Display Type Pressure Sensors
PSAN Series
INSTRUCTION MANUAL
TCD210185AB
PSAN Series Display Type Pressure Sensors
Thank you for choosing our Autonics product.
Read and understand the instruction manual and manual thoroughly before using
the product.
For your safety, read and follow the below safety considerations before using.
For your safety, read and follow the considerations written in the instruction
manual, other manuals and Autonics website.
Keep this instruction manual in a place where you can find easily.
The specifications, dimensions, etc are subject to change without notice for
product improvement Some models may be discontinued without notice.
Follow Autonics website for the latest information.
Safety Considerations
- Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
- symbol indicates caution due to special circumstances in which hazards may occur.
Warning Failure to follow instructions may result in serious injury or death
-
Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
Failure to follow this instruction may result in personal injury, economic loss or fire. -
Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct sunlight, radiant heat, vibration, impact, or salinity may be present.
Failure to follow this instruction may result in explosion or fire. -
Install on a device panel or to a pressure port directly to use.
Failure to follow this instruction may result in fire. -
Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in fire. -
Check ‘Connections’ before wiring.
Failure to follow this instruction may result in fire. -
Do not disassemble or modify the unit.
Failure to follow this instruction may result in fire or electric shock.
Caution Failure to follow instructions may result in injury or product damage
-
Use the unit within the rated specifications.
Failure to follow this instruction may result in fire or product damage. -
Use a dry cloth to clean the unit, and do not use water or organic solvent.
Failure to follow this instruction may result in fire. -
This product is designed to detect the pressure of noncorrosive medium. Do not use for corrosive medium.
Failure to follow this instruction may result in product damage. -
Keep the product away from metal chip, dust, and wire residue which flow into the unit.
Failure to follow this instruction may result in fire or product damage.
Cautions during Use
- Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected accidents.
- 12 – 24 VDC ****power supply should be insulated and limited voltage/current or Class 2, SELV power supply device.
- Use the product, 3 sec after supplying power.
- When using switching mode power supply, frame ground (F.G.) terminal of power supply should be grounded.
- Wire as short as possible and keep away from high voltage lines or power lines, to prevent inductive noise.
- This unit may be used in the following environments.
– Indoors (in the environment condition rated in ‘Specifications’)
– Altitude max 2,000 m
– Pollution degree 3
– Installation category II
Ordering Information
This is only for reference, the actual product does not support all combinations. For selecting the specified model, follow the Autonics website.
-
Medium / Port fitting position
No mark: Pneumatic type (gas) / Back
D: Pneumatic type (gas) / Bottom
B: Fluid type (liquid, gas) / Back
L: Fluid type (liquid, gas) / Bottom -
Pressure type and Range
| Pressure| Rated range
---|---|---
01| Static| 0.0 to 100.0 kPa
1| 0 to 1,000 kPa
V01| Negative| 0.0 to -101.3 kPa
C01| Compound| -101.3 to 100.0 kPa -
Wiring
No mark: Cable type (fluid type)
C: Connector type -
Control output
No mark: NPN open collector output
P: PNP open collector output -
Option input / output
V: Voltage output
A: Current output
H: External input -
Pressure port
Medium Port| Pneumatic| Fluid
---|---|---
R1/8| ○| ○
Rc1/8| ○| –
NPT1/8| ○| ○
7/16- 20UNF| –| ○
9/16- 18UNF| –| ○
Product Components
- Product
- Instruction manual
- Unit sticker
- Connector type: Bracket A / B, Connector wiring (PSO-C01)
- Cable type: Bracket C
Sold Separately
- Front cover (PSO-P01), Panel bracket (PSO-B02/B03)
- Pneumatic type: M5 gender (PSO-Z01)
Unit Descriptions
-
Pressure range (sticker)
-
Display part (red)
Run mode: Displays PV (present value), SV (setting value)
Setting mode: Displays parameter and setting value -
Output indicator (OUT1: red , OUT2: green)
Turns ON when the corresponding control output is ON. -
[M] key
Enters parameter group, selects item and returns run mode. -
[▼] , [▲] key
Sets preset of output operation mode, runs the mode or changes parameter.
Connections
Color | Function |
---|---|
Brown | +V |
Blue | 0 V |
Black | OUT 1 |
White | OUT 2 |
Orange | Option input / output |
NPN open collector output
PNP open collector output
- ①: Option voltage / current output model, ②: Option external input model
- OCP (over current protection circuit)
- There is no short circuit protection circuit. Do not connect directly to power or capacitive loads.
- The control output is abnormal when the control output circuit is shorted or over current is supplied.
- Pay attention to the input impedance of the connected device when using analog voltage output. Be sure to the voltage drop due to the resistance of the wiring when extending the wiring.
Dimensions
- Unit: mm, For the detailed drawings, follow the Autonics website.
Pneumatic type, back port, connector type
Pneumatic type, bottom port, connector type
Fluid type, bottom port, connector type
Fluid type, back port, cable type
Installation
One-touch fitting
Pneumatic type | Fluid type |
---|---|
Connect the metal part with a spanner so that no large force is applied to the
unit body. (tightening torque: ≤ 10 N m, it may cause malfunction.)
Bracket
Use spring washers and hexagon wrench bolts (tightening torque: ≤ 3 N m) to
select and install a bracket suitable for your environment.
Connector type | Cable type |
---|---|
• Bracket A | • Bracket B |
Wiring
- Do not pull the wiring with a force of more than 30 N.
Specifications
Model| PSAN- □V01C□□- □| PSAN- □01C□□- □|
PSAN-□1□□□- □| PSAN- □C01□□□- □
---|---|---|---|---
Pressure Type| Pneumatic type model: Gauge pressure Fluid type
model: Gauge pressure 01) or sealed gauge pressure 02)
Pressure| Negative| Static| Compound
Min display unit| 0.1 kPa| 0.1 kPa| 1 kPa| 0.1 kPa
Rated pressure range| 0.0 to -101.3 kPa| 0.0 to 100.0 kPa| 0 to
1,000 kPa| -101.3 to 100.0 kPa
Display & **setting pressure range| 5.0 to -101.3 kPa|
-5.0 to 110.0 kPa| -101.3 to 1,100 kPa| -101.3 to 110.0 kPa
Display type| 7 Segment LED, 4 ½ digit
Display accuracy| -10 to 0 ℃: ≤ ±1% F.S., 0 to 50 ℃: ≤ ±0.5% F.S.
Max. pressure**| Rated pressure ×2| Rated pressure ×2| • Pneumatic
type: Rated pressure ×1.5
• Fluid type: Rated pressure ×2| Rated pressure ×2
- Only for static pressure, rated pressure range 100.0 kPa model
- The unit is sealed structure. It is based on atmospheric pressure 101.3 kPa.
Applicable medium| Pneumatic type (air, non-
corrosive gas)| Fluid type (non-corrosive gas and
fluid that do not corrode stainless steel
316L)
---|---|---
Connection type| Connector type| Cable type / connector type
Cable| Ø 4 mm, 5-core, 2 m| Connector type: Ø 4 mm, 5-core, 2 m Cable
type: Ø 4 mm, 5-core, 3 m
Wire spec.| AWG24 (0.08 mm, 40-core), insulator diameter: Ø 1 mm
Material| Front case: PC Back case: (back port) PC / (bottom port)
PBT+GF15%
Pressure port: Brass-nickel plated| Front case: PC Back case: PA6
Pressure port: SUS304/SUS316L
Protection structure| Connector type: IP40 (IEC standard)| Connector
type: IP40 (IEC standard) Cable type: IP65 (IEC standard)
Approval|
Unit weight (packaged)| Back port: ≈ 80 g (≈ 165 g) Bottom port:
≈ 85 g (≈ 170 g)| Connector type: ≈ 88 g (≈ 173 g) Cable type: ≈ 90 g (≈ 167
g)
Power supply| 12 – 24 VDC **(ripple P-P: ≤ 10%)
---|---
Allowable voltage range| 90 to 110% of rated voltage
Current consumption| ≤ 50 mA 01)
Control output| NPN open collector output / PNP open collector
output model
Load voltage| ≤ 30 VDC **
Load current| ≤ 100 mA
Residual voltage| NPN: ≤ 1 VDC , PNP: ≤ 2 VDC
Hysteresis| According to output operation mode 02)
Repeat error| ±0.2% F.S. ±min display interval
Response time| 2.5, 5, 100, 500, 1000 ms
Protection circuit| Output short over-current protection circuit
Insulation resistance| ≥ 50 MΩ (500 VDC **megger)
Dielectric strength| 1,000 VAC **50 / 60 Hz for 1 min
Vibration| 1.5 mm amplitude at frequency of 10 to 55Hz (for 1 min) in
each X, Y, Z direction for 2 hours
Ambient temperature| -10 to 50 ℃, Storage: -20 to 60 ℃ (no freezing
or condensation)
Ambient humidity| 30 to 80%RH, Storage: 30 to 80%RH (no freezing or
condensation)
- Current output: ≤ 75 mA
- Refer to ‘Output operation mode’. ±1digit error may occur due to pressure unit operation.
Analog output| Voltage (1 – 5 VDCᜡ ±2%
F.S)| Current (DC 4 – 20mA ±2% F.S)
---|---|---
Output impedance| 1 kΩ| –
Linearity| ≤ ±1% F.S| ≤ ±1% F.S
Zero-point| ≤ 1 VDC ±2% F.S.| ≤ DC 4 mA ±2% F.S.
Span| ≤ 4 VDC ±2% F.S.| ≤ DC 16 mA ±2% F.S.
Resolution| 1/1000 or 1/2000 (different by pressure type and display unit)
Response time| 50 ms| 70 ms
Minimum Display Interval
Pressure | Negative | Static | Compound |
---|---|---|---|
Min display interval | 0.1 kPa | 0.1 kPa | **1 |
kPa** | 0.1 kPa |
Resolution
Display unit
| 1/1000| 1/2000| 1/1000| 1/2000| 1/1000|
1/2000| 1/1000| 1/2000
MPa| –| –| 0.001| –| 0.001| –| –| –
kPa| 0.1| –| 0.1| –| 1| –| –| 0.1
kgf/cm 2| 0.001| –| 0.001| –| 0.01| –| –| 0.001
bar| 0.001| –| 0.001| –| 0.01| –| –| 0.001
psi| –| 0.01| –| 0.01| –| 0.1| –| 0.02
mmHg| –| 0.4| | –| 0.8
inHg| –| 0.02| –| 0.03
01) mmH 2O| 0.1| –| –| 0.1
Mode Setting
- Max. / Min. pressure value is available to check by monitoring.
[Option external input model] Auto shift judgment level checking / setting is available when P-9 External input terminal is set as SHFT. (no input displays
Parameter Setting
- Some parameter are activated / deactivated depending on other parameters. Refer to the description.
- The setting item name and setting value are cross-displayed on the display part.
- It returns to RUN mode when there is no additional key input for 60 sec in each parameter group.
- Guaranteed write life: 100,000 times
- [M] key: Saves setting value and moves to next parameter [▼], [▲] key: Selects setting value
Parameter | Display | Default | Setting range |
---|---|---|---|
P-1 | Display unit |
bar, psi, mmHg, inHg, H2O: mmH O2
| [Static pressure model] MPa, kPa, KGC: kgf/cm2, bar, psi
P-2| OUT operation mode| | | HYS.M: Hysteresis
WIN: Window comparison output
HY-W: Hysteresis-Window comparison output AUTO: Auto sensitivity setting
F.OUT: Forced output control
P-3| Output type| | | | OUT1| OUT2|
1O2O| Normally open| Normally open
1O2C| Normally closed| Normally open
1C2O| Normally closed| Normally open
1C2C| Normally closed| Normally closed
P-4| Response time| | | 2.5, 5.0, 100, 500, 1,000 ms
P-5| Voltage low limit scale| | | [Option voltage output model] Min. rated
pressure ≤ Low limit scale ≤ 90% of rated pressure
P-6| Voltage high limit scale| | | [Option voltage output model] Low limit
scale setting value + 10% of rated pressure ≤ High limit scale ≤ Max. rated
pressure
P-7| Current low limit scale| | | [Option current output model] Min. rated
pressure ≤ Low limit scale ≤ 90% of rated pressure
P-8| Current high limit scale| | | [Option current output model] Low limit
scale setting value +10% of rated pressure ≤ High limit scale ≤ Max. rated
pressure
P-9| External input terminal| | | [Option external input model] HOLD: Hold
SHFT: Auto shift
P-10| Auto shift output 01)| | | [Option external input model] OUT1, OUT2, ALL
P-11| Lock| | | LOC1: Parameter, preset, zero-point adjustment setting lock /
Monitoring value reset lock
LOC2: Parameter lock (available to check setting value) OFF
- Condition: P-9. External input terminal SHFT setting
Preset Setting
Setting method
- Setting name and value are cross-displayed in SV display part.
1. Set the operation mode in P-2 OUT operation mode.
2. Enter the preset setting mode by pressing [M] key from RUN mode.
3. Select the setting item by [M] key and change the preset by [▼] or [▲] key.
4. Press [M] key to save setting or no key input over 60 sec not to save setting and return to RUN mode. (except forced output control mode)
Preset setting by operation mode
Operation mode | Preset | Setting range |
---|---|---|
Hysteresis | Pressure detection level 1 |
display
pressure
Hysteresis level 1| | Min. display pressure ≤ HYS1 < ST1
Pressure detection level 2| | Min. display pressure < ST2 ≤ Max. display
pressure
Hysteresis level 2| | Min. display pressure ≤ HYS2 < ST2
Window comparison output 01)| | Pressure detection low limit 1| | Min. display
pressure ≤ LO-1 ≤ Max. display pressure -(3 × Min display interval)
Pressure detection high limit 1| | LO-1 + (3 × Min display interval) ≤ HI-1 ≤
Max. display pressure
Pressure detection low limit 2| | Min. display pressure ≤ LO-2 ≤ Max. display
pressure – (3 × Min display interval)
Pressure detection high limit 2| | LO-2 + (3 × Min display interval) ≤ HI-2 ≤
Max. display pressure
Hysteresis- Window comparison output 02)| | Pressure detection level 1| | Min.
display pressure < ST1 ≤ Max. display pressure
Hysteresis level 1| | Min. display pressure ≤ HYS1 < ST1
Pressure detection low limit| | Min. display pressure ≤ LOW ≤ Max. display
pressure – (3 × Min display interval)
Pressure detection high limit| | Low + (3 × Min display interval) ≤ HIGH ≤
Max. display pressure
Auto sensitivity setting| | Pressure level 1| | Min. display pressure ≤ ST1 ≤
Max. display pressure – 1% of rated pressure
Pressure level 2 03)| | ST1 + 1% of rated pressure ≤ ST2 ≤ Max. display
pressure
Pressure detection level| | Auto setting SET=
• Manual setting is possible by [▼] or [▲] key.
Forced output control 04)| | –| –| • Manual ON/OFF for OUT1/2 is possible by
[▼] or [▲] key.
- Hysteresis: 1 (min display interval, fixed)
- ST1 = HYS1, actual hysteresis is 1 (min. display interval)
- When error appears, check setting conditions and set proper setting values.
- [Option external input model] Forced output does not support external input terminal.
■ Precaution
- The preset value (default) of the changed operation mode is set when changing P-2 OUT operation mode setting.
- Preset value is converted as the changed unit automatically when changing P-1 Display unit setting.
- Preset is reset when changing P-9 External input terminal setting.
■ Default setting value
Operation mode| Preset| Negative| Static|
Compound
---|---|---|---|---
0.1 kPa| 0.1 kPa| 1 kPa| 0.1 kPa
Hysteresis| | | -50.0| 50.0| 500| 50.0
| 0.0| 0.0| 0| -50.0
| -50.0| 50.0| 500| 50.0
| 0.0| 0.0| 0| -50.0
Window comparison output| | | 0.0| 0.0| 0| -50.0
| -50.0| 50.0| 500| 50.0
| 0.0| 0.0| 0| -50.0
| -50.0| 50.0| 500| 50.0
Hysteresis- Window comparison output| | | -50.0| 50.0| 500| 50.0
| 0.0| 0.0| 0| -50.0
| 0.0| 0.0| 500| -50.0
| -50.0| 50.0| 0| 50.0
Auto sensitivity setting| | | 0.0| 0.0| 0| -50.0
| -50.0| 50.0| 500| 50.0
| -25.0| 25.0| 250| 0.0
Forced output control| | –
Output Operation Mode
Change the output operation mode to change pressure detection method.
■ Hysteresis
- Set the hysteresis for pressure detection directly.
- Setting: Pressure detection level (ST1, ST2), Hysteresis (HYS1, HYS2)
Hysteresis – Window comparison output
- It is available both hysteresis mode and window comparison output mode operations.
- Setting: Pressure detection level (ST1), Hysteresis (HYS1), High limit (HIGH), Low limit (LOW)
Forced output control
- It displays the present pressure with forcibly holding comparing output OFF regardless of setting value.
- Manual ON/OFF for OUT1/2 is possible by [M], [▼] or [▲] key during forced output control operation.
Window comparison output
- It detects pressure at the desired range.
- Hysteresis is fixed as min. display interval.
- Setting: High limit (HI1, HI2), Low limit (LO1, LO2)
Auto sensitivity setting
- This function is to set the proper position (SET) automatically by applied pressure from two positions (ST1, ST2). SET=
- Hysteresis is fixed as min. display interval.
Auto shift Preset Setting
Setting method [Parameter setting]
- Select P-9 External input terminal: SHFT.
- Press the [▲] key for over 3 sec. in RUN mode to enter Max / Min monitoring / Auto shift menu.
- Press the [M] key to entering Auto shift setting and press the [▼] or [▲] key to change preset.
- When reset the set correction value, press the [▼] + [▲] keys for over 1 sec .
[External input setting]
- At the desired preset value pressure, maintain low level for over 1 ms of Auto shift input (orange).
- The pressure at this time is measured and applied after 7.5 ms and is stored in the auto shift correction value.
Operation mode | Preset | Default | Selling range |
---|---|---|---|
Auto- shift | Auto-shift | ||
correction | Min. preset | ||
Pressure | Setting range | ||
(after correction) | Setting range |
(preset range)
Negavive| -101.3 to 5.0 kPa| -101.3 to 101.3 kPa
Static| -5.0 to 110.0 kPa| -110.0 to 110.0 kPa
-50.0 to 1100 kPa| -1100 to 1100 kPa
Compound| -101.3 to 110.0 kPa| -101.3 to 110.0 kPa
Precaution
- Auto shift correction is reset as 0 when changing P-2 OUT operation mode and preset value.
- Preset setting range is wider than the rated pressure with the source pressure fluctuations.
- In case of forced output control mode or PV HHHH/LLLL, Auto shift function does not operate.
Error
Display | Cause | Troubleshooting |
---|---|---|
When external pressure is input while adjusting zero point. | Try again |
after removing external pressure.
| When overload is applied on control output| Remove overload.
| When ‘ST1’, ‘ST2’ setting range is not met in auto sensitivity setting
mode.| Check setting conditions and set proper setting values.
| When applied pressure exceeds high-limit of display pressure range.| Apply
pressure within display pressure range.
| When applied pressure exceeds low-limit of display pressure range.
| Auto shift correction error.| Set the corrected setting value within setting
pressure range.