Features

  • Screw type connection for stable and reliable connection
  • Contactless relay ideal for systems requiring long life-cycle and high-speed response
  • Compact, space-saving design
  • Comprehensive connection type for use without jumper bar
  • Operation status indicator (blue LED)
  • DIN rail mount and screw mount installation
  • Convenient SSR removal with ejector clip
  • SSR protection cover

※ Autonics CH/CO series I/O terminal block cables are recommended for best performance.

Safety Considerations

  • Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
  • symbol indicates caution due to special circumstances in which hazards may occur.

Warning Failure to follow instructions may result in serious injury or death.

  1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss.(e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
    Failure to follow this instruction may result in personal injury, economic loss or fire.

  2. Do not use the unit in the place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present.
    Failure to follow this instruction may result in explosion or fire.

  3. Do not connect, repair, or inspect the unit, remove connector, or change SSR while connected to a power source.
    Failure to follow this instruction may result in fire or electric shock.

  4. Do not disassemble or modify the unit.
    Failure to follow this instruction may result in fire or electric shock.

Caution Failure to follow instructions may result in injury or product damage.

  1. Use the unit within the rated specifications.
    Failure to follow this instruction may result in fire or product damage.

  2. Use a dry cloth to clean the unit, and do not use water or organic solvent.
    Failure to follow this instruction may result in fire or electric shock.

  3. Keep the product away from metal chip, dust, and wire residue which flow into the unit.
    Failure to follow this instruction may result in fire or product damage.

  4. Do not use the product when a screw of terminal is loosened.
    Failure to follow this instruction may result in fire or product damage.

Cautions during Use

  • Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected accidents.

  • Check the polarity of power or COMMON before connecting PLC or other controllers.

  • Do not touch the unit immediately after the load power is supplied or cut.
    It may cause burn by high temperature.

  • 24VDC power supply should be insulated and limited voltage/current or Class 2, SELV power supply device.

  • Wire as short as possible and keep away from high voltage lines or power lines, to prevent surge and inductive noise. Do not use near the equipment which generates strong magnetic force or high frequency noise (transceiver, etc.). In case installing the product near the equipment which generates strong surge (motor, welding machine, etc.), use diode or varistor to remove surge.

  • This unit may be used in the following environments.

    • Indoors (in the environment condition rated in ‘Specifications’)
    • Altitude max. 2,000 m
    • Pollution degree 2
    • Installation category II

Product Components

  • Product
  • Instruction manual
  • Ejector

Sold Separately

  • I/O cable CH/CO Series

Ordering Information

This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website.

  1. Connector type
    H : Hirose connector

  2. Wire connection
    C : Common

  3. The number of SSR
    16: 16-point
    32: 32-point

  4. SSR type
    MP0 : AQZ202D [Panasonic]

  5. Input logic
    N : NPN (+COM)
    P : PNP (-COM)

  6. Varistor
    N : None
    Ordering Information

Specifications

Model ASS-HC16MP0-□N ASS-HC32MP0-□N
Applied SSR 01) AQZ202D [Panasonic]
Output method 1a 1a
Power supply ≤ 24 VDC ±10 % ≤ 24 VDC ±10 %
Current consumption ≤ 10.4 mA 02) or ≤ 13.1 mA 03) ≤ 11.5 mA 02) or ≤

15.3 mA 03)
SSR output rated spec.| 24 VAC∼50/60 Hz 1.6A, 24 VDC 1.6A

(1.6 A / 1-point, 8 A / 1COM)

| 24 VAC∼50/60 Hz 1.6A, 24 VDC 1.6A

(1.6 A / 1-point, 8 A / 1COM)

No. of connector pins| 20| 40
Connector for controller side| 20-pin Omron (XG4A-2031)| 40-pin Hirose

(HIF3BA-40PA-2.54DSA)

No. of SSR points| 16| 32
Output connection| 8-point/1COM| 8-point/1COM
Terminal type| Screw| Screw
Terminal pitch| 7.62 mm| 7.62 mm
Indicator| Power indicator: red, operating indicator: blue| Power indicator: red, operating indicator: blue
Varistor| None| None
Input logic| NPN / PNP model| NPN / PNP model
Material| CASE, BASE, COVER: PC,

terminal pin: brass, Ni-plating

| CASE: MPPO, BASE: PA66 (G25%),

COVER: PC, terminal pin: brass, Ni-plating

Approval| Symbol| Symbol
Unit weight (packaged)| ≈ 185 g (≈ 232 g)| ≈ 370 g (≈ 463 g)

  1. For the detailed information about the SSR, please refer to ‘SSR’ or data sheet from the manufacturer.
  2. It is current consumption per a SSR including LED current.
  3. It is current consumption including LED current for power part to 02).
Insulation resistance ≥ 1,000 MΩ (500 VDC megger)
Dielectric strength (coil-contact) 2,500 VAC∼50/60 Hz for 1 minute
Dielectric strength (same polarity contact) 1,000 VAC∼

50/60 Hz for 1 minute
Vibration| 0.75mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction for 2 hours
Vibration (malfunction)| 0.75mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction for 10 min
Shock| 300 m/s² (≈ 30 G) in each X, Y, Z direction for 3 times
Shock (malfunction)| 150 m/s² (≈ 15 G) in each X, Y, Z direction for 3 times
Ambient temperature| -15 to 55 ℃, storage: -25 to 65 ℃ (no freezing or condensation)
Ambient humidity| 35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation)
Applicable wire – solid| Ø 0.3 to Ø 1.2 mm
---|---
Applicable wire – stranded| AWG 22-16 (0.30 to 1.25 mm²)
Tightening torque| 0.5 to 0.6 N·m

Crimp Terminal Specifications

  • Unit: mm, Use the UL approved crimp terminal.
    Crimp Terminal Specifications

Replacing SSR

  1. Disassemble a SSR by using Two Way Ejector for SSR replacement inside the product.
    Replacing SSR

  2. After checking the location of the SSR socket, insert the SSR to be replaced.
    Replacing SSR

Dimensions

  • Unit: mm, For the detailed drawings, follow the Autonics website.
    Dimensions

Installation

DIN Rail

  • Mounting

    1. Pull the Rail lock on the rear of the product to the direction ①.
    2. Hang DIN rail hook on the rear of the product onto DIN rail.
    3. Push the product to the direction ②, and push the Rail lock to the direction ③ to fix onto the DIN rail.
      DIN Rail
  • Removing

    1. Insert a tool such as screwdriver into the hole of Rail lock.
    2. Push the tool to the direction ① and pull the Rail lock.
    3. Lift bottom of the product to the direction ② and remove the product from DIN rail.

Panel
Product with the mounting hole can be installed on panel with screw.
It is recommended to use M4×15 mm of spring washer screws.
If you use flat washer, its diameter should be Ø 6 mm.
Tighten the screw with the tightening torque of 0.7 to 1.0 N·m.

Example

  • When two or more terminal blocks are installed
    : Use a stopper (sold separately) to make space between devices.
    Example

Temperature Characteristic Graph

  • Load current by ambient temperature for each rated current
    Temperature Characteristic Graph
    VIN: 24 VDC

  • VIN is input voltage

Wire Connection

Wire connection

  • 16-point NPN
    Wire connection

  • 16-point PNP
    Wire connection A| Pin| 20| 18| 16| 14| 12| 10| 8| 6| 19| 17| 15| 13| 11| 9| 7| 5
    ---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
    COM| COM| COM1| COM2
    B| Upper terminal| –| 01| –| 03| –| 05| –| 07| 08| –| 0A| –| 0C| –| 0E| –
    –| R2| –| R4| –| R6| –| R8| R9| –| R11| –| R13| –| R15| –
    C| Low terminal| 00| –| 02| –| 04| –| 06| –| –| 09| –| 0B| –| 0D| –| 0F
    R1| –| R3| –| R5| –| R7| –| –| R10| –| R12| –| R14| –| R16

  • 32-point NPN
    Wire connection

  • 32-point PNP
    Wire connection A| Pin| 40| 38| 36| 34| 32| 30| 28| 26| 24| 22| 20| 18| 16| 14| 12| 10
    ---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
    COM| COM| COM1| COM2
    B| Upper terminal| –| 01| –| 03| –| 05| –| 07| 08| –| 0A| –| 0C| –| 0E| –
    –| R2| –| R4| –| R6| –| R8| R9| –| R11| –| R13| –| R15| –
    C| Low terminal| 00| –| 02| –| 04| –| 06| –| –| 09| –| 0B| –| 0D| –| 0F
    R1| –| R3| –| R5| –| R7| –| –| R10| –| R12| –| R14| –| R16
    A| Pin| 39| 37| 35| 33| 31| 29| 27| 25| 23| 21| 19| 17| 15| 13| 11| 9
    ---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
    COM| COM| COM3| COM4
    B| Upper terminal| –| 11| –| 13| –| 15| –| 17| 18| –| 1A| –| 1C| –| 1E| –
    –| R18| –| R20| –| R22| –| R24| R25| –| R27| –| R29| –| R31| –
    C| Low terminal| 10| –| 12| –| 14| –| 16| –| –| 19| –| 1B| –| 1D| –| 1F
    R17| –| R19| –| R21| –| R23| –| –| R26| –| R28| –| R30| –| R32

Hirose connector pin arrangement

  • 20-pin connector
    Omron (XG4A-2031)

  • 40-pin connector
    Hirose (HIF3BA-40PA-2.54DSA)

SSR AQZ202D [Panasonic]

Input

Rated voltage| Operate voltage| Release voltage| Input impedance
---|---|---|---
30 VDC | ≥ 4 V| ≤ 1.3 V| –

Output

Manufacture Panasonic

Contact

arrangement

| SPST-1a (N.O)
Load voltage range| 60 VAC∼ / DC (Peak)
Max. load current| ≤ 2.7 A
Min. load current| –
Non-repetitive surge

current

| 9 A (Peak)
Output OFF leakage

current

| 10 μA
Output ON on voltage| –
Insulation resistance| ≥ 1,000 MΩ (500 VDC megger)
Dielectric strength (contact-coil)| 2,500 VAC∼ 50/60 Hz for 1 minute
Operate time| ≤ 10 ms
Release time| ≤ 3 ms
Ambient temperature| -40 to 60 ℃, storage: -40 to 100 ℃ (a non freezing or condensation environment)

Dimensions

  • unit: mm
    Dimensions

  • Circuit diagram (bottom view)

  • PCB pattern

It was written based on the data provided by each manufacturer, but there is room for change, so be sure to check the manufacturer’s data.

CUSTOMER SUPPORT

18, Bansong-ro 513Beon-gil, Haeundae-gu, Busan, Republic of Korea, 48002
www.autonics.com | +82-2-2048-1577 | [email protected]Symbol

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Autonics User Manuals

Related Manuals