in case if CO concentration is dangerous
Jeweller Signal Strength Test
| Switches the device to the signal strength test mode
FireProtect Self Test| Starts FireProtect selftest
Temporary Deactivation| Allows the user to disconnect the device without
removing it from the system.
Two options are available:
Entirely — the device will not execute system commands or participate in automation scenarios, and the system will ignore device alarms and other notifications
Lid only — the system will ignore only notifications about the triggering of the device
| tamper button
Learn more about temporary deactivation of devices
Note that a disabled device does not trigger an interconnected alarm of fire detectors. But if smoke is detected, the built-in siren will sound
---|---
User Guide| Opens the detector User Guide
Unpair Device| Deletes device and its settings
Interconnected FireProtect Alarms Setup
The function activates built-in sirens of all are detectors if at least one of them is triggered. Sirens are activated within the hub–detector ping interval according to the Jeweller settings.
To enable Interconnected Alarms:
-
Open the Devices tab in the Ajax app
-
Select a hub
-
Go to its Settings by pressing
-
Select the Service item
-
Go to the Fire detectors settings menu and activate the Interconnected FireProtect Alarms option
Interconnected alarms are supported by FireProtect and FireProtect Plus detectors with rmware versions 3.42 and later. Please note that when you turn on the interconnected alarms, you cannot set the hub–detector ping interval (Jeweller settings) of more than 48 seconds. -
If necessary, set the Delay of Interconnected Alarms from 0 to 5 minutes (in 1-minute increments). The option allows you to postpone the interconnected alarm for a specied period of time.
When this option is inactive, the interconnected alarm is sent to all are detectors within a minute.
The function works as follows:
-
One of the FireProtect/FireProtect Plus detectors detects an alarm.
-
Delay of Interconnected Alarms starts.
-
The built-in siren of the are detector informs the alarm. Users receive
notifications in the Ajax app (if appropriate notifications are enabled). At the object, Ajax sirens are activated (if the corresponding settings are enabled). -
An alarm confirmation event is sent to the monitoring station and security system users, and the system starts the interconnected alarm for are detectors if:
- The interconnected alarm delay time has passed, and the triggered detector is still registering an alarm.
- During the delay of the interconnected alarms, the triggered detector reports a different type of alarm (for example, the detector report the exceeding of the temperature threshold after a smoke alarm).
- During the interconnected alarm delay, another are detector in the system raised an alarm.
- To give more time to eliminate the cause of false triggering of the detector, the user can delay the propagation of the interconnected alarm for another 10 minutes:
- Through Ajax apps.
- By pressing the KeyPad/KeyPad Plus function button (in the interconnected are alarm muting mode).
- By pressing the Button in the interconnected are alarm muting mode.
- By eliminating the cause of the alarm (are detectors at the facility no longer detect an alarm).
- By pressing the touch button of the triggered are detector.
If a triggered detector does not return to a normal state within 10 minutes after the user postponed the interconnected alarm, another are detector reports an alarm or a triggered detector reports an alarm of another type (for example, temperature and smoke), the system will send an alarm confirmation and activate an interconnected alarm for re detectors.
If necessary, activate the Ignore First Alarm option. This setting is recommended for premises with potential sources of false alarms. For example, if the device is installed in a place where dust or steam can get into the detector.
The option functions as follows:
- The detector reports a smoke alarm.
- The built-in 30-second timer of the detector starts.
- If after 30 seconds the detector still detects a threat, an alarm is sent to the hub.
Setting the Residential re-alarm system
A residential re-alarm system is an Ajax system feature that denes user and
device rights to mute the interconnected alarms ofare-detectors.
If the feature is enabled, users can silence are alarms of triggered detectors
only in the groups to which they have access. And Button, KeyPad, KeyPad Plus
— the alarms only of those re detectors that are in the same group.
The feature is useful for objects consisting of several rooms and protected by
a single hub. For example, for multi-apartment complexes where each apartment
is a group with at least one re detector installed. In this case, users can
respond to the alarms of their groups without silencing the alarms of other
groups.
Indication
Event | Indication |
---|---|
Detector switching on | The logo lights up green for 1 second |
Detector switching off
| The logo blinks red three times and the device switches off
Registration failed
| The logo blinks green for a minute, then the device switches to the autonomous mode
Smoke or temperature increase detected
| The siren switches on, the logo lights red during the fire/smoke alarm
Battery low
|
One short sound signal per 90 sec — main batteries low (CR2)
Two short sound signals per 90 sec — backup battery low (CR2032)
Three short sound signals per 90 sec — both batteries low
Performance testing
The Ajax security system allows conducting tests for checking the
functionality of connected devices.
The tests do not start straight away but within a period of 36 seconds when
using the standard settings. The test time start depends on the settings of
the detector scanning period (the paragraph on “Jeweller” settings in hub
settings).
- Jeweller Signal Strength Test
- FireProtect Self Test
- Attenuation Test
According to the requirements of the EN50131 standard, the level of the radio signal sent by wireless devices is decreased during the test mode.
