MITSUBISHI ELECTRIC MXZ-5C42NA3 3.5 Ton Multi Zone Inverter Heat Pump System User Guide

June 4, 2024
Mitsubishi Electric

ELECTRIC MXZ-5C42NA3 3.5 Ton Multi-Zone Inverter Heat Pump System
**User Guide

**

MXZ-5C42NA3
3.5-TON MULTI-ZONE INVERTER HEAT-PUMP SYSTEM
Job Name: System Reference:
Date:

FEATURES

  • Variable speed INVERTER-driven compressor
  • Optional base pan heater
  • Quiet outdoor unit operation as low as 56 dB(A)
  • High-pressure protection
  • Compressor thermal protection
  • Compressor overcurrent detection
  • Fan motor overheating/voltage protection

SPECIFICATIONS: MXZ-5C42NA3

Cooling1 (Non-Ducted // Mix // Ducted)| Maximum Capacity| BTU/H| 43,000 // 43,000 // 43,000
---|---|---|---
Rated Capacity| BTU/H| 40,500 // 39,000 // 37,500
Minimum Capacity| BTU/H| 12,600 // 12,600 // 12,600
Maximum Power Input| W| 4,775 // 4,775 // 4,775
Rated Power Input| W| 4,403 // 4,286 // 4,112
Power Factor (208V, 230V)| %| 98.9, 98.9 // 98.9, 98.9 // 98.9, 98.9
Heating at 47°F2 (Non-Ducted // Mix // Ducted)| Maximum Capacity| BTU/H| 53,600 // 53,600 // 53,600
Rated Capacity| BTU/H| 45,000 // 43,000 // 41,000
Minimum Capacity| BTU/H| 11,400 // 11,400 // 11,400
Maximum Power Input| W| 6,160 // 6,160 // 6,160
Rated Power Input| W| 3,575 // 3,519 // 3,463
Power Factor (208V, 230V)| %| 98.1, 98.1 // 98.2, 98.2 // 98.2, 98.2
Heating at 17°F3 (Non-Ducted // Mix // Ducted)| Maximum Capacity| BTU/H| 30,500 // 29,800 // 29,100
Rated Capacity| BTU/H| 24,400 // 23,700 // 23,000
Maximum Power Input| W| 4,750 // 4,991 // 5,231
Rated Power Input| W| 2,943 // 2,906 // 2,869
Heating at 5°F4 (Non-Ducted // Mix // Ducted)| Maximum Capacity| BTU/H| 25,000 // 25,000 // 25,000
Maximum Power Input| W| 5,000 // 5,200 // 5,400
Efficiency (Non-Ducted // Mix // Ducted)| SEER| 19.7 // 17.4 // 15.2
EER1| 9.2 // 9.1 // 9.0
HSPF (IV)| 10.3 // 9.7 // 9.1
COP at 47°F2| 3.69 // 3.58 // 3.47
COP at 17°F at Maximum Capacity3| 1.88 // 1.75 // 1.63
COP at 5°F at Maximum Capacity4| 1.47 // 1.42 // 1.36
ENERGY STAR® Certified| No // No // No
Electrical| Electrical Power Requirements| Voltage, Phase, Frequency| 208/230, 1, 60
Guaranteed Voltage Range| V AC| 187-253
Voltage: Indoor – Outdoor, S1-S2| V AC| 208/230
Voltage: Indoor – Outdoor, S2-S3| V DC| 24
Short-circuit Current Rating (SCCR)| kA| 5
Recommended Fuse/Breaker Size| A| 40
Recommended Wire Size| AWG| 14
Minimum Circuit Ampacity| A| 32.5
Maximum Overcurrent Protection| A| 40
Fan Motor Full Load Amperage| A| 2.43
Outdoor unit| Airflow Rate (Cooling / Heating)| CFM| 2,150 / 2,550
Refrigerant Control| LEV
Defrost Method| Reverse Cycle
Heat Exchanger Type| Plate fin coil
Sound Pressure Level, Cooling1| dB(A)| 56
Sound Pressure Level, Heating2| dB(A)| 58
Compressor Type| DC INVERTER-driven Twin Rotary
Compressor Model| MNB33FBTMC-L
Compressor Rated Load Amps| A| 20
Compressor Locked Rotor Amps| A| 28.8
Compressor Oil Type // Charge| oz.| FV50S // 37.2
Base Pan Heater| Optional

