RAB X34 Floodlight Instruction Manual

June 3, 2024
RAB

RAB X34 Floodlight

RAB-X34-Floodlight-product

RAB Lighting is committed to creating high-quality, affordable, well-designed, and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com.RAB-X34
-Floodlight-fig-1

IMPORTANT

READ CAREFULLY BEFORE INSTALLING THE FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE. Fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.

WARNING:
Make certain power is OFF before installing or maintaining the fixture. No user-serviceable parts inside.

NOTE: No user maintenance or cleaning is required.

SLIPFITTER MOUNTING

  1. The slip fitter mounting fits a 2 3/8” O.D. Tenon. Place the slip fitter over the Tenon and secure the fixture with the two Set Screws on the side of the slipfitter.
  2. Loosen the Locking Bolt and swivel the fixture to the desired angle.
  3. Tighten the Locking Bolt.RAB-X34-Floodlight-fig-2

TRUNNION MOUNTING

CAUTION:
UL and C-UL listed or CSA-certified liquid-tight cord grip suitable for use with three-conductor-type STW flexible cord shall be used for connection to a wet location outlet box provided by others.

To adjust the angle of the fixture using the trunnion:

  1. Loosen the Pivot Bolts & angle locking screw.
  2. Adjust the fixture to the desired angle.
  3. Tighten Pivot Bolts & angle locking screw.

0-10V DIMMABLE WIRING

Universal voltage driver permits operation at 120V thru 277V, 50 or 60 Hz. For 0-10 Dimming, follow the wiring directions as shown in Fig. 3.

  1. Connect the black fixture lead to the LINE supply lead.
  2. Connect the white fixture lead to the COMMON supply lead.
  3. Connect the GROUND wire from the fixture to the supply ground. Do NOT connect the GROUND of the dimming fixture to the output.
  4. Connect the purple fixture lead to the DIM V+ lead.
  5. Connect the pink (or gray) fixture lead to the DIM V- lead.
  6. Cap the yellow fixture lead, if present. Do NOT connect.RAB-X34-Floodlight-fig-4

CLEANING & MAINTENANCE

CAUTION: Be sure the fixture temperature is cool enough to touch. Do not clean or maintain while the fixture is energized.

  1. Clean the glass lens with a non-abrasive glass cleaning solution.
  2. Do not open the fixture to clean the LED. Do not touch the LED.

DIMENSIONAL DRAWINGS

RAB-X34-Floodlight-fig-5RAB-X34-Floodlight-
fig-6

Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.

rablighting.com. Visit our website for product infoTech Help Line Call our experts: 888 722-1000. e-mail Answered promptly – sales@rablighting.com.

RAB WARRANTY

RAB’s warranty is subject to all terms and conditions found at rablighting.com/warranty. © 2021 RAB LIGHTING Inc.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals