REGENCY CV50E Direct Vent Gas Fireplace Instruction Manual

June 1, 2024
Regency

CV50E Direct Vent Gas Fireplace

“`html

Specifications:

  • Model: City Series CV50E Direct Vent Gas
    Fireplace

  • Fuel Type: Natural Gas (CV50E-NG) / Propane
    (CV50E-LP)

  • Minimum Supply Pressure: 5 W.C. (1.25
    kPa)

  • Manifold Pressure – High: 11 W.C. (2.73
    kPa)

  • Manifold Pressure – Low: 10.5 W.C. (2.62
    kPa)

  • Orifice Size: # 36 DMS for Altitude 0-4500 ft
    (19,000 Btu/h) / # 52 DMS for Altitude 0-4500 ft (17,000
    Btu/h)

  • Vent Sizing: 5 Inner / 8 Outer

  • Efficiency: 57.49% / 60.55%

Product Usage Instructions:

Gas Connection:

The gas connection can be made at the bottom or side of the
unit. Follow the provided dimensions for accurate placement.

Electrical Connection:

The electrical connection can also be made at the bottom or side
of the unit. Ensure proper clearance and follow the specified
measurements.

Clearances:

Adhere to the minimum clearance distances to prevent
chimney-related fires. Follow the guidelines for mantel height,
sidewall distance, enclosure width, alcove dimensions, framing
depth, and ceiling clearance.

FAQ:

Q: Can this fireplace be used with both natural gas and

propane?

A: Yes, the City Series CV50E Direct Vent Gas Fireplace is
compatible with both natural gas and propane fuel types.

Q: What is the efficiency rating of this fireplace?

A: The efficiency of the fireplace is 57.49% for natural gas and
60.55% for propane.

Q: What are the minimum supply pressure requirements?

A: The minimum supply pressure required is 5 W.C. (1.25
kPa).

“`

City Series CV50E Direct Vent Gas Fireplace

MODEL

CV50E-NG

CV50E-LP

Fuel Type

Natural Gas

Propane

Minimum Supply Pressure
Manifold Pressure – High
Manifold Pressure – Low
Orifice Size -Altitude 0-4500 ft Minimum Input Altitude 0-4500 ft. (0-1372m) Maximum Input Altitude 0-4500 ft. (0-1372m) Vent Sizing
CSA P.4.1.

5″ W.C. (1.25 kPa)
3.8″ W.C. (0.94 kPa) 1.1″ W.C. (0.27 kPa)

36 DMS 19,000 Btu/h

(5.56 kW) 35,000 Btu/h (10.25 kW) 5″ Inner / 8″ Outer
57.49%

11″ W.C. (2.73 kPa)
10.5″ W.C. (2.62 kPa) 2.9″ W.C. (0.72 kPa)

52 DMS 17,000 Btu/h

(4.98 kW) 33,000 Btu/h
(9.66 kW) 5″ Inner / 8″ Outer
60.55%

NOTE: This model comes with a 5″ inner and 8″ outer collar (127 mm x 203 mm) which must be reduced to 4″ inner x 6-5/8″ outer (102 mm x 168 mm) in all applications when used as a power vent system. See power vent manual for details.

DimensioDInMEsNSIONS

231mm

PAGE 7

45

7 8

1165mm

8″ 203mm

5″ 127mm

8

1 2

216mm

1 8

9

301mm

7 8

11

49

3 16

1249mm

54

3 8

1382mm

20

15 16

532mm

20-7/16”

(519 mm)

340mm

3 8

13

37″ 940mm

18″ 457mm

258mm

3 16

10

Note: Height Dimension is taken with leveling legs fully inserted and may vary depending on the height of the leveling legs, when unscrewed or extended. Dimensions will appear as (inches)” / (metric) mm throughout this manual. The inches are rounded to the nearest 1/16″ when converted, when greater accuracy is required, use the metric dimensions. Note: These units are non-load bearing.
ALL PICTURES / DIAGRAMS SHOWN THROUGHOUT THIS MANUAL ARE FOR ILLUSTRATION PURPOSES ONLY. ACTUAL PRODUCT MAY VARY DUE TO PRODUCT ENHANCEMENTS.
City Series CV50E Direct Vent Gas Fireplace | 1

Gas Connection – Bottom of Unit
OPEN BOTTOM

221mm

11 16

8

261mm

1 4

10

Gas Connection – Side of Unit

1

15 16

50mm

49

1 16

1246mm

FRONT OF UNIT

1

11 16

42mm

BACK OF UNIT

38mm

1 2

30mm

3 16

30mm

3 16

38mm

1 2

1

1

1

1

16

1 8

409mm

3

3 4

95mm

9 16

15mm

LEFT SIDE 2 | City Series CV50E Direct Vent Gas Fireplace

9 16

15mm

3

3 4

95mm

16

1 8

409mm

RIGHT SIDE

Electrical Connection – Bottom of Unit

OPEN BOTTOM

221mm

11 16

8

261mm

1 4

10

1

15 16

Electrical Connection – Side of Unit

50mm

49

1 16

1246mm

FRONT OF UNIT

1

11 16

42mm

BACK OF UNIT

38mm

1 2

30mm

3 16

1

1

5

3 4

145mm

2

3 8

60mm

12

3 8

314mm

RIGHT SIDE

City Series CV50E Direct Vent Gas Fireplace | 3

Clearances

Note: The clearances listed below are minimum distances unless otherwise stated.
A major cause of chimney-related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

Clearance A1: Mantel Height (min.)

Dimension **

A: From Floor (min.)

10-3/16″ (462 mm)

B: Sidewall (on one side) min.

5″ (127 mm)

B1: Sidewall (on one side) min.

24″ (610 mm)

C: Enclosure Width (min.)

54-3/8″ (1381 mm)

D: Mantel Depth (max.)

**

E: Alcove Width

92″ (2337 mm)

F: Alcove Depth

35″ (889 mm)

G: Convection Air Outlet Opening Offset (min.)
H: Convection Air Outlet
I: Framing Depth (min.)

0-2″ (0-51 mm)
152 in2 (981 cm2) 20-7/16″ (519 mm)

J: Opening Height

18″ (457 mm)

K: minimum clearance to ceiling

1-3/4″ (44 mm)

L: Chase Enclosure (min.)

62-7/8″ (1597 mm)

M:Clearance to Sprinkler Head (min.)

36″ (914mm)

Ceiling Height

81-1/4″ (2064 mm)

Hearth

0″

** See mantel clearances chart in the manual.

Measured From: Top of Fireplace Opening Bottom of fireplace opening Side of fireplace opening Side air outlet to side wall (min.) Side of fireplace opening
Sidewall to sidewall (minimum) Front to unit (maximum) Max. offset from top of chase enclosure
From back wall to chase front Bottom/top of fireplace opening Top of chase to ceiling From base of unit/floor to top of enclosure Perpendicular from chase grill From base of unit/floor to top of alcove No hearth required

Flue Clearances to Combustibles

Horizontal – Top

3″ (76 mm)

Horizontal – Side

2″ (51 mm)

Horizontal – Bottom

2″ (51 mm)

Vertical

2″ (51 mm)

Passing through wall/ floor/ceiling – when firestop is used.

1-1/2″ (38 mm)

Note: This appliance uses 5″ x 8″ (127 mm x 203 mm) venting for the Non Power Vent.

When installed as a power vent, the venting must be reduced to 4″ inner x 6-5/8″ outer (102 mm x 168 mm) in all applications. See required reducers required in this manual if using rigid/flex pipe.

*inAcmheinsmimoinfuimomupmoefno1f5a12r8es0aqs,uqnauaorerte
loofwelneorcwlteohrsatuhnaren0,0-r2-e2″q” ffurroiormmedtotfpooporf all installations.

G H
D

L A1 B J

Caution Requirements The top, back and sides of the fireplace are
defined by standoffs. The metal ends of the standoff may NOT be recessed into
combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not adhered to. It is of greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

A

LM
Chase grill

Sprinkler

F E
Alcove
4 | City Series CV50E Direct Vent Gas Fireplace

Side view

Clearances

Floor to ceiling with top opening.

Full framing with vents in front, 2 sides, or top.

Full framing with low vents in front or 2 sides.

Full framing with vents in front or 2 sides.

The ventilation opening may only be placed above, on both sides and in front as shown above. Ventilation grills can never be placed behind the appliance.

City Series CV50E Direct Vent Gas Fireplace | 5

Mantel Clearances
Combustible mantel clearances from top of front facing are shown in the diagram below. 14 12 10 8 6 4 2
26

20

1/2″ (13 mm) Drywall, wood, wood panel, etc.

10 12″ (305mm)

0
To Bottom of Fireplace Opening

9″ (229mm)
5-1/4″ (133mm)
Top of Fireplace Opening

18″ (457mm)

Mantel Leg Clearances
Combustible mantel leg clearances as per diagram:

MANTEL LEG

49-3/16″ (1249 mm)

MANTEL LEG

12″ (305 mm) 9″ (229 mm)
7 ” (178 mm)
5″ (127mm)

12″ (305 mm)
9″ (229 mm) 7″
(178 mm)
5″ (127mm)

10″ (254 mm)
Allowable mantel leg projection
6 | City Series CV50E Direct Vent Gas Fireplace

10″ (254 mm)
Allowable mantel leg projection

Framing Dimensions

NOTE: Framing may be constructed of combustible material (i.e. 2 x 4/2 x 6) and does not require steel studs.

Framing Dimensions

Description

A

Framing Height

B*

Framing Width

C*

Framing Depth

D

Minimum Height to Combustibles

E

Corner Wall Depth

F

Corner Facing Wall Depth

G

Vent Centerline Height

** See manual for alternate Gas/ Electrical connection options

CV50E
2 x 4 : 44-3/4″ (1137 mm) 2 x 6 : 51-7/8″ (1318 mm)
54-3/8″ (1381 mm) 20-7/16″ (519 mm) 62-7/8″ (1597 mm)
66″ (1676 mm) 93-3/8″ (2372 mm) 45-3/4″ (1162 mm)

The lift handles add approximately 4 inches to the width of the appliance. If the appliance will be lifted off the ground and slid into the framed opening, we suggest changing the framing width from 54-3/8″ (1381 mm) to 58-3/8″ (1483 mm) to allow the appliance to slide into position with the handles on,
or creating a platform in front of the framed opening where the lift handles can be removed prior to installation. If the framing is raised off the ground you can install it after the appliance is in place with handles removed to maintain the framing width of 54-3/8″ (1381 mm). Ensure that the wood base for the
appliance is strong enough to support its shipping weight of 480 pounds.

Note: A combined minimum of 152 square inches of open area is required for the convection air outlet to cool the enclosure. Ensure clearances for convection air outlets are met. See clearances in this manual for different ways to achieve this.

minimum of open the concool the ances Outlets
in this different this can

Note: This appliance must be
installed on a solid surface
such as a plywood floor which must be the full width and
depth of the appliance.

ust be surface
floor width appliance.

  • The framing depth/width does not take into account drywall/wood or similar materials against the back /side wall. The framing depth will need to change based on the thickness of the material. Example: B – 54-3/8″ framing width +1/2″ drywall per side = 55-3/8″) Example: C – 20-7/16″ framing depth +1/2″ drywall = 20-15/16″)
    City Series CV50E Direct Vent Gas Fireplace | 7

Chase Vent Installation Part #482-991 (White)
In this application, both the flange and screws to secure the chase vent are exposed as this chase vent is designed to be installed after the finished facing has been placed on the wall.
Framing Opening must be between 3” (76 mm) and 3-1/2” (89 mm) tall, and at least 51-1/2” (1308 mm) wide to accomodate the Chase vent. The top of the chase vent opening must be 2” (51 mm) or less from the top of the chase enclosure.

Opening for vent 3″-3-1/2″
(76 mm – 89 mm)

Min 51-1/2″ (1308 mm)

Max 2″ (51 mm)

Ceiling Stud
51-1/2″ (1308 mm) Chase Vent Stud

8 | City Series CV50E Direct Vent Gas Fireplace

Max 2″ (51 mm)

Stud

Ceiling Top of chase enclosure

51-1/2″ (1308 mm) Chase Vent
Stud

Typical Installations Flush Install

Recessed Install

2″ 51mm MAX. TO TOP OF ENCLOSURE

152 sq.in MIN. CHASE VENT OPENING
2X4 OR 2X6 STUD

152 sq.in MIN. CHASE VENT OPENING

MIN.

881mm

11 16

MIN.

881mm

11 16

34

34

2 X 6 STUD

594mm

3 8

23

2 X 4 STUD

419mm

1 2

16

MIN.

1597mm

62

Screws must not penetrate unit more than 1/2″. Adhere to “No Screw” zones painted on unit Glue can be used as an alternative

28

3 16

716mm

5

1 4

133mm

MAX. DEPTH

MANTLE

See Mantel clearance in manual

MAX DEPTH 36″ (914 MM) HEARTH

1597mm

7 8

7 8

62

City Series CV50E Direct Vent Gas Fireplace | 9

Typical Installations Maximum TV Recess

Flush TV with Hearth

MAX. 2″
51mm TO TOP OF ENCLOSURE
MAX. 2″
51mm TO TOP OF ENCLOSURE

152 sq.in MIN. CHASE VENT OPENING
MAX. 2X6 STUD

152 sq.in MIN. CHASE VENT OPENING
MAX. 2X4 STUD

34 11/16″ [881 mm] MIN.

62 7/8″ [1597 mm] MIN.

62 7/8″ [1597 mm] MIN.

594mm

3 8

MIN.

419mm

23

1 2

16

Screws must not penetrate unit more than 1/2″. Adhere to “No Screw” zones painted on unit. Glue can be used as an alternative

Screws must not penetrate unit more than 1/2″. Adhere to “No Screw” zones painted on unit. Glue can be used as an alternative

Note: The TV mounting bracket cannot be secured directly to the appliance. It must be secured to framing. The TV depicted in the picture may need to be higher depending on the style of TV mounting bracket used.

10 | City Series CV50E Direct Vent Gas Fireplace

Horizontal Terminations – Flex Vent 5″ x 8″ (Non Power Vent)
These venting systems, in combination with the CB50E Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by Intertek. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in “Exterior Vent Termination Locations” section.
Regency® Direct Vent (Flex) System Termination Kits include all the parts needed to install the CB50E using a flexible vent.

FPI Kit # #946-615

946-618

946-616

Length 4 Feet 6 Feet
10 Feet

Contains:

  1. 8″ flexible liner (Kit length) 2) 5″ flexible liner (Kit length) 3) spring spacers 4) thimble 5) AstroCap XL termination cap 6) screws 7) tube of Mill Pac 8) plated screws 9) S.S. screws #8 x 1-1/2″ drill point 10) vinyl siding standoff

Notes:
1. Liner sections should be continuous without any joints or seams.
2. Only Flex pipe purchased from Regency® may be used for Flex installations
3. Horizontal vent must be supported every 3 feet.
4. Regency® Direct Vent System (Flex) is only approved for horizontal terminations.
5. Flex system can only be used up to a maximum continuous vent length of up to 10 feet. If longer runs are required, rigid pipe must be used.

5″ (127 mm) 8″ (203 mm)

Vent Guard – if required* (Part #946-604/P)

City Series CV50E Direct Vent Gas Fireplace | 11

Horizontal Terminations – Flex Vent 5″ x 8″ (Non Power Vent)

Unit Installation with
Horizontal Termination – 5″ x 8″ Venting (Flex Vent Systems)

NOTE: Horizontal sections must be supported at intervals not exceeding 3 feet (0.9 meter). (Flame picture and performance will be affected by sags in the liner).

Minimum Vent Clearances to Combustibles

  • Clearances noted below must be maintained; except when passing through a wall, ceiling or at the termination where the use of a firestop or wall thimble reduces clearance to 1-1/2″ (38mm).

4. Separate the 2 halves of the wall thimble and securely fasten the one with the tabs to the outside wall making sure that the tabs are on top and bottom. Fasten the other thimble half to the inside wall. The thimble halves slip inside each other and can be adjusted for 2 x 4 or 2 x 6 walls.

Horizontal Top Horizontal Side Horizontal Bottom Vertical Vent

3″ (76mm) 2 ” (51mm) 2″ (51mm) 2″ (51mm)

5. Slip the assembled liner and termination assembly through the thimble making sure the termination cap faces up (there are markings on the cap that show which way is up). This will position the termination cap with proper down slope for draining water. Fasten the cap to the outer wall with the 4 supplied screws.

Below are the recommended framing dimensions
(inside measurements) for the 5″ x 8″ rigid vent
terminations – for use with a firestop or wall thimble.

Recommended Framed Opening Size

Vent Size

Framing Size

5″ x 8″

11″ x 11″

1. Locate the unit in the framing, rough in the gas (preferably on the right side of the unit). Locate the centerline of the termination and mark wall accordingly. Cut an square hole in the wall – see chart (inside dimension).
Note: If installing termination on a siding covered wall, a vinyl siding standoff or vinyl furring strips must be used to ensure that the termination is not recessed into the siding.

Outside Wall

6. Pull the centre inner and outer flex liner out enough to slip over the flue collars of the fireplace. (You may wish to cut the liner shorter to make it more workable.) Do not bend liner more than 90º. The liners must slip over the collars a minimum of 1-3/8″.
7. Apply Mill-Pac over the fireplace inner flue collar and slip the inner flex liner down over it and attach with 3 supplied screws.
8. Do the same with the outer flue collar and outer flex liner.
9. Apply a bead of silicone between the thimble and termination and around the outer edge of the terminal at the wall in order to keep the water out.
IMPORTANT: Do not locate termination hood where excessive snow or ice buildup may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.

ASTROCAP XL DIMENSIONS (946-623/P)
12-1/4 ” (311 mm) 12-1/4 ” (311 mm)
Diagram 1 center of hole
Diagram 3

Min. 45-3/4” (1162 mm)

Furring Strips
2. Level the fireplace and fasten it to the framing using nails or screws through the nailing strips.

5″ dia. flue pipe with spring spacer

2″ x 4″ or 2″ x 6″
AstroCap XL Termination Cap

3. Assemble the vent assembly by applying Mill-Pac
to the inner flue collar of the termination and slipping the inner flex liner over it at least 1-3/8″ (35mm). Fasten with the 3 screws (drilling pilot
holes will make this easier). Apply Mill-Pac to
the outer flex pipe and slip it over the outer flue collar of the vent terminal at least 1-3/8″(35mm)
and fasten with the 3 screws.

8″ dia. air intake

Screws Vinyl Siding

Screws

Wall Thimble

12 | City Series CV50E Direct Vent Gas Fireplace Diagram 2

NOTE

NOTES

Venting Introduction (Non Power Vent)
The CV50E uses the “balanced flue” technology co-axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber, thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney. The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it’s own separate vent system. Common vent systems are prohibited.
These flue pipes must not be connected to any other appliance.
Venting Arrangement for Horizontal Terminations (Rigid and Flex)
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o elbow (two 45o elbows equal one 90o elbow). · Must use optional rigid pipe adapter (part# 770-994) when using rigid pipe venting systems. · For horizontal terminations, the Regency direct vent flex system may be used for installations with a maximum continuous vent length of up to 10 feet. If longer runs are required, rigid pipe must be used.
Vent Restrictor Set 3: 2-3/8″ Open
Vent Restrictor Set 2: 3-1/8″ Open
Set 0 Fully Open Factory Set
45-3/4″ (1162 mm) Minimum Height Requirement
VENT RESTRICTOR SETTING: Vent restrictor factory set at Set 0. Refer to the “Vent Restrictor Position” section for details on how to change the vent restrictor from the factory setting of Set 0 to Set 3 if required. · Maintain clearances to combustibles as listed in “Clearances” section · Horizontal vent must be supported every 3 feet. · Firestops are required at each floor level and whenever passing through a wall. · A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
City Series CV50E Direct Vent Gas Fireplace | 13

Horizontal Terminations – Rigid Pipe 5″ x 8″ (Non Power Vent)
The minimum components required for a basic horizontal termination are:

1 Horizontal Termination Cap 1 Rigid Pipe Adaptor (770-994) 1 Wall Thimble 1 Length of pipe to suit wall thickness
(see chart)

Wall thickness is measured from the back standoffs to the inside mounting surface of termination cap. For siding other than vinyl
furring strips may be used, instead of the vinyl siding standoff, to create a level surface to mount the vent terminal. The Terminal
must not be recessed into siding. Measure the wall thickness
including furring strips.

If a Vinyl Siding Standoff is required (it must be used with vinyl siding), measure to outside surface of wall without siding and
add 2 inches.

Flat Wall Installation

Wall Thickness (inches)

Vent Length Required (inches)

4″ – 5-1/2″

6″

7″ – 8-1/2″

9″

10″ – 11-1/2″

12″

9″ – 14-1/2′

11″ – 14-5/8″ Adj. Pipe

15″ – 23-1/2″

17″ – 24″ Adj. Pipe

Horizontal Termination Cap Vinyl Siding Standoff (Optional)
Wall Thimble Adj.Pipe Length 90o Elbow
Pipe Length Rigid Pipe Adapter

WARNING:
Do not combine venting components from different venting systems.
However use of the the AstroCapTM and FPI Riser is acceptable with all systems.
This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with Duravent Direct-Vent, Selkirk Direct-Temp, Ameri Vent Direct Venting, ICC Excel Direct, Olympia Ventis DV, and Security Secure Vent systems. Use of these systems with the Rigid Pipe adaptor is deemed acceptable and does not affect the Intertek WHI listing of components.

*Unit is not exactly as shown.

When using Rigid Vent other than Simpson Dura-Vent, 3 screws must be used to secure rigid pipe to adaptor.
The FPI AstroCapTM and FPI Riser Vent terminal are certified for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent, American Metal Products Ameri Vent Direct Vent, Security Secure Vent®, ICC Excel, Olympia Ventis DV, Selkirk Direct-Temp. AstroCapTM is a proprietary trademark of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.

14 | City Series CV50E Direct Vent Gas Fireplace

Unit Installation with
Horizontal Termination (Non Power Vent) 5″ x 8″ Venting (Rigid Vent Systems) Minimum Vent Clearances to
Combustibles

3 feet (0.9meter). Wall straps are available for this purpose.
6. Mark the wall for a square hole.-see chart to left for size. The center of the square hole should line up with the center-line of the horizontal pipe. Cut and frame the square hole in the exterior wall where the vent will be terminated. See diagram 54 for center line requirements.

  • Clearances noted below must be maintained;
    except when passing through a wall, ceiling or
    at the termination where the use of a firestop or wall thimble reduces clearance to 1-1/2″ (38mm).

If the wall being penetrated is constructed of non-combustible material, i.e. masonry block or concrete, an 8″ (203mm) diameter hole is acceptable.

Horizontal Top*

3″ (76mm)*

Horizontal Side

2 ” (51mm)

Horizontal Bottom 2″ (51mm)

Vertical Vent

2″ (51mm)

Below are the recommended framing dimensions (inside measurements) for the 5″ x 8″ rigid vent terminations – for use with a firestop or wall thimble.

Install the vent system according to the manufacturer’s instructions included with the components.

1. Set the unit in its desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the unit. Rough in the gas preferably on the right side of the unit and the electrical (junction block is on the left side) on the left.
2. Direct Vent pipe and fittings are designed with special twist-lock connections to connect the
venting system to the appliance flue outlet. A twist-lock appliance adaptor is required. 3. In conjunction with the Approved Vent system, install the adaptor after the unit is set in its desired location. Slip the adapter over the
existing inner and outer flue collar. Fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier).
4. Level the fireplace and fasten it to the framing using nails or screws through the top and side nailing strips.

Notes: a) The horizontal run of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fire. b) The location of the horizontal vent termination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. See “Exterior Vent Termination Locations” section for more details.
center of hole
Diagram 3 c) Snorkel Terminations:
For installations requiring a vertical rise on the exterior of the building, 14-inch and 36-inch tall Snorkel Terminations are available, as well as the standard Riser Vent. Follow the same installation procedures as used for standard Horizontal Termination. NEVER install the snorkel upside down.

Min. 45-3/4” (1162 mm)

Diagram 2
5. Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection.

Below Grade Snorkel Installation If the snorkel termination must be installed below grade, i.e. basement application, proper drainage must be provided to prevent water from entering the snorkel termination. See diagram 56. Do not attempt to enclose the snorkel within the wall or any other type of enclosure.
Diagram 5 7. Ensure that the pipe clearances to combustible
materials are maintained (Diagram 55). Install the termination cap. Note: If installing termination on a vinyl siding
covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding. The four wood screws provided should be
replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings. 8. Before connecting the horizontal run of vent pipe to the vent termination, slide the Wall Thimble over the vent pipe. The wall thimble is required for all horizontal terminations. 9. Slide the appliance and vent assembly towards the wall carefully inserting the vent pipe into the vent cap assembly. It is important that the vent pipe extends into the vent cap sufficient distance so as to result in a minimum pipe overlap of 1-1/4 inches (32mm). Secure the connection between the vent pipe and the vent cap.

Note: For best results and optimum performance with each approved venting

10. Install wall thimble in the center of the framed hole and attach with wood screws.

system, it is highly recommended to

apply “Mill-Pac” sealant (supplied) to

every inner pipe connection. Failure to do so may result in drafting or

Diagram 4

performance issues not covered under *As specified in CSA B149.1 Installation Code.

warranty.

Local codes or regulations may require different

Horizontal runs of vent must be supported every clearances.

City Series CV50E Direct Vent Gas Fireplace | 15

Horizontal Terminations – Rigid/Flex Pipe 5″ x 8″ (Non Power Vent)
The diagrams below show examples of horizontal termination arrangements using one, two, or three 90o elbows (two 45o elbows equal one 90o elbow).
1. A maximum of three 90o elbows are permitted.
2. Minimum distance between elbows is 1 ft. (305mm).
· Maintain clearances to combustibles as listed in the “Clearances” section. · Horizontal vent must be supported every 3 feet. · Firestops are required at each floor level and whenever passing through a wall. · Must use optional rigid pipe adaptor (Part# 770-994) when using rigid pipe vent systems. · A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes. · Flex system can only be used up to 10 feet – otherwise rigid venting must be used.

Horizontal Venting with Two 90o Elbows

One 90o elbow = Two 45o elbows.

Option

V

H + H1

A) 1′ Min. 2′ Max.

B) 2′ Min. 4′ Max.

C) 3′ Min. 5′ Max.

D) 4′ Min. 6′ Max.

E) 5′ Min. 7′ Max.

F)

6′ Min. 8′ Max.

Restrictor Set 0 – Factory Setting

With these options, maximum total pipe length is 30 feet with minimum of 6 feet total vertical and maximum 8 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.

H1

H

V

Horizontal Venting with Three 90o Elbows

One 90o elbow = Two 45o elbows.

Option

V

H

V + V1

A) 1′ Min. 1′ Max. 2′ Min.

B) 1′ Min. 2′ Max. 3′ Min.

C) 2′ Min. 2′ Max. 5′ Min.

D) 3′ Min. 2′ Max. 7′ Min.

E) 4′ Min. 3 Max. 9′ Min.

F) 5′ Min. 4′ Max. 10′ Min.

G) 6′ Min. 5′ Max. 11′ Min.

H) 7′ Min. 6′ Max. 12′ Min.

Restrictor Set 0 – Factory Setting

H + H1 2′ Max. 3′ Max. 4′ Max. 5′ Max. 6′ Max. 7′ Max. 8′ Max. 9′ Max.

With these options, max. total pipe length is 30 feet with min. of 12 feet total vertical and max. 9 feet total horizontal.
Please note min. 1 foot between 90o elbows is required.

H1 V1

H V

16 | City Series CV50E Direct Vent Gas Fireplace

Vertical Terminations – Rigid Pipe 5″ x 8″ (Non Power Vent)

The minimum components required for a basic vertical termination are:

1 Vertical Termination Cap 1 Rigid Pipe Adaptor (770-994) 1 Ceiling Firestop 1 Flashing 1 Storm Collar 1 Length of pipes to suit wall thickness & vent run
(see chart)

Vertical Terminal
Storm Collar Flashing

Galvanized pipe is desirable above the roofline due to its higher corrosion resistance. Continue to add pipe sections through the flashing until the height of the vent cap meets the minimum height requirements specified in table below or local codes. Note that for steep roof pitches, the
vertical height must be increased. A poor draft, or down drafting
can result from high wind conditions near big trees or adjoining
roof lines, in these cases, increasing the vent height may solve the
problem.

Ceiling Firestop Pipe Length

Roof Pitch

Minimum Vent Height

Feet

flat to 7/12

2

over 7/12 to 8/12 2

over 8/12 to 9/12 2

over 9/12 to 10/12 2.5

over 10/12 to 11/12 3.25

over 11/12 to 12/12 4

over 12/12 to 14/12 5

over 14/12 to 16/12 6

over 16/12 to 18/12 7

over 18/12 to 20/12 7.5

over 20/12 to 21/12 8

Meters 0.61 0.61 0.61 0.76 0.99 1.22 1.52 1.83 2.13 2.29 2.44

Rigid Pipe Adapter
*Unit is not exactly as shown.

WARNING:
Do not combine venting components from different venting systems.
However use of the the AstroCapTM and FPI Riser is acceptable with all systems.
This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with Duravent Direct-Vent, Selkirk Direct-Temp, Ameri Vent Direct Venting, ICC Excel Direct, Olympia Ventis DV, and Security Secure Vent systems. Use of these systems with the Rigid Pipe adaptor is deemed acceptable and does not affect the Intertek WHI listing of components.

When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be used to secure rigid pipe to adaptor.

The FPI AstroCapTM and FPI Riser Vent terminal are certified for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent, American Metal Products Ameri Vent Direct Vent, Security Secure Vent®, ICC Excel, Olympia Ventis DV, Selkirk Direct-Temp. AstroCapTM is a proprietary trademark of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
City Series CV50E Direct Vent Gas Fireplace | 17

Venting Arrangement for Vertical Terminations – 5″ x 8″ (127 mm x 203 mm) Rigid and Flex Pipe (Non Power Vent)

The shaded area in the diagram shows all allowable combinations of straight vertical and offset-to-vertical terminations, using two 90o elbows with rigid/flex pipe venting systems.
· Two 45o elbows equal to one 90o elbow.
· Vent must be supported at offsets.
· Minimum distance between elbows is 1 ft. (305 mm).
· Maintain clearances to combustibles as listed in the “Clearances” section.
· Horizontal vent must be supported every 3 feet (0.9 m).
· Firestops are required at each floor level and whenever passing through a wall.
· Must use optional rigid pipe adaptor (Part# 770-994) when using rigid pipe vent systems.
· Refer to the “Vent Restrictor Position” section for details on how to change the vent restrictor from the factory setting of Set 0 through to Set 5, if required.
For vertical terminations, the Regency Direct Vent Flex System may be used for installations with a maximum vent length of up to 40 feet including offsets. If longer runs are required, rigid pipe must be used. If no offsets are used, the maximum run is per the chart on this page.

Vent Restrictor on Set 5: 3/4″ (23 mm) open
Vent restrictor on Set 4: 1-1/2″ (38 mm) open

Maximum: 27.4 ft. (8.4 m) Maximum: 36.39 ft. (11.09 m)

Set 3: 2-3/8″ (60 mm) open

Min. 45-3/4″ (1162 mm) Min. 87-1/2″ (2223 mm)

Min. length of pipe between elbows: 12″ (305 mm)
18 | City Series CV50E Direct Vent Gas Fireplace

Vertical Terminations – Rigid/Flex Pipe 5″ x 8″ (Non Power Vent)
· Two 45o elbows equal to one 90o elbow. Maximum of six 45o elbows allowed. · Vent must be supported at offsets. · Minimum distance between elbows is 1 ft. (305mm). · Maintain clearances to combustibles as listed in the “Clearances” section. · Horizontal vent must be supported every 3 feet. · Firestops are required at each floor level and whenever passing through a wall. · Must use optional rigid pipe adaptor (Part# 770-994 when using rigid pipe vent systems)

Vertical Venting with Three (3) 90o Elbows

One 90o elbow = Two 45o elbows.

Option A) B) C) D)

V 1′ Min. 2′ Min. 3′ Min. 4′ Min.

H + H1 2′ Max 3′ Max 4′ Max 5′ Max

V + V1 3′ Min. 4′ Min. 6′ Min. 7′ Min.

With these options, max. total pipe length is 30 feet with min. of 10 feet total vertical and max. 8 feet total horizontal.

E) 5′ Min. 6′ Max 8′ Min. F) 6′ Min. 7′ Max 9′ Min. G) 7′ Min. 8′ Max 10′ Min. Lengths do not include elbow indicated Restrictor Set 0 – Factory Setting

Please note min. 1 foot between 90o elbows is required.

V1 H1

H

V

City Series CV50E Direct Vent Gas Fireplace | 19

Termination Cap

Storm Collar Flashing

Vertical Terminations – Vertical Flex Vent Kit (Part #946-772) (Non Power Vent) #946-772)

Vertical Flex Vent Kit includes:
· 20 ft. flex pipe (inner & outer) with 10 spacers
· 3 wall straps
· Ceiling firestop · Firestop spacer · Brackets · Flex to rigid adaptor

· Roof support
· 36″ rigid DuraVent pipe · Storm collar · High wind termination cap · Hardware

Roof supporFt irestop spacer to prevent debris from falling into the ceiling firestop
Ceiling firestop

The roof flashing is not included with this kit and must be purchased separately.

Enclosure

NOTE

Vertical flex installations must conform to the limitations set in the vertical venting charts.

You must choose 1 of the following:

Part #

Description

58DVA-F6-0/12-6/12

Roof Flashing

58DVA-F12-7/12-12/12

Roof Flashing

1. Maintain the 1-1/2″ (38 mm) clearance (air space) to combustibles

when passing through ceilings, walls, floors, enclosures, attic rafters or other nearby combustibles. Do not pack air spaces
with insulation. Check venting sections for the maximum vertical

rise of the venting system and the maximum horizontal offset limitations.

Ensure that you maintain clearances around enclosures, walls,
below or above floors, floor joists, etc. Each appliance has different clearance requirements (top,sides,bottom). See specific appliance manual for details.

2. Set the appliance in its desired position. Drop a plumb bob down
from the ceiling/floor joist to the position of the appliance flue exit and mark the location where the vent will penetrate the ceiling. Drill a small hole at this point. Next drop a plumb bob from the roof to the hole previously drilled at the ceiling level and mark the spot where the vent will penetrate the roof.

3. Cut a hole in the roof centered on the small hole placed in the roof in the previous steps. The hole should be a minimum of 11″ (279 mm). The hole may be round and or square.

4. Slip the flashing under the shingles and line up flashing so it is
centered to the hole (shingles should overlap half of the flashing) as per Diagram 1.

Diagram 1 – The upper half of the flashing is installed under the
roofing material and not nailed down until the chimney is installed. This allows for small adjustments.
Diagram 1
5. A ceiling firestop/firestop spacer must be installed when passing through each floor or ceiling level. To install the ceiling firestop/ firestop spacer in a flat ceiling or floor joist cut a 11″ (279 mm) square hole. Frame the hole as show in Diagram 2 and install the ceiling firestop. Slide the top attic insulation spacer onto the top of the attic insulation shield/firestop – See Diagram 2a. Secure with 4 screws/nails. If more than one is required, these can be purchased separately.
The ceiling firestop/firestop spacer may be cut down to size if this shield is too high for the application.
11″ 79

NOTE

Diagram 2a

Ceiling firestop

6. Determine the overall height of the chimney from the top of the appliance to the underside of the vent. If required cut the flexible inner and outer pipe to the desired length up to a maximum of 20 ft. (6.1 m).
7. Put a bead of Mill-Pac around the 5″ (127 mm) collar on the appliance and slide the inner flex pipe over the inner collar of the appliance and secure with a minimum of 3 screws.
8. Install 5″ (127 mm) spacers around 5″ (127 mm) flex.
9. Repeat Step 7 to install the outer pipe to the outer collar of the appliance.
If an offset is necessary in the attic or floor joists it is important to support the vent pipe every 3 feet (914 mm )to avoid excessive stress and sagging of the vent pipe. Wall straps are provided (3 in total) for this purpose. All round/plumbers strapping may also be used if further supports are required.
10. Attach the rigid pipe section to the adaptor by using MillPac on the inner/ outer pipe. Use 3 screws to secure outer pipe.
11. Secure inner flex pipe to pipe adaptor using Mill-Pac over the adaptor. Slide the inner pipe over the flex to rigid adaptor and secure with 3 screws.
12. Repeat Step 11 to secure outer flex.

NOTE

Ceiling firestop

Diagram 2

20 | City Series CV50E Direct Vent Gas Fireplace

13. Slide the finished length up towards the flashing ensuring the

1le3n. gStlihdeotfhepifpineishisedalemnginthimupumtowoafrd2s ftheeetfla(s0h.6in1g emn)sumrinegatshuereledngftrhoomf theptipoepisofatmhienimrouomf. oLfe0v.6eml tmheeacshuirmednferoymatnhde stoepcoufrteheusroinofg. Ltehveelrothoef supcsphidoimertnopef rytohaevnirddoeosdef cawusirteshhuokswiitnntgoutbhsieontgrtooaomfmssiunipdimpeouormtfptorhofev2irdsoecodrefwwaissthsphkeiotr wtsoidnbeuo-tstsoienmeg 1a3. mSDliidnieaigmthreaumfmini3sbohe .fdS2eleensgcDtrhieauwgprsatomwpae4rrdfossrtihdreoeof-lfaspsheiticnehg Deanniasdugrhirneagimgthhet3rlebenq.guSthireeoemf eDnitasg. rSaeme 4 pfoiDpreiairgsoraaommfinp3imiatucfmhoroafs0ne.c6dumrhimnegeiagmshuertethdroefrdqomuifitrh0ee.6mtmoep niosftstihn.esSurofeofiefc.iLeDenviteaalgtnhrdeamadd3itaionfoalr sleencsDchiglDdiueaimetugrnhirrngonaaseftmgvhythesa3aemnrbnater.dreocSeostoerefhrmeeceaouqDsqpdruiuoesahinigirurfoeerseawdni2mndn,tgs,ft4uhtelhsiftisoeieshntrtgirmrisono(aooa0tfmfmyh.sp6eiubinat1pcieiymnphsompuatrbmunrt)uerdpcocrihhoftspeiva2oiiugisdnnsheercstmcddrrueheawwsfqanfiestuishupcirpeaeaikeeldimrtrafnotesottsnierdteblpaesyop.-a.ntStsraSodteermeneeaaeutdmeSdlbiymiet.iprosSsn.oeanel

TermTineartmioninCaatipon Cap

Termination Cap

StormStCoormllarCollar FlashFinlagshing

Storm Collar Flashing

Roof support

SimDleinapggstrhoasmnar3Deaurefroqaruvsireeecdnu,trtihncTigesormmmmineaapttyiohonobCndeaeppifnu0rtc.s6hmalisseistdiinsnseuptfahfircaeietenilnty.saStnredueacSdtidimoitpinosnomanl anual for paDrutranvuemnt bcoemrpso.nents list in the instruction manual for part numbers.

Diagram 3b Roof support
RRooofosufppPoDrittciah gram 3bMinimum Vent Height

Storm Collar TerminFatlaiosnhCinagp

Diagram 3b

Ceiling firestop

Diagram 4

Storm Collar FlashingRoof Support / Brace
Roof Support / Brace
Ceiling Firestop Ceiling Firestop

Roof Pitchflat to 7/12Minimum Vent Height

0.61

Enclosure

over 7/1C2eiltinog f8ire/s1to2p

CeilMinginfireimstopu0m.61Vent

flat to 7/12 oveErnc8los/Ru1re2otoof9P/1i2tch 0.61

Hei0g.6h1t

over 7/12 to 8o/1v2er 9/12 to 10/12 Enc0lo.s6u1re

Fe0e.7t6

over over

8/12 9/12

to to

9o/1v2er 10/12

10f/l1a2t

ttoo171//1122

C0e.6ilin1g firestop 0.76

20.99

over over over

10/12 11/12 12/12

tttoooooo111vvv214eee///oo111rrr222vv111ee142/rr//C111e87222ilin//tgtt11ooofir22e111st264ottp///oo11122298//1101122…925922Ceiling

21.22
1.52
firestop21.83

Minimum Vent Height Meters 0.61
0.61
0.61

Ceiling Firestop CFeleilixngPFipireestop Flex Pipe

over over

14/12 16/12

ttoooo11vv68eeo//11rrv2211e68r//11922/1ttoo212t80o//111220/1122..8133

2.25.13
2.29

0.76

over 18/12 too2vo0e/v1r2e2r0/1102/t1o221t/o1211/21.229

over 20/12 to 21/12

2.44

3.22.544

0.99

Ptoupt raebveean1dt 4wo.faooctPtoeavvurueeptlfkrrarroienmb11vgee21opanne//dt11nthweo22etfareactttxteaooitnrueg11rlfkirot42oihrnme//bg11ecopt22hwniementenheneetytrheasextyitonseutgertiemotrhr.peb54ipecethwaimnedenfnleaytshhseinyogsutetemr.pipe

1.22
and flashing
1.52

15. Slide stor1m5.cooSlvllaiedr erovs1etr4op/rmi1pe2cloetnlolgatr1ho6uv/ne1tirl2ipt ripeaeclheensgtthhe uflna6stihl iintgr.eaches the flashi1ng.8. 3

Diagram 3
Termination Cap

16. Install ter1m6in.aoIntviosentarclal1pte6br/ym1ti2wniastttoiloon1ck8cina/g1pi2tb. y twist lockin7g it.

2.13

17. Secure th1e7f.laoSsveheicnurgr1teo8tthh/ee12rfolaotsfohusi2ning0g/ts1oc2rtehwesroof using7.s5crews

2.29

:

Abenyencclolosseetsod.v:oAresnrtyo2rac0gl/oe1sse2ptsatcooers2sw1tho/i1rcah2gtehesvpeanctepsaswseh8sicthhrtohueghvemnutstpasses

2.44
through

must

be enclosed.

Storm Collar Termination Cap Flashing
Storm Collar Roof Support Flashing
Roof Support Ceiling Firestop Enclosure

14. Put a bead of caulking on the exterior between the outer pipe and flashing to prevent water from penetrating the chimney system.
15. Slide storm collar over pipe length until it reaches the flashing.

Support to prevent sagging

Elbow Support

Ceiling Firestop
Ceiling Firestop Enclosure
Flex Pipe

16. Install termination cap by twist locking it.

Support to prevent sagging

Elbow Support

Ceiling Firestop Flex Pipe

17. Secure the flashing to the roof using screws
Note: Any closets or storage spaces which the vent passes through must be enclosed.

Diagram 3a

City Series CV50E Direct Vent Gas Fireplace | 21

Vertical Flex Extension Kit (Part # 946-769) (Non Power Vent)
20 foot (6.1 m) flex pipe extension

Vertical Flex Extension Kit includes: · 20 ft. flex pipe (inner & outer) with 10 spacers
· 3 wall straps · Flex adaptor · Hardware
Used in conjunction with the 946-772 Vertical Flex Vent Kit for vertical installations.
1. Stretch out both inner 5″ (127 mm) and outer 8″ (203 mm) pipe up to a maximum of 20 ft. (6.1 m).
The inner and outer pipes may be cut if only a short length is required.

5″ (127 mm) inner pipe – 20 ft. (6.1 m) 10 spring spacers
Flex adaptor 3 wall straps

NOTE

2. Install spring spacers around 5″ (127 mm) inner pipe as shown. Slide outer flex pipe over and all the way down the 5″ (127 mm) pipe.
3. Apply a bead of Mill Pac around the perimeter of the 5″ (127 mm) inner collar of the flex adapter and slip the 5″ (127 mm) inner flex pipe from the Vertical termination kit over the flex adapter ensuring that the inner flex pipe overlaps the collar by at least 1.4″ (35 mm). Fasten with 3 screws.
4. Apply a bead of Mill Pac around the perimeter of the 8″ (203 mm) outer collar of the flue adapter and slip it over the 8″ (203 mm) outer flex pipe from the vertical termination kit ensuring that the outer flex pipe overlaps the collar by at least 1.4″ (35 mm). Fasten with the 3 screws.
5. Repeat steps to secure the other end of the flex adapter using the flex kit.
6. See Vertical Vent installation instructions for installation of the complete vent system.

8″ (203 mm) outer flex pipe 20 ft. (6.10 m)

NOTE

If an offset is necessary in the attic or floor joists it is important to support the vent pipe every 3 ft. (0.91 m) to avoid excessive stress and sagging of the vent pipe. Wall straps are provided (3 in total) for this purpose.
All round/plumbers strapping may also be used if further supports are required.

22 | City Series CV50E Direct Vent Gas Fireplace

Ceiling Firestop / Firestop Spacer (Part # 946-770) (Non Power Vent)

Used in conjunction with the 946-772 Vertical Flex Kit and 946-769 Vertical Flex Extension Kit.
A ceiling firestop/firestop spacer must be installed when passing through each floor or ceiling level.

11″ (279 mm) square hole
framing

Steps to install the ceiling firestop/firestop spacer in a flat ceiling or floor joist:

1. Cut a 11″ (279 mm) square hole. 2. Frame the hole as show in Diagram 1. 3. Install the ceiling firestop. 4. Slide the top attic insulation spacer onto the top of the attic insu-
lation shield/firestop – See Diagram 1a. 5. Secure with 4 screws/nails.

Diagram 1

Firestops can be purchased separately if more than one is required.

The ceiling firestop/firestop spacer may be cut down to size if it is too high for the application.

Termination Cap

127 mm inner pipe

Storm Collar

Termination CaFplashing Firestop spacer to prevent debris

127 mm inner pipe10 spSritnorgm Csopllaarcers

from falling into the ceiling

Flashing Roof support firestop

Ceiling firestop

10 spring spacers

Roof support

Ceilfilnegxfiaredsatopptor

Enclosure
flex adaptor

Diagram 1a

Ceiling firestop

NOTE

outer flex pipe

outer flex pipe

Used in conjunction with the 946-755 Vertical flex kit and 946-756 kit Vertical flex extension kit/Horizontal power vent kit.

Used in cAocnejuilinncgtifoirneswtiothp/tfhirees9t4o6p- s7p5a5cVeerrmticuasltfbleexinksittaalnledd9w4h6e-7n5p6aksistiVnegrtthicraolugh each

flex extefnlosoiornorkcite/Hilionrgizleovnetal.lTpooiwnsetravllethnet kciet.iling firestop/firestop spacer in a flat ceiling

or floor joist cut a 279 mm square hole. Frame the hole as show in Diagram

79

Aceiling1firaensdtoipn/sfitraelsl ttohpe scpeailcinegr mfiruessttobpe.inSslitdaellethdewthoepnapttaicssininsgultahtriooungshpeaaccehr onto the floor or cetoilpingofletvheel.aTtoticinsintaslul ltahteiocneislihnigeflidr/efisrteospto/fipre-stSoepespDaiacegrrainma 1flaat. cSeeilcinugre with 4 or floor josicsrtecwust/ana2i7ls9. Imf mmorseqtuhaarneohnoeleis. Freraqmuireetdh,ethheosleecaasnsbheopwuirnchDaisaegdrasmeparately. 79

1 and install the ceiling firestop. Slide the top attic insulation spacer onto the top of the atticTihnesucleaitliionng fsirheisetlodp/f/ifrieresstotopp- sSpaeceeDr miaagyrabme c1uat.dSowecnutroesiwzeithif t4his shield screws/nails. Ifims otoreo thhiagnhofonretihsereaqpupirliecda,titohne.se can be purchased separately.

The ceiling firestop/firestop spacer may be cut down to size if this shield is too high for the application.

TeTremrminiantaiotinonCCapap

SStotromrmCCololallrar TeTremrminiantaiotinonCCaFpaFlaplsahsihnigng Ceiling firestop

Ceiling firestop

SStotromrmCCololallrar
FFlalsahsihnigng RRooofosf uspuppoprotrftirestop

RRooofosf uspuppoprotrftirestop
Ceiling firestop

Enclosure Ceiling firestop

Enclosure

Ceiling firestop

Ceiling firestop

City Series CV50E Direct Vent Gas Fireplace | 23

Exterior Vent Termination Locations (Power Vent)

Minimum Clearance Requirements
A Clearance above grade, veranda, porch, deck, or balcony
B Clearance to window or door that may be opened
C Clearance to permanently closed window
D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61cm) from the center line of the terminal (check with the local code)

Canada1 12″(30cm) 12″(30cm)

  • 29″(74cm)

USA2 12″(30cm) 9″ (23cm)

  • 29″(74cm)

E Clearance to unventilated soffit
F Clearance to outside corner: with PowerVent Termination Cap (End of line) Clearance to outside corner: with AstroCap Termination Cap (Inline)
G Clearance to inside corner: with PowerVent Termination Cap (End of line) Clearance to inside corner: with Astro Cap Termination Cap (Inline)
H Clearance to each side of center line extended above meter/regulator assembly
J Clearance to service regulator vent outlet
K Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance
L Clearance to a mechanical air supply inlet #3′ (91cm) above if within 10′ (3m) horizontally.

29″(74cm) 7″(18cm)

29″(74cm) 7″(18cm)

7″(18cm) 36″(90cm)a 36″(90cm) 12″(30cm) 72″(1.8m)

7″(18cm)

    • 9″ (23cm) 36″(90cm)b

M Clearance above paved sidewalk or a paved driveway located on public property

84″(2.1m)

N Clearance under veranda, porch, deck, or balcony

12″(30cm)

1 In accordance with current CSA B149.1, Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings

Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor

a *

Clearance in accordance with local 3 feet (91cm) within a height of 15

installation codes and the requirements of the gas feet (4.5m) above the meter / regulator assembly

supplier

b 3 feet (91cm) above – if within 10 feet (3m) horizontally

24 | City Series CV50E Direct Vent Gas Fireplace

4″x 6-5/8″ Rigid Pipe Cross Reference Chart (Power Vent)
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI. IMPORTANT : When using the inline Power Vent system & rigid pipe: Vertical Terminations (Inline): Only Simpson Duravent rigid pipe is approved for use. Must use the 46DVA-VCH vertical high wind cap as this is the only approved cap. Horizontal Terminations (Inline): Only the 946-523/P Astro horizontal cap may be used in conjunction with any of the vent systems noted below.

Description
High Wind Vertical Cap Flashing Flat Roof Flashing 0/12-6/12 Flashing 7/12-12/12 Storm Collar 6″ Pipe Length-Galvanized 6″ Pipe Length-Black 7″ Pipe Length-Galvanized 7″ Pipe Length-Black 9″ Pipe Length-Galvanized 9″ Pipe Length-Black 12″ Pipe Length-Galvanized 12″ Pipe Length-Black 18″ Pipe Length- Galvanized 18″ Pipe Length-Black 24″ Pipe Length-Galvanized 24″ Pipe Length- Black 36″ Pipe Length-Galvanized 36″ Pipe Length-Black 48″ Pipe Length- Galvanized 48″ Pipe Length-Black 60″ Pipe Length-Galvanized 60″ Pipe Length- Black

Simpson Direct Vent Pro®
46DVA-VCH 46DVA-FF 46DVA-F6 46DVA-F12 46DVA-SC 46DVA-06 46DVA-06B N/A N/A 46DVA-09 46DVA-09B 46DVA-12 46DVA-12B 46DVA-18 46DVA-18B 46DVA-24 46DVA-24B 46DVA-36 46DVA-36B 46DVA-48 46DVA-48B 46DVA-60 46DVA-60B

Selkirk Direct TempTM
N/A N/A N/A N/A N/A 4DT-6 4DT-6B N/A N/A 4DT-9 4DT-9B 4DT-12 4DT-12B 4DT-18 4DT-18B 4DT-24 4DT-24B 4DT-36 4DT-36B 4DT-48 4DT-48B 4DT-60 4DT-60B

American Metal Products® Amerivent Direct N/A N/A N/A N/A N/A N/A N/A 4D7 4D7B N/A N/A 4D12 4D12B 4D18 4D18B 4D24 4D24B 4D36 4D36B 4D48 4D48B N/A N/A

Metal-FabTM Sure Seal
N/A N/A N/A N/A N/A 4D6 4D6B N/A N/A N/A N/A 4D12 4D12B 4D18 4D18B 4D24 4D24B 4D36 4D36B 4D48 4D48B N/A N/A

Security Secure- Vent®
N/A N/A N/A N/A N/A SV4L6 SV4LB6 N/A N/A N/A N/A SV4L12 SV4LB12 SV4LA SV4LA SV4L24 SV4LB24 SV4L36 SV4LB36 SV4L48 SV4LB48 N/A N/A

ICC Excel Direct
N/A N/A N/A N/A N/A TC-4DL6 TC-4DL6B N/A N/A TC-4DL9 TC-4DL9B TC-4DL1 TC-4DL1B TC-4DL18 TC-4DL18B TC-4DL2 TC-4DL2B TC-4DL3 TC-4DL3B TC-4DL4 TC-4DL4B N/A N/A

Olympia Ventis DV*
N/A N/A N/A N/A N/A VDV-0406 VDVB-0406 N/A N/A VDV-0409 VDVB-0409 VDV-0412 VDVB-0412 VDV-0418 VDVB-0418 VDV-0424 VDVB-0424 VDV-0436 VDVCB-0436 VDV-0448 VDVB-0448 N/A N/A

Adjustable Length 3″-10″-Galvanized N/A

N/A

Adjustable Length 3″-10″-Black

N/A

N/A

Adjustable Length 7″-Galvanized

N/A

N/A

Adjustable Length 7″-Black

N/A

N/A

Extension Pipe 8-1/2″-Galvanized

46DVA-08A

N/A

Extension Pipe 8-1/2″-Black

46DVA-08AB

N/A

Adjustable Length 12″-Galvanized N/A

N/A

Adjustable Length 12″-Black

N/A

N/A

Extension Pipe 16″-Galvanized

46DVA-16A

N/A

Extension Pipe 16″-Black

46DVA-16AB

N/A

N/A N/A 4D7A 4D7AB N/A N/A 4D12A 4D12A N/A N/A

4DAL 4DALB N/A N/A N/A N/A N/A N/A N/A N/A

N/A

TC-4DLT

N/A

N/A

TC-4DLTB

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

SV4LA12

TC-4dLSI

N/A

SV4LBA12

TC-4dLSIB

N/A

N/A

N/A

N/A

N/A

N/A

N/A

45º Elbow-Galvanized 45º Elbow-Black 45º Elbow Swivel-Galvanized 45º Elbow Swivel-Black 90º Elbow-Galvanized 90º Elbow-Black 90º Elbow, Swivel-Galvanized 90º Elbow, Swivel-Black 90º Starter Elbow, Swivel-Galvanized Adaptor*

46DVA-E45 46DVA-E45B See 46DVA-E45 See 46DVA-E45B 46DVA-E90 46DVA-E90B See 46DVA-E90 See 46DVA-E90B N/A N/A

4DT-EL45 4DT-EL45B N/A N/A 4DT-EL90S 4DT-EL90SB N/A N/A N/A N/A

4D45L 4DT-EL45B N/A N/A 4DT-EL90S 4DT-EL90SB N/A N/A N/A N/A

N/A N/A 4D45L 4D45LB N/A N/A 4D90L 4D90LB 4D90A 4D90L

N/A N/A SV4E45 SV4EB45 N/A SV4EBR90-1 SV4E90-1 SV4EB90-1 N/A N/A

TE-4DE45 TE-4DE45B N/A N/A TE-4DE90 TE-4DE90B N/A N/A N/A N/A

VDV-EL0445 VDVB-EL0445 N/A N/A VDV-EL0445 VDVB-EL0445 N/A N/A N/A VDV-UAA04

Ceiling Support Cathedral Support Box Wall Support/Band

N/A 46DVA-CS 46DVA-WS

4DT-CS 4DT-CSS 4DT-WS/B

4DSP 4DRSB 4DWS

4DFSP 4DRS 4DWS

SV4SD SV4CSB SV4BM

TM4-RDS TM4-SDS TM-SWS

VDV-SCR04 VDV-CSS04 VDV-WS04

City Series CV50E Direct Vent Gas Fireplace | 25

4″x 6-5/8″ Rigid Pipe Cross Reference Chart (Power Vent)

Description

Simpson Direct Vent Pro®

Offset Support Wall Thimble-Black Wall Thimble Support/Ceiling Support Firestop Spacer

46DVA-ES 46DVA-WT 46DVA-DC 46DVA-FS

Selkirk Direct TempTM
4DT-OS 4DT-WT N/A 4DT-FS

American Metal Products® Amerivent Direct
N/A
4DWT
N/A
4DFSP

Metal-FabTM Sure Seal
N/A 4DWT N/A 4DFS

Trim Plate-Black

N/A

4DT-TP

Attic Insulation Shield 12″

46DVA-IS N/A@ FPI N/A

Attic Insulation Shield – Cold Climates 36″ N/A

N/A

4DFPB 4DAIS12 4DAIS12

4DcP DDIS N/A

Wall Firestop

46DVA-WFS

N/A

N/A

N/A

Security Secure- Vent®
SV4SU SV4RSM SV4PF SV4BF
SV4LA SV4RSA N/A
N/A

ICC Excel Direct
TM-SOS N/A N/A TM-4CS
TM-4TP N/A TM-4AS
TM-4TR

Olympia Ventis DV*
N/A VDV-WPT04 N/A VDV-FS04
VDV-WTC04 VDV-AIS04 N/A
VDV-FS04

Offset Pipe Selection: Use this table to determine offset pipe lengths.

Pipe Length (L)

4″ x 6-5/8″ Venting

Run (X)

Rise (Y)

0″ (0mm)

4-7/8″ (124mm)

13-7/8″ (340mm)

6″ (152mm)

8″ (203mm)

16-1/2″ (419mm)

9″ (229mm)

10-1/8″ (257mm)

18-5/8″ (473mm)

12″ (305mm)

12-1/4″ (311mm)

20-3/4″ (527mm)

24″ (610mm)

20-5/8″ (524mm)

29-1/8″ (740mm)

36″ (914mm)

29″ (737mm)

37-1/2″ (953mm)

48″ (1219mm)

37-7/16″ (951mm)

45-15/16″ (1167mm)

For specific instructions on venting components – visit the manufacturers website listed below.
Simpson Direct Vent Pro: www.duravent.com Selkirk Direct-Temp: www.selkirkcorp.com American Metal Products: www.americanmetalproducts.com Metal-Fab Sure Seal: www.mtlfab.com Security Secure Vent: www.securitychimneys.com Industrial Chimney Company: www.icc-rsf.com Olympia Ventic DV: www.olympiachimney.com

26 | City Series CV50E Direct Vent Gas Fireplace

IMPORTANT

Introduction
· The instructions contained in this manual must be read carefully prior to installation of this appliance. · 120 Volt AC power is required for this appliance to operate. A receptacle box, receptacle, and cover are provided.
See the “Wiring the Unit” section in this manual. Electrical power must be brought to the appliance by a licensed electrician.
The City 50 Series power vent system is designed to allow the installation of this gas appliance when typical vent configurations (Non-Power Vent Direct Vent Systems With no Fan Assist) are not possible due to excessive offsets, long or negative vent runs, etc.
When installed as a power vent appliance, this unit is designed to use flex or rigid venting.
The City 50 models come with a 5″ inner and 8″outer collar which must be reduced to 4″ inner x 6-5/8″ outer (102 mm x 168 mm) in all applications. See required reducers required as per below depending if using rigid/flex pipe.

NOTES

The Vent Pipe Adaptor must always be used for Power Vent System: See below ” Pipe Adaptor & Reducer CHART”.
Vent Pipe Adaptor & Reducer Chart

City 50, 60 & 72 Series

Ridge Pipe Adaptor 5″ x 8″ Adaptor (770 – 994) 4″ x 6 ” Collar Reducer (946 – 606)
x 6 ” Adaptor

Flex Pipe Reducer 4″ x 6 ” Reducer (946 – 758)

· Rigid pipe is approved for up to 72 feet (21.95 m). · Flex pipe is approved for up to 40 feet (12.19 m) using 2 X 946-756– 20 foot (6.10 m) flex kits.

