AIRTECHNIC TT Silent M Series Energy Efficient Mixed In-Line Fans User Manual
- June 9, 2024
- AIRTECHNIC
Table of Contents
VENTS INLINE FANS IN
SOUND-INSULATED CASING
USER’S MANUAL
TT Silent-M
This user’s manual is a main operating document intended for technical,
maintenance, and operating staff.
The manual contains information about purpose, technical details, operating
principle, design, and installation of the TT Silent-M unit and all its
modifications.
Technical and maintenance staff must have theoretical and practical training
in the field of ventilation systems and should be able to work in accordance
with workplace safety rules as well as construction norms and standards
applicable in the territory of the country.
FOLLOW THE USER’S MANUAL REQUIREMENTS TO ENSURE DURABLE AND TROUBLE-FREE OPERATION OF THE UNIT
SAFETY REQUIREMENTS
All user’s manual requirements as well as the provisions of all the applicable
local and national construction, electrical, and technical norms and standards
must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing,
maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to
1000 V are allowed for installation. The present user’s manual should be
carefully read before beginning works.
Check the unit for any visible damage of the impeller, the casing, and the
grille before starting installation. The casing internals must be free of any
foreign objects that can damage the impeller blades.
While mounting the unit, avoid compression of the casing! Deformation of the
casing may result in motor jam and excessive noise.
Misuse of the unit and any unauthorised modifications are not allowed. Do not
expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky
substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing
spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the
efficient air flow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the
document’s preparation.
The Company reserves the right to modify the technical characteristics,
design, or configuration of its products at any time in order to incorporate
the latest technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.
This unit is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of the
unit by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the unit.
Connection to the mains must be made through a disconnecting device, which is integrated into the fixed wiring system in accordance with the wiring rules for design of electrical units, and has a contact separation in all poles that allows for full disconnection under overvoltage category III conditions.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons in order to avoid a safety hazard.
CAUTION: In order to avoid a safety hazard due to inadvertent resetting of the thermal cut-out, this unit must not be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly switched on and off by the utility.
Ensure that the unit is switched off from the supply mains before removing the
guard.
WARNING: If there are any unusual oscillating movements, immediately stop
using the unit and contact the manufacturer, its service agent or suitably
qualified persons.
The replacement of parts of the safety suspension system device shall be
performed by the manufacturer, its service agent or suitably qualified
persons.
Fixing means for attachment to the ceiling such as hooks or other devices
shall be fixed with a sufficient strength to withstand 4 times the weight of
the appliance.
The mounting of the suspension system shall be performed by the manufacturer,
its service agent or suitably qualified persons.
The appliance is to be installed so that the blades are more than 2.3m above
the floor.
Precautions must be taken to avoid the back-flow of gases into the room from
the open flue of gas or other fuel-burning appliances.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
DELIVERY SET
Fan
1 pc.
Screws with dowels 4
pcs.
Plastic screwdriver (only for the models with a timer) 1 pc.
User’s manual 1
pc.
Packing box
1 pc.
OPERATION GUIDELINES
The fan is rated for connection to single-phase AC 220-240 V/50 Hz or 220 V/60
Hz power mains.
The unit is rated for continuous operation.
The arrow on the fan casing must match the air direction in the system.
The fan is rated as a class II electric appliance.
Ingress protection rating against access to hazardous parts and water ingress
is IPX4.
The fan is rated for operation at the ambient air temperature from +1 °C up to
+40 °C.
Power [V/Hz] | Transported air temperature [°C] |
---|---|
220-240/50 | -25…+60 |
220/60 | -25…+40 |
To comply with the ErP 2018 regulation, a local demand controller and speed controller must be used.
BRIEF DESCRIPTION
The unit described herein is a mixed-flow duct fan for supply or exhaust
ventilation of premises. The fan is designed for connection to ø 100, 125,
150, 160, 200, 250 and 315 mm air ducts.
An external control unit can be connected to the fan.
The fan design is constantly being improved, thus some models may be slightly
different from those described in this manual.
Overall dimensions:
|
Ø D
| B| H| L| M|
N
---|---|---|---|---|---|---
TT Silent-M 100|
98
| 243| 237| 505| 231|
44
TT Silent-M 125|
123
| 243| 237| 474| 231|
44
TT Silent-M 150|
148
| 274| 263| 580| 231|
44
TT Silent-M 160|
157
| 274| 263| 580| 231|
44
TT Silent-M 200|
198
| 392| 295| 560| 310|
115
TT Silent-M 250|
248
| 445| 360| 665| 370|
130
TT Silent-M 315|
313
| 526| 434| 785| 450|
180
DESIGNATION KEY
-
Unit voltage:
_ — 220-240 V/50 (60) Hz (by default)
YYY V/ZZ Hz — mains parameters other than the default ones -
Options:
T: timer
U: speed controller with an electronic thermostat and a temperature sensor integrated into the air duct; power cord with a mains plug. Temperature-based operation logic
Un: speed controller with an electronic thermostat and external temperature sensor fixed on 4 m cable; power cord with a mains plug. Temperature-based operation logic
U1: speed controller with an electronic thermostat and a temperature sensor integrated into the air duct; power cord with a mains plug. Timer-based operation logic
U1n: speed controller with an electronic thermostat and external temperature sensor fixed on 4 m cable; power cord with a mains plug. Timer-based operation logic
U2: speed controller with an electronic thermostat and a temperature sensor integrated into the air duct; power cord with a mains plug. Temperature-based switching on/off
U2n: speed controller with an electronic thermostat and external temperature sensor fixed on 4 m cable; power cord with a mains plug. Temperature-based switching on/off
P: smooth speed controller from 0 to 100 % and a power cord with a mains plug
R: power cord with a mains plug
V: speed switch -
Outlet spigot diameter [mm]
-
Casing material:
M — metal -
Casing design:
Silent – sound-insulated -
Fan model
For a description of the fan options, see the «Electronics operation algorithm» section.
INSTALLATION AND SET-UP
The fan is suitable both for horizontal or vertical mounting on the floor, on
the wall or on the ceiling.
While mounting the fan, provide extra protection against water ingress, such
as:
- For the top mounting install an outer protecting hood above.
- For any mounting position connect an air duct on both sides of the fan.
Cut off power supply and make sure electricity has been turned off. Mark the holes for fixing the fan and the power cable.
|
Lead the power cable to the ventilation hole, drill the mounting holes and install the dowels.
---|---
Fix the fan with the screws.
|
For any mounting position connect an air duct on both sides of the fan.
Cut off power supply and make sure electricity has been turned off. Remove the cover of the fan.
|
Connect the power cord wires to the terminal block and assemble the fan in reverse order.
| Supply power to the fan.
|
Mounting sequence for different fan models
|
|
|
|
TT Silent-M … T
| TT Silent-M … RV
---|---
|
TT Silent-M … U (U1, U2, Un, U1n, U2n)
| TT Silent-M … P
- Thermostat control knob
- Speed control knob
|
- Speed control knob
CONNECTION TO POWER MAINS
The fan is rated for connection to single-phase AC 220-240 V/50 (60) Hz power mains.
TERMINAL DESIGNATIONS ON WIRING DIAGRAMS
L1 — minimum speed terminal S — external speed controller
L2 — maximum speed terminal ST — external switch
QF — automatic circuit breaker SW — control mode switch
Automatic circuit breaker Automatic
designation in the wiring diagram circuit breaker
Designation of the external switch on External
the wiring diagram switch
DO NOT USE A METAL SCREWDRIVER, KNIFE, ETC. FOR ADJUSTMENT OPERATIONS NOT TO DAMAGE THE CIRCUIT BOARD
TT Silent-M 100/125
Max
|
Max/min
Min
|
TT Silent-M 150/160/200/250/315
Max
|
Max/min
Min
|
TT Silent-M … T
terminal block for 5 contacts
Max
|
terminal block for 4 contacts
terminal block for 5 contacts
Max/min
|
terminal block for 4 contacts
terminal block for 5 contacts
Min
|
terminal block for 4 contacts
ELECTRONICS OPERATION ALGORITHM
It is possible to control the fan rotation speed without options by voltage,
as well as by thyristor controllers.
The speed controller is purchased separately.
Warning! When adjusting the voltage, make sure there is no unusual noise
or vibration at reduced motor speed.
The motor current may exceed the rated current during voltage regulation.
The fan is equipped with a thermal switch with no self-reset.
To reset the thermal relay:
- Switch off the power supply.
- Find and eliminate the cause of overheating.
- Make sure the motor has cooled down to operating temperature.
- Switch on the power supply.
