Multifunction instrument for electrical installation safety testing, power quality analysis and EVSE safety testing
COMBI521 carries out tests on electric systems in compliance with IEC/EN 61557-1 and therefore measurements of continuity of the protection cable, insulation resistance (with calculation of PI and DAR), overall earth resistance, RCDs type B, A and AC tripping time and current, line / fault impedance with calculation of prospective short circuit / fault current, phase sequence and conformity. COMBI521 also allows measuring and saving environmental parameters (illuminance, temperature), leakage current and electric quantities such as voltage, current, power factor, power and harmonics on single-phase systems. In combination with EV-TEST100, COMBI521 performs verification and control of electric car charging stations (EVSE) in accordance with IEC / EN 61851-1 and IEC / EN60364-7-722 standards. COMBI521 is provided with the innovative AUTO function: by selecting this function and only setting the value of RCD current, COMBI521 carries out tests of overall earth resistance, RCD tripping time and insulation resistance in a sequence. At the end of the test, the device shows all results with the indication of compliance or non-compliance with the standards with simple OK or NOT OK symbols.The internal memory allows saving the measures and subsequently transfer them onto the PC through the optical/USB connection. Thanks to the brand new HTAnalysis App, free to download for iOS and Android systems, COMBI521 is capable of transferring measured and recorded data

onto tablets and smartphones, thus giving the operator the possibility to customize and share through HtCloud the result of their tests.

Measurement function:

  • All electrical safety measurements as required by the international safety standards
  • AUTOMATIC test (no-trip ground resistance, RCD tripping time, insulation resistance) in a sequence
  • Continuity of protective conductors with 200mA
  • Insulation resistance up to 1000V, with dielectric absorption ratio D.A.R. and polarization index P.I.
  • Polarity test
  • Type A, AC, B General and Selective RCD tripping time and current
  • Line/Fault impedance, Phase-Phase, Phase-Neutral, Phase-PE (also at high resolution with optional accessory IMP57)
  • Coordination of MCBs and fuses
  • Global earth resistance
  • Phase sequence and conformity measurement
  • Measurement of leakage current
  • Measurement of electrical parameters in single-phase installations (V, A, W, VAR, VA, PF)
  • Measurement of environmental parameters through external probes (HT52/05 and HT53/05)
  • Internal memory and PC connection
  • Wi-Fi connection to Android and iOS smartphones and tablets

TECHNICAL SPECIFICATION

3M COMBI521 Multifunction Tester-fig2 3M
COMBI521 Multifunction Tester-fig3 3M
COMBI521 Multifunction Tester-fig4 3M
COMBI521 Multifunction Tester-fig5 3M
COMBI521 Multifunction Tester-fig6 3M
COMBI521 Multifunction Tester-fig7 3M
COMBI521 Multifunction Tester-fig8 3M
COMBI521 Multifunction Tester-fig9 3M
COMBI521 Multifunction Tester-fig10 3M
COMBI521 Multifunction Tester-fig11

Hamonics are zeroed in the followed conditions:

  • DC: if the DC value <0.5% fundamental value or if the DC value < 5mV
  • 1 harmonic: if the value of 1°harmonic <5mV (not displayed)
  • 2nd 25th harmonics: if harmonic value <0.5% fundamental value or if the value <5mV

GENERAL SPECIFICATIONS

3M COMBI521 Multifunction Tester-fig12 3M
COMBI521 Multifunction Tester-fig13

This instrument satisfies the requirements of Low Voltage Directive 2014/35/EU (LVD) and of EMC

Directive 2014/35/EU
This instrument satisfies the requirements of European Directive 2011/65/EU (RoHS) and 2012/19/EU (WEEE

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals