camfil CAMGT 4V-300 General Ventilation Filters Instructions
- June 3, 2024
- camfil
Table of Contents
ADVANTAGES
-
Resistant to turbulence and extreme pressure drop
-
Patented Aerodynamic support grid for lower pressure drop
-
Optimized media area for the lowest pressure drop at EPA efficiency
-
Hydrophobic filter construction and media
-
Low operational pressure drop, even when wet, with patented built-in
drainage -
Sealed on all sides and featuring our patented double sealing process
Application| All installations where safety/reliability is important.
All installations with high humidity/heavy rain
---|---
Frame| Plastic molded
Gasket| Polyurethane, endless foamed
Media| Glass fiber
Separator| Hot-melt
Sealant| Polyurethane
Grille, Downstream| Support grid for filtermedia
Rec. final pressure drop| 600 Pa
Max airflow| 1.3 x nominal flow
Max Temperature (°C)| 70°C
Relative Humidity max| 100%
Comment| Fire rating: Available according to DIN4102 class b2 rating on
request Burst strength: > 6250 Pa continuous wet/soaked Reverse flow version:
With support metal grid available on request Additional information: Also
available in 1/2 and 3/4 size on request.
Cam GT 4V-300 is a high efficiency air inlet filter used for second and/or third stage filtration, depending on the gas turbine air inlet system. Typical range from M6 or MERV 11 up to E12 (EPA level), for the best gas turbine protection. Also available in versions with Fire rating DIN4102 class b2, Reverse flow, half size and 3/4 size on request.
Type| EN779| EN1822| ISO16890| Dimensions WxHxD (mm)| Airflow/pressure drop
(m³/h/Pa)| Area (m²)| Weight (kg)| ePM1| ePM1min| ePM2,5| ePM2,5min| ePM10|
ASHRAE 52.2-2017
---|---|---|---|---|---|---|---|---|---|---|---|---|---
4V-300-T7-Std| F7| | ePM1 70%| 592x592x300| 4250/130| 19| 8| 72| 72| 80| 80|
93| MERV 13
4V-300-T7-XL| F7| | ePM1 70%| 592x592x300| 4250/125| 26| 8.5| 72| 72| 80| 80|
93| MERV 13
4V-300-T8| F8| | ePM1 80%| 592x592x300| 4250/140| 19| 8| 80| 80| 87| 87| 96|
MERV 14
4V-300-T8-XL| F8| | ePM1 80%| 592x592x300| 4250/135| 26| 8.5| 80| 80| 87| 87|
96| MERV 14
4V-300-T9| F9| | ePM1 85%| 592x592x300| 4250/165| 19| 8| 85| 84| 89| 89| 96|
MERV 15
4V-300-T9-XL| F9| | ePM1 85%| 592x592x300| 4250/160| 26| 8.5| 85| 84| 89| 89|
96| MERV 15
4V-300-T10| | E10| | 592x592x300| 4250/200| 29| 8.5| 97| 97| 98| 97| 98|
4V-300-T11| | E11| | 592x592x300| 4250/225| 29| 8.5| | | | | |
4V-300-T12| | E12| | 592x592x300| 4250/260| 30| 9.0| | | | | |
4V-300-T12-CamBrane| | E12| | 592x592x300| | | | | | | | |
ME%: Minimum efficiency ref. to EN779:2012
As part of our program for continuous improvement, Cam fil reserves the right to change specifications without notice. 2021-12-09