The TT Silent-M … T fan starts operation when the control voltage is
applied to the LT input terminal by an external switch (e.g. switching on the
room light).
After the control voltage is off, the fan continues to operate within the set
time period adjustable from 2 to 30 minutes by the timer.
To adjust the fan turn-on delay time, turn the control knob T clockwise to
increase and counter-clockwise to decrease the turn-on delay time
respectively.
Warning! The timer circuit is under mains voltage. Make adjustments only after disconnecting the fan from power mains. The fan is supplied with a special plastic screwdriver for adjusting the fan settings. Use it if you want to change the fan turnoff delay time or the humidity threshold. Using a metal screwdriver, knife, etc. for adjustment may damage the electronics board.
The TT Silent-M … U/U1/U2(n) fan is equipped with an electronic module TSC (speed controller with an electronic thermostat) for automatic motor speed (air flow) control depending on the air temperature.
The terminal compartment incorporates 2 control knobs:
- presetting the speed
- setting the threshold for the electronic thermostat
The thermostat operation indicator is located on the fan cover. It lights up
when the air temperature exceeds the set value.
To set the thermostat threshold, turn the temperature knob clockwise to
increase the value and counter-clockwise to decrease the value. To set the fan
speed (air flow), rotate the speed control knob in the same way.
The fan operating logic may be based on temperature or timer indications:
TT Silent-M … U(n): The fan switches to the maximum speed as the room air
temperature exceeds the set point. As the air temperature drops 2 °C below the
set point or if the initial temperature is below the set point, the fan
operates with the set speed.
TT Silent-M … U1(n): The fan switches to the maximum speed as the room air temperature exceeds the set point. As the air temperature drops down below the set point, the timer starts a 5-minute countdown and then the fan switches to the set speed.
TT Silent-M … U2(n): The fan switches to the set speed as the room air temperature exceeds the set point. As the air temperature drops 2 °C below the set point or if the initial temperature is below the set point, the fan is turned off.
The TT Silent-M … P fan is equipped with a speed controller that enables switching the fan on/off and smooth speed (air flow) regulation from minimum to maximum value.
TECHNICAL MAINTENANCE
The fan maintenance periodicity is at least once per 6 months.
Maintenance steps:
Disconnect the fan from power supply and make sure electricity has been turned off. Disconnect an air duct on both sides of the fan.
| Clean the fan with a soft dry cloth or a brush.
---|---
Wipe the fan surfaces dry.
| Connect an air duct on both sides of the fan. Supply power to the fan.
CAUTION! Do not allow water or liquid come into contact with electric components!
TROUBLESHOOTING
Problem
| Possible reasons| Troubleshooting
---|---|---
When the unit is connected to power mains, the fan does not rotate and does
not respond to any controls.| No power supply.|
Make sure the power supply line is connected correctly, otherwise troubleshoot the connection error.
Internal connection fault.
| Contact the Seller.
Low air flow.| The ventilation system is clogged.|
Clean the ventilation system.
Increased noise, vibration.
| The impeller is clogged.| Clean the impeller.
The fan is not secured well or is not mounted properly.|
Troubleshoot the installation error.
The ventilation system is clogged.
|
Clean the ventilation system.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +5 °C to + 40 °C and relative humidity up to 70 %.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage
guidelines and electromagnetic compatibility. We hereby declare that the
product complies with the provisions of Electromagnetic Compatibility (EMC)
Directive 2014/30/ EU of the European Parliament and of the Council, Low
Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the
Council and CE-marking Council Directive 93/68/EEC. This certificate is issued
following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months
after the retail sale date provided the user’s observance of the
transportation, storage, installation, and operation regulations. Should any
malfunctions occur in the course of the unit operation through the
Manufacturer’s fault during the guaranteed period of operation, the user is
entitled to get all the faults eliminated by the manufacturer by means of
warranty repair at the factory free of charge. The warranty repair includes
work specific to elimination of faults in the unit operation to ensure its
intended use by the user within the guaranteed period of operation. The faults
are eliminated by means of replacement or repair of the unit components or a
specific part of such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE- FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP.
Quality Inspector’s Stamp
Sold by
(name and stamp of the seller)
Manufacture Date
Purchase Date
100
125 T
150 V
TT Silent-M 160 P 1 n
200 U 2
250 R
315
220 V/60 Hz
Τηλ: 211 – 70.55.500 & 210 – 21.30.051, Fax: 210 – 22.23.283
V97EN-05
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>