NOTES

There are two options available when installing this unit as a power vent appliance: · End of line flush horizontal power vent system (Part #946-535): flush power vent fan acts as the termination cap and sits flush to the outside
wall. Allowed for horizontal termination only. · Inline power vent system (Part #666-945): power vent fan terminal is incorporated into the vent run – allows for both horizontal and vertical
termination.
This unit may be terminated vertically or horizontally using the Power Vent Systems available. See the following pages for various vent configurations using rigid or flex & vertical or horizontal terminations. The instructions contained in this manual must be read carefully prior to installation.
Vent Restrictor Position

In_Line End_Line

City 50 Series, City 60 Series City 72 Series
Full open Full open

In-Line

City 40 Series
Full open 1″ Open

End-Line

Ristrictor Position

Note: For specific installation instructions for both In line and End of line, see power vent system instruction manual which may be found in the QR code
located below. The following pages in this manual will only detail allowable vent configurations for both inline and end of line vent power vent systems. Part # of the Power Vent System manual is 920-544.

Power Vent System Manual

Minimum Vent Clearances

to Combustibles

Horizontal Top

3″ (76mm)

Horizontal Side

2 ” (51mm)

Horizontal Bottom

2″ (51mm)

Vertical Vent

2″ (51mm)

City Series CV50E Direct Vent Gas Fireplace | 27

Vent Chart for Power Vent Only Horizontal Terminations – Inline Horizontal Vent Chart Rigid/Flex
This section is for the Power Vent System installation. For a detailed installation information, refer Power Vent System installation instructions that comes with the Power Vent Kit. When you install the Power vented fireplace, you need one of the following Power Vent System Kit depending your venting layout. For the complete Power Vent installation, refer the Power Vent System installation instruction in Power vent system Kit. In line Power Vent Kit # 666-945
RIGID PIPE: MUST USE RIGID PIPE ADAPTOR 770-994 AND 946-606 PIPE REDUCER TO 4″ X 6 5/8″ (102 mm x 168 mm). FLEX VENT: MUST USE REDUCER 946-758 TO 4″ X 6 5/8″ (102 mm x 168 mm).
· Rigid pipe is approved for up to 72 feet (22 m). · Flex pipe is approved for up to 40 feet (12.2 m) using two 20 foot (6.1 m) flex kits (part # 946-756). · This model comes with a 5″ (127 mm) inner and an 8″ (203 mm) outer collar which must be reduced to 4″ x 6-5/8″ (102 mm x 168 mm) in all applications. · Must be terminated horizontally. Vertical terminations are not permitted.

NOTES

The gas power vent system is designed to allow the installation of a gas appliance when typical vent configurations (shown in this manual) are not possible.

Minimum 1 ft (0.3 m) following an elbow
72′ (22 m) Overall length Max. Shown with 5 – 900 elbows

Minimum 1 ft (0.3 m) prior to a termination cap

Restrictor – Fully Open

72′ (22 m) Overall length Max. Shown with 3 – 900 elbows
Minimum 4 ft (1.2 m) from the unit

Minimum 1 ft (0.3 m) prior to an elbow
Maximum allowable negative run 7 ft (2.1 m)

72′ (22 m) run (no rise)

**Inline blower when installed after a negative run must be an equal distance or greater from a 90 degree elbow. (Example: In a 3-foot (.91 m) negative run, the inline power vent must be a minimum of 3 feet (0,91 m) away from the elbow.)

· Maximum total vent length (based on overall length of combined chimney components) = 72′ (22 m)
· Maximum total negative vent length = 7′ (2.1 m). · Do not run positive venting after a negative run. · Maximum of six – 90° elbows permitted. · One 90° elbow = two 45° elbows. · Minimum 4′ (1.2 m) from the unit prior to terminating.

Inline power vent location restrictions: Minimum 4 ft (1.2 m) from the unit Minimum 1 ft (0.3 m) prior to an elbow. Minimum 1 ft (0.3 m) following an elbow. Minimum 1 ft (0.3 m) prior to a termination cap. When the inline blower is installed after a negative run, for every foot of negative run the inline blower must be an equal distance or greater from the 90-degree elbow. See example above.

IMPORTANT

Vent Restrictor Position
No vent restrictor required.

Set 0 Fully open Factory Set
28 | City Series CV50E Dir3e18″ct Vent Gas Fireplace
318″

NOTES

Vent Chart for Power Vent Only Horizontal Terminations – End of Line Horizontal Vent Chart Rigid/Flex
For the complete Power Vent installation, refer the Power Vent System installation instruction in Power vent system Kit End Line Power Vent Kit # 946-535 RIGID PIPE: MUST USE RIGID PIPE ADAPTOR 770-994 AND 946-606 PIPE REDUCER TO 4″ X 6 5/8″ (102 mm x 168 mm). FLEX VENT: MUST USE REDUCER 946-758 TO 4″ X 6 5/8″ (102 mm x 168 mm).
· Rigid pipe is approved for up to 72 feet (22 m). · Flex pipe is approved for up to 40 feet (12.2 m) using two 20 foot (6.1 m) flex kits (part # 946-756). · This model comes with a 5″ (127 mm) inner and an 8″ (203 mm) outer collar which must be reduced to 4″ x 6-5/8″ (102 mm x 168 mm) in all applications. · Must be terminated horizontally. Vertical terminations are not permitted.
The gas power vent system is designed to allow the installation of a gas appliance when typical vent configurations (shown in this manual) are not possible.
72′ (21.95 m) overall length max. Shown with 5 – 900 elbows

Restrictor – Fully Open

72′ (21.95 m) overall length max. Shown with 3 – 900 elbows

72′ (21.95 m) run (no rise)

IMPORTANT

Shown with 2 elbows (negative run 72′ – 21.95 m)

This negative run is for the end of line power vent cap only. Do not run with the inline power vent.

· Maximum total vent length (based on overall length of combined chimney components) = 72′ (21.95 m) · Maximum total negative vent length = 7′ (2.1 m). · Do not run positive venting after a negative run. · Maximum of six – 90° elbows permitted. · One 90° elbow = two 45° elbows. · Minimum 4′ (1.2 m) from the unit prior to terminating.

Vent Restrictor Position
No vent restrictor required.

Set 0 Fully open Factory Set

City Series CV50E Direct Vent Gas Fireplace | 29
318″

Venting Arrangement for Vertical Terminations Inline Power Vent Rigid/Flex In line Power Vent Kit # 666-945
Vertical venting with straight vertical veOn4t”inXg6 a5/n8d” (1o0r2wmimthx a16m8 maxm.).of six (6) 90o Elbows (1 – 90o = 2 – 45o)
· Rigid pipe is approved for up to 72 feet (22 m). · Flex pipe is approved for up to 40 feet (12.2 m) using
two 20 foot (6.1 m) flex kits (part # 946-756).

NOTES

· Two 45o elbows equal to one 90o elbow. · Vent must be supported at offsets. · Minimum distance between elbows is 1 ft. (0.3 m). · Maintain clearances to combustibles as listed in the
“Clearances” section. · Horizontal vent must be supported every 3 feet (0.91 m). · Firestops are required at each floor level and whenever
passing through a wall.
Restrictor set on 0 (fully open) regardless of vent run.
Inline power vent location restrictions: · Minimum 4 ft (1.2 m) from the unit. · Minimum 1 ft (0.3 m) prior to an elbow. · Minimum 1 ft (0.3 m) following an elbow. · Minimum 2 ft (0.6 m) prior to a termination cap. · Minimum 2 ft. from inline PV to termination cap. · Minimum 4′ from top of unit to inline PV. · Max. of 72′ (22 m), using up to six 900 elbows · (Example shows two 900 elbows). · No negative runs.
· The inline power vent must be installed within the confines of the home/structure.

Max. 72′ (21.95 m)

Min. 2′ (0.61 m) from inline PV to termination cap
Min. 4′ (1.22 m) from top of unit to inline PV

NOTE

(0.61 m) from inline o termination cap
(1.22 m) from nit to inline PV

Max. of 72′ (21.95 m), using up to six 900 elbows
(Note: two 900 elbows shown.)

3RD ANGLE PROJECTION
DO NOT SCALE DRAWING
UNITS IN INCHES

TOLERANCES UNLESS OTHERWISE STATED DIMENSIONS 0.000 = 0.01 CRITICAL 0.000 = SPECIFIED TOLERANCE 0.000 = 0.031 0.000 REF = REFERENCE ONLY ANGULAR = 1

FIREPLAC INTER
SCALE: 1:24 DWN: MEDRA
E.C.N.:

THIS DRAWING IS THE PROPERTY OF FPI LTD., IT MAY NOT BE COPIED IN W

Min. 55′ 1/4″ Flex Vent Min. 59′ 1/4″ to C/L Rigid Vent

Min. 4′ (1.22 m) from top of unit to inline PV

Min. 2′ (0,61 m) from inline PV to termination cap

30 | City Series CV50E Direct Vent Gas Fireplace

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Regency User Manuals

Related Manuals