Evikon PluraSens E2418DP Low Differential Pressure Transmitter User Manual

June 4, 2024
Evikon

Evikon PluraSens E2418DP Low Differential Pressure Transmitter

Specifications

Version E2418DP-1K E2418DP-10K
Detection range options -1…+1 kPa -10…+10 kPa
Resolution 1 Pa (0,01 mbar) 10 Pa (0,1 mbar)
Max. overpressure 10 kPa 80 kPa
Accuracy ±20 Pa ±200 Pa
Zero point drift <5 Pa/year <50 Pa/year
Temperature effect Compensated within -5…+65 °C range
Analog outputs 2 × 4-20 mA or 0-10 V, user settable



Standard output scales

| E2418DP-1K| E2418DP-10K
0-250 Pa,

0-500 Pa,

0-1,0 kPa

-250 – +250 Pa

-500 – +500 Pa

-1,0 – +1,0 kPa

| 0-2,5 kPa,

0-5 kPa,

0-10 kPa

-2,5 – +2,5 kPa

-5 – +5 kPa

-10 – +10 kPa

Digital interface| RS485, Modbus RTU protocol


Load resistance

| RL < (Us – 3 V) / 22 mA for 4-20 mA

RL > 100 kOhm for 0-10 V mode


Operating conditions

| -20…+70 °C, <99 %RH non+condensing, Without dust, aggressive gases, mist or oil; Residential or business spaces
Power supply options| 12…36 VDC (default), 24 VAC as option
Power consumption| < 1 W
Electromagnetic compatibility| According to 2014/30/EU: EN 61000-6-3:2020, EN 61326-1:2013(EMC, emissions) EN 61000-6-1:2019, EN 61000-6-2:2019(EMC, Immunity)
Enclosure| Grey ABS 82 × 80 × 55 mm, IP65

Product description

  • Differential pressure transmitter E2418DP is a member of the new PluraSens® family of multifunctional measurement instruments. The transmitter is intended for measurement of differential pressure of clean air or nonflammable gases.
  • The main HVAC applications for the transmitter are monitoring of fans, filters, valves, dampers, measurement of airflow in ventilation ducts and pressure in cleanrooms. E2418 is based on a fully calibrated, linearised and temperature compensated digital differential pressure sensor with high repeatability, stability and long lifetime.
  • The instrument provides two independent analog outputs OUT1 and OUT2, user selectable to 4-20 mA or 0-10 V, proportional either to differential pressure or internal temperature. RS485 Modbus RTU digital communication interface allows easy configuration of the transmitter and its integration into various automation systems through the Fieldbus network. If the symbol is marked on the equipment, consult the documentation for further information.

Safety requirements

  • Misuse will impair the protection of the product. Always adhere to the safety provisions applicable in the country of use.
  • Do not perform any maintenance operation with the power on. Do not let water or foreign objects inside the device.
  • Removal of the PCB from the enclosure voids the warranty. Do not touch the electronic components directly, as they are sensitive to static electricity.
  • Connection diagrams can be found in the installation and connections section. The device might not perform correctly or be damaged if the wrong power supply is connected.
  • External circuits connected to the equipment should have sufficient insulation rating according to the environmental conditions and equipment power.
  • A disconnecting device that is marked as such and easily accessible should be included in the installation of this product.

Operating conditions

The device should be used in explosion-safe (indoor areas, without aggressive gases in the atmosphere. Allowed conditions are:

  • temperature in the range of -20…+70 °C
  • relative humidity in the range of 0…99% without condensation
  • atmospheric pressure in the range of 84…106,7 kPa.

Installation and connections

Before proceeding with the installation it is mandatory to read carefully the Safety requirements section and make sure to comply with all listed instructions.
The pressure transmitter should be mounted on a wall.

Evikon PluraSens E2418DP Low Differential Pressure Transmitter-
fig2

To install the device, proceed as follows:

  1. Unscrew four lid screws and detach the lid from the transmitter.
  2. Attach the device to a wall with screws passing through mounting holes (for dimensions see the antecedent drawing). This step may be done after step 3, consider your convenience.
  3. Use M16 cable gland to let in cables of the power supply and of the external devices. Attach the power cable to the device without turning it on. Using the connection diagram below, connect the analog outputs and digital interface terminals to the relevant devices according to your tasks.

Evikon PluraSens E2418DP Low Differential Pressure Transmitter-
fig3

Jumpers

J1| OUT1 type (open: 4-20 mA; closed 0-10 V)
J2| OUT2 type (open: 4-20 mA; closed 0-10 V)
X6| Reset Modbus network parameters to default
X4 terminals
OUT1| 4-20 mA / 0-10 V output
OUT2| 4-20 mA / 0-10 V output
0V| 0 V / 24 VAC Neutral (optional)
A| RS485 A / Data +
B| RS485 B / Data –
+U| +24 VDC / 24 VAC Phase (optional)

The screwless quick connect spring terminals on the E2407 are suitable for a wide range of wires with cross-section 0,2…1,5 mm2. The recommended wire stripping length is 8…9 mm. Push the spring loaded terminal lever, insert the wire end into the terminal hole and release the lever.
Use twisted pair cable, e.g. LiYY TP 2×2×0,5 mm2 or CAT 5, to connect the device to the RS485 network. Use one pair for A and B wires and the second pair for common 0V and power +U wires. to connect the transmitter to the Fieldbus network.polarity must be respected when connecting to an external RS485 network.
Overall length of all connections via the RS485 interface should not exceed 1200 m.
Both analog outputs can be independently changed between 4-20 mA and 0-10 V type using jumpers J1 (OUT1) and J2 (OUT2). By closing pins on a specific jumper the related output is 0-10 V, with an open jumper the output is 4-20 mA. Power restart is required after changing the position of the jumpers.
NOTE! Power restart is required after changing the position of the jumpers.

  1. Turn on the power. The operating status is indicated by the LED on the PCB of the device. The LED response to different processes is presented in the following table:
    Mode| LED mode
    ---|---
    During calibration mode or sensor heating period (if activated)|

0.5 Hz (50% on, 50% off)

During the Modbus communication cycle| Short on-off pulses
Normal operating/measurement| Continuously on or off

  1. Make sure that the transmitter is properly mounted, the external devices connected, power on and control LED is constantly lit. Place the lid back and fix it with the screws. To connect the device with measurement point use tubes of appropriate diameter (4 or 6 mm) and length.
    NOTE! The connecting tubes should not be squeezed or folded.

Delivery set

  • Differential pressure transmitter E2418DP
  • Set of mounting accessories (4 screws with plastic dowels)

Order code for E2418DP options

E2418DP options Order code
Differential pressure transmitter-regulator, -1…1 kPa, resolution 0,5 Pa

E2418DP-1K

Differential pressure transmitter-regulator, -2…2 kPa, resolution 1 Pa| ****

E2418DP-2K

Differential pressure transmitter-regulator, -5…5 kPa, resolution 2,5 Pa|


E2418DP-5K

Differential pressure transmitter-regulator, -10…10 kPa, resolution 5 Pa|


E2418DP-10K

Differential pressure transmitter-regulator, -25…25 kPa, resolution 12,5 Pa|


E2418DP-25K

Integrated 90…265 V mains power supply module| E2418DP-230

Configuring

Differential pressure transmitter-regulator E2418DP shares all functionalities of the PluraSens® multifunctional transmitter platform. The features and options include:

  • digital output change rate limiting filter
  • digital integrating (averaging) filter
  • flexible setting of analog output scales for each output
  • E2418 can be configured through its RS485 interface by Modbus RTU commands. A standard configuration kit includes a USB-RS485 converter and a software pack.
  • Please contact your Seller for more information.

Return to default settings

To reset the device’s Slave ID, baud rate and stop bit number to factory settings, proceed as follows:

  1. De-energize the device
  2. Connect the X6 jumper
  3. Turn on the device
  4. De-energize the device
  5. Disconnect the X6 jumper
  6. Turn on the device

Emergency mode

The current outputs of the detector may be programmed via Modbus commands (register 255) to signal if the connection with the sensor is lost. The signal may be set to 3,8 mA (low current) or 21,5 mA (high current).

