camfil CamCube AS HEPA Filter Housing Instruction Manual

June 3, 2024
camfil

camfil CamCube AS HEPA Filter Housing

CAMCUBE AS
Ducted HEPA filter housing with an innovative integrated scanning system to perform integrity tests. The filter housing is reversible depending on the airflow direction.
The filter housing and the scanning system is designed so that the scanning covers the entire downstream face of each filter, the perimeter of each filter, the seal between the filter frame and the grid structure, including its joints.

DESCRIPTION

  1. INSPECTION LENSES
  2. CRANK TO MOVE THE SCANNING PROBE
  3. BATTERY BOX WITH LIGHT SWITCH
  4. DOWNSTREAM SCANNING PORT/S
  5. UPSTREAM AEROSOL SAMPLING PORT
  6. PRESSURE DROP MEASUREMENT PORTS
  7. SCANNING PROBE
  8. LIGHT
  9. FILTER CLAMPING SYSTEM
  10. FLANGE CONNECTION
  11. UPSTREAM MEASURING POINT

HANDLING INSTRUCTION

When the housing is moved or transported the service door must be closed and the scanning mechanism and crank must be protected. When needed the housing can be wiped with water or a mild detergent.

INSTALLATION OF THE FILTER HOUSING
For information about the flange connections, see the drawings. The equipment needed for installing the housing is not provided by Camfil. Be aware of the airflow direction when installing the housing. A minimum 1-meter free space in front of the service door is needed for a filter change. The housing is provided with measurement ports for pressure drop.

NOTE: Designed for indoor use

VISUAL INSPECTION

For visual inspection of the scanning system, the housing is equipped with wide-angle inspection lenses and LED strip lights. The led strip has a lifetime of 20 000 hours and protection class IP44. The on/off switch is placed on the battery cover. To change the battery (9 V Lithium block), the cover is removed by loosening the two socket screws with a hex key (3 mm). The used battery shall be recycled at a local collection facility.

SCANNING

Upstream aerosol concentration is sampled through the upstream sample port, hydraulic coupling ID 4,3. Follow the recommendations in ISO 14644-3 when it comes to the concentration of upstream aerosol challenge and its verification.

Connect the particle counter to the scanning port, hydraulic coupling ID 4,3. The scanning process is executed one filter at a time. To obtain the optimal probe velocity of 10 mm/s the crank should be turned at 12 rpm, roughly 5 seconds per turn. Turn the crank until you feel a slight resistance. Use the inspection lenses to verify that the probe is either in the top or bottom position.

WARNING:
Turning the crank beyond the end position or the use of excessive force can damage the probe mechanism. If damaged, the entire probe mechanism will need to be replaced.

Closest to the service door you find the port for pressure drop tests. Aerosol sampling port in brass.

When equipped with two filters the housing has double sampling ports. The schematic drawing indicates which port is connected to which scanning probe.

Crank to move the scanning probe. Turning the crank beyond the end position or the use of excessive force can damage the probe mechanism. If damaged, the entire probe mechanism will need to be replaced.

FILTER INSTALLATION & FILTER CHANGE

Camfil recommends filters with handles for simplified filter installations and filter change.

Filter installation
Shut down the ventilation system and open the service door. Handle the filter very carefully. It is essential you do not touch the filter media. The media is extremely sensitive and the slightest touch of the media can lead to leakage. Place the new filter carefully into the clamping device. Be careful not to damage the filter gasket. The gasket should be placed on the outlet side. Use a hex key (5 mm) to tighten the screw until the gasket is compressed about 30 % or a maximum 2,5 Nm. Close the service door and restart the ventilation system.

HEPA-filter change
Camfil recommends protective equipment like overalls, gloves and face masks when changing filters. Always check local regulations before changing filters. Shut down the ventilation system and open the service door. Untighten the filter clamping device with a hex key (5 mm) and remove the used filter. See the instructions for installing the new filter above. The used filter must be taken care of and be handled according to local regulations.

Example of filter with handle (Absolute DG)

The tightening screw for the clamping device tightens a maximum of two parallel filters.

Pressure-relieving hinges;
Designed to avoid shearing damage to the service door gasket.

www.camfil.com.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

camfil User Manuals

Related Manuals