Detector Testing
Before installing the detector, check the smoke sensor. To test it, switch on
the detector and press the sensor button (the logo center) for a few seconds –
the detector will test the smoke chamber with the electronic simulation of
smoke generation and then will switch on the siren for 6 seconds.
You will receive a notification in the Ajax app regarding the test result and
detector status.
Installation
Selecting the Location
The location of the detector depends on its remoteness from the hub, and
obstacles hindering the radio signal transmission: walls, doors, large objects
inside the room.
If the signal level is low (one bar), we cannot guarantee the stable operation
of the detector. Take all possible measures to improve the quality of the
signal. At least, move the detector: even a 20 cm shift can significantly
improve the quality of signal reception. If the detector has low or unstable
signal strength even after moving, use a radio signal range extender. Install
the detector at the ceiling in the highest point where hot air and smoke are
concentrated in case of are.
If there are any beams at the ceiling, protruding by 30 or more centimeters
from the ceiling level, install the detector between every two beams.
- How to install FireProtect re detector correctly
- Where and how to install FireProtect Plus
Installation procedure
Before installing the detector, make sure that you have selected the optimal location that follows the guidelines of this manual!
-
Fix the SmartBracket panel on the ceiling using bundled screws. If you use any other attachment tools, make sure that they do not damage or deform the attachment panel.
Use double-side adhesive tape only for temporary attachment of the detector. The tape runs dry with time, which can cause falling, false triggering, and detector malfunction. -
Put the detector on the attachment panel by turning it clockwise on SmartBracket. When the detector is fxed in SmartBracket, it blinks with LED, signaling that the tamper is closed.
If LED doesn’t blink after fxing in SmartBracket, check the status of the
tamper in the Ajax app and then the fxing tightness of the panel.
If someone detaches the detector from the surface or takes it off the
attachment panel, the security system notifes you.
Do not install the detector:
- outside the premises (outdoors);
- nearby any metal objects or mirrors causing attenuation or screening of the signal;
- at any places with fast air circulation (air fans, open windows or doors);
- closer than a meter to the cooking surface;
- inside premises with the temperature and humidity beyond the range of permissible limits;
- closer than 1 m to the hub.
Autonomous Use of the Detector
The detector can be used autonomously, without connecting to a security
system.
- Switch on the detector by pressing the on/off button for 3 seconds (the logo will light up green for 1 second) and conduct the smoke test.
- Select the optimal location of the detector following the recommendations in the second part of the section Select the location of this manual.
- Install the detector as described in the section Installation procedure.
In case of autonomous use, the detector notified of the detected are/smoke with the siren sound and light of the logo. To switch off the siren, press the logo (there is a sensor button) or eliminate the cause of the actuated alarm.
Maintenance and Battery Replacement
Check the operational capability of the detector regularly. Clean the detector
body from dust, spider web, and other contaminants as they appear. Use soft
dry napkin suitable for tech equipment.
Do not use any substances containing alcohol, acetone, gasoline, and other
active solvents to clean the detector.
To a certain level, the detector ignores the dust in the smoke chamber. When
the chamber becomes too dusty, the detector notifies the user of the need to
clean it via the app (and beeps every minute and a half). Such maintenance is
compulsory for the detector to operate correctly.
How to clean up the smoke chamber
Pre-installed batteries ensure up to 4 years of autonomous operation. If the
batteries are discharged, the security system sends the respective
notifications and the detector signal with a sound every 90 seconds:
- if the main batteries are low — a single short signal;
- if the backup battery is low — two short signals;
- if both batteries are low — three short signals.
Keep new and used batteries away from children. Do not ingest battery, Chemical Burn Hazard.
Tech Specs
Smoke-sensitive element | Photoelectric sensor |
---|---|
Temperature sensitive element | Thermocouple |
Sound notification volume | 85 dB at a distance of 3 m |
Alarm threshold at the temperature | +59°С ±2°С |
Tamper protection | Yes |
Frequency band
| 868.0 – 868.6 MHz or 868.7 – 869.2 MHz
depending on the region of sale
Compatibility
| Operates independently or with all Ajax h ubs, range extenders, ocBridge Plus,
Maximum RF output power| Up to 20 mW
Radio signal modulation| GFSK
Radio signal range
| Up to 1,300 m (any obstacles absent)
Power supply
| 2 × CR2 (main batteries), CR2032 (backup battery), 3 V
Battery life| Up to 4 years
Installation method
| Indoors
Operating temperature range| From 0°С to +65°С
Operating humidity| Up to 80%
Complete Set
- FireProtect (FireProtect Plus)
- SmartBracket mounting panel
- Batteries CR2 (pre-installed) — 2 pcs
- Battery CR2032 (pre-installed) — 1 pcs
- Installation kit
- Quick Start Guide
Warranty
Warranty for the “AJAX SYSTEMS MANUFACTURING” LIMITED LIABILITY COMPANY
products is valid for 2 years after the purchase and does not apply to the
pre-installed battery.
If the device does not work correctly, you should arst contact the support
service —in half of the cases, technical issues can be solved remotely!
Technical support: csupport@ajax.systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>