Bites Functions Notes Default
bit[0]=0/1 sensor present/absent Read-only
bit[1]=0/1 analog outputs activated/deactivated   1
bit[2]=0/1 in case of sensor absence, turn signalling off/on (OUT 1)   1
bit[3]=0/1 In case of sensor absence turn on signalling with low/high current
on OUT 1 if bit [2]=0, this bit is ignored 0
bit[4]=0/1 in case of sensor absence, turn signalling off/on (OUT 2)   1

bit[5]=0/1

| In case of sensor absence turn on signalling with low/high current on OUT 2|

if bit [4]=0, this bit is ignored

|

0

bit[6]=0/1| Current/voltage output detected on OUT 1| Read-only| User defined
bit[7]=0/1| Current/voltage output detected on OUT 2| Read-only| User defined
bit[8]=0/1| LED deactivated/activated|  | 1

Modbus RTU Communication

Modbus main holding registers (00xxx or 40xxx): 0-based, decimal

Reg RW Description Supported values
1 R hardware version 0…65535
2 R software version
3 R product serial number 0…65535
4 RW* Slave ID [1…247] 0…247
5 RW* baud rate 1200, 2400, 4800, 9600, 19200, 38400,

57600

6| RW| Response delay, ms| 1…255 ms
7| RW| Stop bits| 1, 2, 3, 4
8| R| Last error code| 1…255
17| RW
| Technological: data age in seconds (read) / restart(write)| 0…65535 s (read), 42330(write)
167| RW| Change rate limit for pressure data, pressure units| 1…32000 pressure units,0=no limit
168| RW
| Integrating filter time constant for pressure data, s| 1…32000 s, 0=no filter


201

| ****

RW**

| ****

Parameter assigned to OUT1

| 0=none, 1=temperature, 2=pressure, 9=forced Modbus control, value set in 203


202

| ****

RW**

| ****

Parameter assigned to OUT2

| 0=none, 1=temperature, 2=pressure, 9=forced Modbus control, value set in 204
203| RW| Forced value for OUT1| 0…1000 (0.0%… 100.0% of scale)
204| RW
| Forced value for OUT2| 0…1000 (0.0%… 100.0% of scale)
255| RW**| Sensor control/status| see Emergency mode paragraph
257| R| Raw pressure data| -32000…+32000 pressure units


258

| ****

R

| ****

Measured temperature, °Cx100

| signed integer, -4000…+12500

(-40,00…+125,00 °C)

259| R| Measured pressure| -32000…+32000 pressure units
261| RW| 0% value of analog OUT1| -32000…+32000 pressure units
262| RW
| 100% value of analog OUT1| -32000…+32000 pressure units
263| RW| 0% value of analog OUT2| -32000…+32000 pressure units
---|---|---|---
264| RW
| 100% value of analog OUT2| -32000…+32000 pressure units

  • the new value is applied after restart.
  • the new value is applied immediately.
  • writing 42330 restarts the device immediately, no response on Modbus. Broadcast ID=0 may be used to assign a new ID to a device with unknown ID.

RS485 Communication parameters

Parameter Permitted values Default
Supported baud rates 1200, 2400, 4800, 9600, 19200, 38400, 57600 9600
Data bits 8 8
Parity none / odd / even none
Stop bits 1, 2 1
Protocol Modbus RTU
Modbus functions 03 – Read multiple registers 06 – Write a single register


Error codes

| 01 – Illegal function

02 – Illegal data address 03 – Illegal data value 04 – Slave device failure

(details of last error 04 can be read from register 0x0008)

Factory settings

Pressure unit depending on the range
OUT1 parameter and scale 2: pressure, scale set by user
OUT2 parameter and scale 2: pressure, scale set by user

Warranty

This product is warranted to be free from defects in material and workmanship for a period of one year from the date of the original sale. During this warranty period, the Manufacturer will, at its option, either repair or replace a product that proves to be defective. This warranty is void if the product has been operated in conditions outside ranges specified by the Manufacturer or damaged by customer error or negligence or if there has been an unauthorized modification.

Manufacturer contacts

Evikon MCI OÜ Teaduspargi 7/9, Tartu 50411 Estonia info@evikon.eu www.evikon.eu

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals