komfovent C6M Controller Instructions

June 4, 2024
komfovent

komfovent C6M Controller product

komfovent C6M Controller product

UPDATE INSTRUCTIONS

C6/C6M controller firmware can be updated when connected computer to the AHU. This can be done by connecting computer directly as well via local computer network or internet.

To update firmware on C6/C6M controller perform following steps:

  1. Stop AHU by pressing TURN OFF button on the control panel.komfovent C6M Controller fig 1
  2. On the control panel find the IP address of the ventilation unit.komfovent C6M Controller fig 2
  3. Connect AHU to computer or to local computer network1.
  4. On the computer start Internet browser application and enter IP addess that was found in the control panel.
  5. Connect to the C6/C6M user interface: enter user name user , password user2 and press Login button. komfovent C6M Controller fig 3
  6. Press SETTINGS1 button.komfovent C6M Controller fig 21

SETTINGS

USER INTERFACE

DATE/TIME

CONNECTIVITY

INFORMATIONkomfovent C6M Controller fig 7 LOGIN PASSWORD

CONTROL MODE

CONTROL SEQUENCE

AIR QUALITY

FILTERS

CLOUD

  • In the INFORMATION section check current firmware versions of the controller and control panel (firmware version is the last number; for example 1.3.17.20 means that version number is 20).
  • If current control panel version is X.X.X.10 or latter, control panel firmware will be updated together with C6/C6M con-troller firmware. If control panel version is older – only C6/C6M controller can be updated.
  • Download update file from KOMFOVENT website, using following links:
    • Update file for units with main module firmware version X.X.X.15 or later
    •  Intermediate update file for units with main module firmware version X.X.X.14 or earlier
  • In the internet browser application window enter IP address of the AHU and add /g1.html.komfovent C6M Controller fig 14
  • If prompted enter user name and password again (see step 5).
  • When screen loads click Browse1 button and specify location of the update file on your computer:
    • If control main module firmware version is X.X.X.15 or later, chose *.mbin file
    • If control main module firmware version is X.X.X.14 or earlier, chose *.bin file  komfovent C6M Controller fig 15
  • When update file is selected, press Upload button.komfovent C6M Controller fig 16
  • In the Status line „uploading“ will be displayed.komfovent C6M Controller fig 17
  •  After 30–60 seconds the Status line will change to:
    • Firmware uploaded successfully, device is restarting. Panel firmware upload success: wait until finished”, if at the same time control panel firmware was updatedkomfovent C6M Controller fig 18
    • Firmware uploaded successfully, device is restarting.”, if only C6/C6M controller was updated:komfovent C6M Controller fig 19
    • “Firmware upload error”, if update was not successful (see step 21).
  • Wait for 1–2 minutes, until controller will update the firmware and restart.
    • If control panel firmware was updated, on the panel screen “Upda ting” will be displayed together with the status bar.
    • Wait for 1–2 minutes, until control panel firmware will be updated and main screen will return.
  • If C6/C6M controller firmware version before the update was X.X.X.10 or earlier, after update IP address of the unit was restored to default 192.168.0.60. If needed it can be changed using control panel (see step 2).
  • If C6/C6M controller firmware version before the update was X.X.X.14 or earlier, repeat steps 10-16, but use *.mbin update file instead.
  • Check new firmware version number in the internet browser (see steps 4-7) and if OK you can use the ventilation unit normally.
  • If control panel firmware version is X.X.X.9 or earlier, new functions introduced with C6/C6M controller update will be available only in the web interface and will not be shown on the control panel display, however, the control panel will work normally as before the update. In case if new function access from the control panel is needed – control panel should be replaced with a new one.
  • If the firmware update has failed, please perform the following steps and try to update again:
    • Make sure the correct update file was used (see steps 9 and 12)
    • Turn OFF the main power for the AHU, wait for 1 minute and turn the power ON
    • Restart the computer that is used for updated
    • Use different internet browser
    • Connect the computer directly to the AHU (not through a network or internet)
      If still firmware update is not successful please contact Komfovent service department.

LITHUANIA
UAB KOMFOVENT
TECHNINĖS PRIEŽIŪROS SKYRIUS / SERVICE AND SUPPORT
Phone: +370 5 200 8000
Email: service@komfovent.com
www.komfovent.com

PARTNERS

AT| J. PICHLER Gesellschaft m. b. H.| www.pichlerluft.at
---|---|---

BE

| Ventilair group| www.ventilairgroup.com
ACB Airconditioning| www.acbairco.be
CZ| REKUVENT s.r.o.| www.rekuvent.cz

CH

| WESCO AG| www.wesco.ch
SUDCLIMATAIR SA| www.sudclimatair.ch
CLIMAIR GmbH| www.climair.ch
DK| Øland A/S| www.oeland.dk
EE| BVT Partners| www.bvtpartners.ee
FR| ATIB| www.atib.fr
HR| Microclima| www.microclima.hr

HU

| AIRVENT Légtechnikai Zrt.| www.airvent.hu
Gevent Magyarország Kft.| www.gevent.hu
Merkapt| www.merkapt.hu
IR| Fantech Ventilation Ltd| www.fantech.ie

IS

| Blikk & Tækniþjónustan ehf| www.bogt.is
Hitataekni ehf| www.hitataekni.is
IT| Icaria srl| www.icariavmc.it

NL

| Ventilair group| www.ventilairgroup.com
DECIPOL-Vortvent| www.vortvent.nl
CLIMA DIRECT BV| www.climadirect.com

NO

| Ventilution AS| www.ventilution.no
Ventistål AS| www.ventistal.no
Thermo Control AS| www.thermocontrol.no
PL| Ventia Sp. z o.o.| www.ventia.pl
SE| Nordisk Ventilator AB| www.nordiskventilator.se
SI| Agregat d.o.o| www.agregat.si
SK| TZB produkt, s.r.o.| www.tzbprodukt.sk

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals