TONE| TONE TYPE| TONE DESCRIPTION/ APPLICATION| DIP
SWITCH| dBA @ 1m| mA
---|---|---|---|---|---
1.|
| 970Hz| O – O – O – O – O| 99| 21
2.| | 800Hz/970Hz @ 2Hz| O – O – O – O – I| 100| 20
3.| | 800Hz – 970Hz @ 1Hz| O – O – O – I – O| 100| 20
4.| **| 970Hz 1s OFF/1s ON| O – O – O – I – I| 99| 14
5.|
| 970Hz, 0.5s/ 630Hz, 0.5s| O – O – I – O – O| 99| 19
6.| **| 554Hz, 0.1s/ 440Hz, 0.4s (AFNOR NF S 32 001 )| O – O – I – O – I|
97| 13
7.| | 500 – 1200Hz, 3.5s/ 0.5s OFF (NEN 2575:2000 Dutch Slow Whoop)| O –
O – I – I – O| 99| 16
8.| | 420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone)| O – O –
I – I – I| 96| 9
9.| | 1000-2500Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF ( AS1670 Evacuation)| O –
I – O – O – O| 104| 14
10.| | 550Hz/440Hz @ 0.5Hz| O – I – O – O – I| 97| 14
11.| | 970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 )| O – I – O – I
– O| 98| 12
12.| | 2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201)| O – I – O – I –
I| 94| 21
13.| | | | | | | 1200Hz – 500Hz @ 1Hz (DIN 33 404)| O – I – I – O –
O| 99| 17
14.| | 400Hz| O – I – I – O – I| 95| 13
15.| **| 550Hz, 0.7s/1000Hz, 0.33s| O – I – I – I – O| 98| 17
16.|
| 1500Hz – 2700Hz @ 3Hz| O – I – I – I – I| 104| 34
17.| **| 750Hz| I – O – O – O – O| 99| 18
18.| | 2400Hz| I – O – O – O – I| 106| 45
19.| | 660Hz| I – O – O – I – O| 96| 17
20.| | 660Hz 1.8s ON/1.8s OFF| I – O – O – I – I| 96| 12
21.| | 660Hz 0.15s ON/0.15s OFF| I – O – I – O – O| 96| 11
22.| | 510Hz, 0.25s/ 610Hz, 0.25s| I – O – I – O – I| 98| 15
23.| | 800/1000Hz 0.5s each (1Hz)| I – O – I – I – O| 100| 21
24.| | 250Hz – 1200Hz @ 12Hz| I – O – I – I – I| 98| 13
25.| | 500Hz – 1200Hz @ 0.33Hz| I – I – O – O – O| 99| 17
26.| | 2400Hz – 2900Hz @ 9Hz| I – I – O – O – I| 101| 40
27.| | 2400Hz – 2900Hz @ 3Hz| I – I – O – I – O| 104| 40
28.| | 500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF ( AS1670 Evacuation)| I
– I – O – I – I| 98| 10
29.| | 800Hz – 970Hz @ 9Hz| I – I – I – O – O| 99| 20
30.| | 800Hz – 970Hz @ 3Hz| I – I – I – O – I| 100| 20
31.| | 800Hz, 0.25s ON/1s OFF| I – I – I – I – O| 99| 8
32.| ****| 500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220)| I – I – I – I – I| 99|
17
EN54-3:2001+A1+A2
Technical Data Document 18-186215
Fire Alarm Device – Sounder
Type A: For indoor use (Shallow Base)
Type B: For outdoor use (Deep Base)
PSS-0068/73/79/80 & PSC-0055: 0832-CPD-0297
PSC-0045/54/62/63/51 : 0832-CPD-0546
Installation Manual
Installation
If required, the mechanism for locking the sounder to the base can be
activated by removing the thin section of plastic shown in Fig. 1 with side
cutters or a similar tool. To open a locked head,remove the small rubber bung
from the hole on the side of the sounder, insert a tool into the hole and
depress the clip whilst twisting the head. The O-ring and bung must be re-
fitted to maintain the weatherproofing.
Wiring
Line | Terminal Marking |
---|---|
Common Positive Supply IN | (3) IN+ |
Sounder Negative Supply | (2) – or COM – |
Beacon Negative Supply | (1) |
The sounder and beacon 0V terminals can be linked together for simultaneous control of sound and light using a 2-core connection.
(Common-Operation models are supplied with terminals 1 & 2 already linked by a
permanent internal connection.)
A separate earth terminal is provided on the deep base for connecting the
screen or functional earth. On the shallow base, terminal 5 can be used for
this purpose.
Tone Selection and Volume Control
a) The tone is selected using the 5 way dipswitch on the bottom of the sounder
head. Refer to the table overleaf for details of the available tones and the
switch settings required to select them.
b) The sound output of the unit can be reduced by adjusting the potentiometer
on the bottom of the sounder.
Technical Specification
- Supply Voltage Range 17 – 60V DC
- Current Sounder: 4 – 45mA*
- Beacon: 5mA
- Peak Sound Level 94 – 106 dBA at 1m*
- Number of Tones 32
- Frequency Range 400 – 2850 Hz*
- Operating Temperature -25°C to + 70°C
- Casing High Impact Polycarbonate
- IP Rating IP21
- IP65 (with deep base)
- Synchronisation Automatic
depends on selected tone and input voltage. See tone table for details.
EN54-3 certified on tones 1,2,3,4,5,6,7 & 13
The European directive “Waste Electrical and Electronic Equipment” (WEEE) aims to minimise the impact of electrical and electronic equipment waste on the environment and human health. To conform with this directive, electrical equipment marked with this symbol must not be disposed of in European public disposal systems. European users of electrical equipment must now return end- of-life equipment for disposal. Further information can be found on the following website: http://www.recyclethis.info/.