Unit Dimensions

| W: In. [mm]| 37-13/32 [950]
D: In. [mm]| 13 [330]
H: In. [mm]| 41-17/64 [1,048]
Package Dimensions| W: In. [mm]| 41-3/8 [1,050]
D: In. [mm]| 17-3/8 [440]
H: In. [mm]| 46-3/4 [1,190]
Unit Weight| Lbs.[kg]| 189 [86]
Package Weight| Lbs.[kg]| 214 [97]

Outdoor unit operating temperature range

| Cooling Intake Air Temp (Maximum / Minimum*A)| °FDB| 115 / 14
Cooling Thermal Lock-out / Re-start Temperatures| °FDB| 10.4 / 14
Heating Intake Air Temp (Maximum / Minimum)| °FWB| 65 / 5
Heating Thermal Lock-out / Re-start Temperatures| °FDB| 1.4 / 5
Refrigerant| Charge| Lbs, oz| 8.0, 13.0
Chargeless Piping Length| Ft. [m]| 98.0 [30.0]
Additional Refrigerant Charge Per Additional Piping Length| oz./Ft. [g/m]| 0.216 [20]

NOTES:
AHRI Rated Conditions
(Rated data is determined at a fixed compressor speed)

1 Cooling (Indoor // Outdoor)…………°F 80 DB, 67 WB // 95 DB, 75 WB
2 Heating at 47°F (Indoor // Outdoor)………………°F 70 DB, 60 WB // 47 DB, 43 WB
3 Heating at 17°F (Indoor // Outdoor)…………..°F 70 DB, 60 WB // 17 DB, 15 WB
Conditions
4Heating at 5°F (Indoor // Outdoor)……….. °F 70 DB, 60 WB // 5 DB, 4 WB

Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions. A 5°F DB – 115°F DB when optional wind baffles are installed

For actual capacity performance based on indoor unit type and the number of indoor units connected, please refer to MXZ Operational Performance. Although the maximum connectable capacity is 130%, the outdoor unit cannot provide more than 100% of the rated capacity. Please utilize this over capacity capability for load shedding or applications where it is known that all connected units will NOT be operating at the same time.

SPECIFICATIONS: MXZ-5C42NA3

Indoor unit connection

| Maximum Number of Connected IDU| 5
---|---|---
Minimum Number of Connected IDU| 2
Minimum connected capacity| BTU/H| 12,000
Maximum connected capacity| BTU/H| 51,000

Piping

| Liquid Pipe Size O.D. (Flared)| In.[mm]| A,B,C,D,E: 1/4 [A,B,C,D,E: 6.35]
Gas Pipe Size O.D. (Flared)| In.[mm]| A: 1/2; B,C,D,E: 3/8 [A: 12.72; B,C,D,E: 9.52]
Total Piping Length| Ft. [m]| 262 [80]
Maximum Height Difference, ODU above IDU| Ft. [m]| 49 [15]
Maximum Height Difference, ODU below IDU| Ft. [m]| 49 [15]
Farthest Piping Length from ODU to IDU| Ft. [m]| 82 [25]
Maximum Number of Bends for IDU| 80

NOTES:
AHRI Rated Conditions
(Rated data is determined at a fixed compressor speed)
1Cooling (Indoor // Outdoor)…………………..°F 80 DB, 67 WB // 95 DB, 75 WB
2Heating at 47°F (Indoor // Outdoor)……………………..°F 70 DB, 60 WB // 47 DB, 43 WB
3Heating at 17°F (Indoor // Outdoor)……..°F 70 DB, 60 WB // 17 DB, 15 WB
Conditions
4Heating at 5°F (Indoor // Outdoor)………….. °F 70 DB, 60 WB // 5 DB, 4 WB
Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions. A 5°F DB – 115°F DB when optional wind baffles are installed
For actual capacity performance based on indoor unit type and a number of indoor units connected, please refer to MXZ Operational Performance. Although the maximum connectable capacity is 130%, the outdoor unit cannot provide more than 100% of the rated capacity. Please utilize this over capacity capability for load shedding or applications where it is known that all connected units will NOT be operating at the same time.

OUTDOOR UNIT ACCESSORIES: MXZ-5C42NA3

Air Outlet Guide Air Outlet Guide (1 Piece) □ PAC-SH96SG-E
Ball Valve Refrigeration Ball Valve – 1/2” □ BV12FFSI2
Refrigeration Ball Valve – 1/4” □ BV14FFSI2
Refrigeration Ball Valve – 3/8” □ BV38FFSI2
Refrigeration Ball Valve – 5/8” □ BV58FFSI2
Control Wire M-Net Control Wire, 1,000’ Roll (16-AWG, Standard, Twisted Pair,
Shielded, Jacketed- Plenum-rated) □CW162S-1000

M-Net Control Wire, 250’ Roll (16-AWG, Standard, Twisted Pair, Shielded, Jacketed- Plenum-rated)| □CW162S-250
Drain Socket| Drain Socket| □ PAC-SG60DS-E
Hail Guards| Hail Guard| □ HG-A1
M-NET Converter| M-NET Converter| □ PAC-IF01MNT-E
Mini-Split Wire| 14 Gauge, 4 wire MiniSplit Cable—250 ft. roll| □ S144-250
14 Gauge, 4 wire MiniSplit Cable—250 ft. roll| □ SW144-250
14 Gauge, 4 wire MiniSplit Cable—50 ft. roll| □ S144-50
14 Gauge, 4 wire MiniSplit Cable—50 ft. roll| □ SW144-50
16 Gauge, 4 wire MiniSplit Cable—250 ft. roll| □ S164-250
16 Gauge, 4 wire MiniSplit Cable—250 ft. roll| □ SW164-250
16 Gauge, 4 wire MiniSplit Cable—50 ft. roll| □ S164-50
16 Gauge, 4 wire MiniSplit Cable—50 ft. roll| □ SW164-50
Mounting Pad| Condensing Unit Mounting Pad: 16” x 36” x 3”| □ ULTRILITE1
Outdoor Unit 3-1/4 inch Mounting Base (Pair) – Plastic| □ DSD-400P
Optional Defrost Heater| Optional Defrost Heater| □ PAC-645BH-E
Port Adapter| Adaptor: 1/2” x 3/8”| □ MAC-A455JP-E
Adaptor: 1/2” x 5/8”| □ MAC-A456JP-E
Adaptor: 3/8” x 1/2”| □ MAC-A454JP-E
Adaptor: 3/8” x 5/8”| □ PAC-SG76RJ-E
Stand| 18” Single Fan Stand| □ QSMS1801M
24” Single Fan Stand| □ QSMS2401M
Condenser Wall Bracket| □ QSWB2000M-1
Condenser Wall Bracket – Stainless Steel Finish| □ QSWBSS
Outdoor Unit Stand — 12” High| □ QSMS1201M

OUTDOOR UNIT DIMENSIONS: MXZ-5C42NA3
Unit: inch (mm)

FORM# MXZ-5C42NA3 – 202206
Specifications are subject to change without notice.
1340 Satellite Boulevard Suwanee, GA 30024
Toll-Free: 800-433-4822
www.mehvac.com
© 2022 Mitsubishi Electric Trane HVAC US LLC.
All rights reserved.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Mitsubishi Electric User Manuals

Related Manuals