AIRTECHNIC WALL/FREE-40-2T-1.5 IE3 Dynamic Wall Mount Extractor Fans Owner’s Manual
- June 1, 2024
- AIRTECHNIC
Table of Contents
AIRTECHNIC WALL/FREE-40-2T-1.5 IE3 Dynamic Wall Mount Extractor Fans
Owner’s Manual
Dynamic wall mount extractor fans fitted with motorised hatch
Fan:
- Wall fixing flange for correct and easy
- Support frame in galvanized sheet steel.
- Variable angle impeller made of cast
- Airflow direction from motor to
- Protection grid against contacts according to UNE-EN ISO
Extruded aluminum hatch:
- An extremely robust structure that is able to withstand severe weather changes.
- Designed to ensure
- Aluminum profile with thermal bridge
- Central ceiling and structure equipped with high performance thermal
- Thermal resistance of the assembly less than 0.89 W/m2∙
- Limit switches in both positions (open and closed).
- Possibility of mounting in upper and lower
- Manual opening
model.
- IE3 efficiency
- Three-phase 230/400 V 50 Hz (up to 4 kW) and 400/690 V 50 Hz (powers greater than 4 kW).
- Working temperature: -25 ºC +50 ºC.
Actuator:
- Reliability greater than 11,000 dual
- Supply voltage at 230 V AC 50/60
- Working temperature: -25 ºC +60 ºC.
Flap finish:
- Anti-corrosive in extruded
- RAL 7016 supplied as Any other RAL can be supplied on demand.
On request:
- AA: impeller-motor air direction for air entry to
Model| Speed
(r/min)
| Maximum admissible current (A)| Installed power
(kW)
| Blade tilt angle
(º)
| Maximum flow rate
(m3/h)
| Sound pressu- re level1
dB (A)
| Ap- prox. weight
(Kg)
| According ErP*
---|---|---|---|---|---|---|---|---
230V| 400V| 690V
WALL/FREE-63-4T-3 IE3| 1425| 7.86| 4.52| | 2.20| 32| 22170| 65| 97| 2020
---|---|---|---|---|---|---|---|---|---|---
WALL/FREE-63-4T-4 IE3| 1430| 11.01| 6.33| | 3.00| 38| 24240| 66| 103| 2020
WALL/FREE-71-4T-3 IE3| 1425| 7.86| 4.52| | 2.20| 22| 25100| 67| 100| 2020
WALL/FREE-71-4T-4 IE3| 1430| 11.01| 6.33| | 3.00| 28| 27480| 67| 106| 2020
WALL/FREE-71-6T-1.5 IE3| 945| 4.73| 2.72| | 1.10| 34| 19930| 58| 98| 2020
WALL/FREE-80-4T-4 IE3| 1430| 11.01| 6.33| | 3.00| 16| 30270| 71| 120| 2020
---|---|---|---|---|---|---|---|---|---|---
WALL/FREE-80-4T-5.5 IE3| 1440| | 7.95| 4.61| 4.00| 18| 32770| 70| 122| 2020
WALL/FREE-80-6T-1.5 IE3| 945| 4.73| 2.72| | 1.10| 18| 21470| 60| 112| 2020
WALL/FREE-80-6T-2 IE3| 945| 6.25| 3.62| | 1.50| 26| 25970| 61| 116| 2020
WALL/FREE-90-4T-7.5 IE3| 1460| | 10.40| 6.04| 5.50| 18| 46140| 74| 183| 2020
WALL/FREE-90-4T-10 IE3| 1460| | 14.20| 8.17| 7.50| 22| 50140| 73| 187| 2020
WALL/FREE-90-6T-3 IE3| 950| 9.78| 5.62| | 2.20| 24| 34000| 63| 145| 2020
WALL/FREE-90-6T-4 IE3| 970| 12.80| 6.36| | 3.00| 30| 38910| 66| 165| 2020
WALL/FREE-100-4T-10 IE3| 1460| | 14.20| 8.17| 7.50| 16| 57420| 76| 194| 2020
WALL/FREE-100-4T-15 IE3| 1460| | 20.70| 11.99| 11.00| 22| 66300| 76| 226|
2020
WALL/FREE-100-4T-20 IE3| 1460| | 27.80| 16.03| 15.00| 28| 76160| 77| 237|
2020
1 Irradiated sound pressure level in dB(A) at a distance of 3 m.
- In accordance with the ErP 2020 draft
WALL/FREE
Model
|
A
|
B
|
C
|
D
|
E
|
F
|
G
|
J1
|
J2
|
K1
|
K2
---|---|---|---|---|---|---|---|---|---|---|---
WALL/FREE-40| 640| 590| 650| 600| 82| 430| 375| 700| 200| 700| 200
---|---|---|---|---|---|---|---|---|---|---|---
WALL/FREE-45| 640| 590| 650| 600| 82| 430| 400| 700| 200| 700| 200
WALL/FREE-56| 690| 690| 700| 700| 82| 560| 415| 790| 220| 790| 220
WALL/FREE-63| 990| 990| 1000| 1000| 82| 760| 475| 1050| 300| 1050| 300
WALL/FREE-71| 990| 990| 1000| 1000| 82| 760| 500| 1050| 300| 1050| 300
WALL/FREE-80| 990| 990| 1000| 1000| 82| 760| 500| 1050| 300| 1050| 300
WALL/FREE-90| 1190| 1190| 1200| 1200| 82| 790| 525| 1250| 250| 1250| 250
WALL/FREE-100| 1190| 1190| 1200| 1200| 82| 790| 550| 1250| 250| 1250| 250
C x D) Nominal size of the wall opening.
Read More About This Manual & Download PDF:
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>