SENECA T203PM100-MU Energy Power Meters Instruction Manual
- June 12, 2024
- SENECA
Table of Contents
INSTALLATION MANUAL
T203PM100-MU
T203PM300-MU
T203PM600-MU
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol **indicates conditions or
actions that put the user’s safety at risk.
The word ATTENTION preceded by the symbol **indicates conditions or
actions that might damage the instrument or the connected equipment. The
warranty shall become null and void in the event of improper use or tampering
with the module or devices supplied by the manufacturer as necessary for its
correct operation, and if the instructions contained in this manual are not
followed.
**| WARNING:** The full content of this manual must be read before any
operation. The module must only be used by qualified electricians. Specific
documentation is available via QR-CODE shown on page 1.
---|---
| The module must be repaired and damaged parts replaced by the Manufacturer.
The product is sensitive to electrostatic discharges. Take appropriate
measures during any operation.
| Electrical and electronic waste disposal (applicable in the European Union
and other countries with recycling).
The symbol on the product or its packaging shows the product must be
surrendered to a collection centre authorized to recycle electrical and
electronic waste.
This document is the property of SENECA srl. Copies and reproduction are
prohibited unless authorised.
The content of this document corresponds to the described products and
technologies.
Stated data may be modified or supplemented for technical and/or sales
purposes.
MI00562-3-EN
INSTALLATION MANUAL
MODULE LAYOUT
Dimensions LxHxD 95 x 75 x 35 mm; Weight: ≈ 150 g; Enclosure: PA6, black
SIGNALS VIA LED ON FRONT PANEL
LED | STATUS | LED meaning |
---|---|---|
PWR/COM Green | ON | The device is powered correctly |
PWR/COM Green | Flashing | Communication via RS485 port |
D-OUT Yellow | ON | Digital output activated |
ASSEMBLY
The device can be mounted in any position, in compliance with the expected
environmental conditions.
CAUTION
Magnetic fields of considerable magnitude can alter the measurement: avoid
proximity to permanent magnetic fields, solenoids or ferrous masses which
induce strong alterations of the magnetic field; possibly, if the zero error
is greater than the declared error, try a different arrangement or change
orientation.
USB PORT
The front USB port allows easy connection to configure the device using the
configuration software. If it is necessary to restore the initial
configuration of the instrument, use the configuration software.
Through the USB port it is possible to update the firmware (for further
information please refer to the Easy Setup 2 software).
To restore communication on the RS485 port, the cable must be physically
disconnected from the USB port.
CAUTION
Check that the device in question is included in the list of products
supported by the Easy Setup APP in the store.
When the USB port is connected to a cable, communication on the RS485 port is
blocked.
TECHNICAL SPECIFICATIONS
CERTIFICATIONS|
https://www.seneca.it/products/t203pm100-mu/doc/CE_declaration
---|---
INSULATION| Using an insulated conductor. its sheath determines the insulation
voltage. An insulation of 3 kVac is guaranteed on bare conductors.
ENVIRONMENTAL CONDITIONS| Temperature: -25 + +65 °C
Humidity. 10% + 90% non condensing.
Altitude: Up to 2000 m above sea level
Storage temperature: -30 + +85°C
Degree of protection: IP20.
ASSEMBLY| 35mm DIN rail IEC EN60715, suspended with ties
CONNECTIONS| Removable 6-way screw terminals, 5 mm pitch for cable up to 2.5
rnm1 micro US8
POWER SUPPLY| Vottage: on Vic and GND terminals, 11 + 28 Vdc Absorption:
Typical: < 70 mA (/ 24 Vdc
COMMUNICATION
PORT| RS4.85 serial port on terminal Nock with ModBUS protocol (see user
manual)
INPUT| Type of measurement ACOC TRMS or DC Bipolar Live: 1000Vdc; 290Vac
Crest factor 100A =1.7 ;300A= 1.9 ;600A= 1.9 Pass-band: 1.4 kHz
Overload: 3 x IN continuous
CAPACITY| =DC True MS| TRMS DC Bipolar (DIP7MDN)
T203PM600-MU| 0 – 600A / 0 – 290Vac| -600 – +600A / 0 – +1000Vdc
7203PM300•MU| 0 – 300A/ 0 – 290Vac| -300 – +300A 1 0 – +1000Vdc
T203P11100-MU| 0 – 100A I 0 – 290Vac| -100 – +100A / 0 – +1000Vdc
ANALOGUE OUTPUT| Type: 0 -10 Vdc, minimum load Rith, =2 kn.
Protection: Reverse polarity protection and over voltage prceedion
Resolution: 13.5 full scale AC
EMI error < 1 %
The type of output can be selected via software
DIGITAL OUTPUT| Type: active. 0 – Vcc, maximum load 50mA
The type of output can be selected via software
ACCURACY| below 3% of full scale| 1% of ful scale at 50160 Hz, 23°C
above 3% of full scale| 0,5% of full scale at 50160 Hz, 23°C
Coetlic. Temperature: < 200 ppmrC
Hysteresis on measurement 0.3% of full scale
Response speed: 500 ms (DC); 1 s (AC) at 99.5%
OVERVOLTAGE CATEGORIES| Bare conductor. CAT. III 600V
Insulated conductorOAT.III lkV
ELECTRICAL CONNECTIONS
WARNING
Disconnect the high voltage before carrying out any work on the instrument.
CAUTION
Switch off the module before connecting the inputs and outputs.
To meet electromagnetic immunity requirements:
– use properly insulated and dimensioned cables;
– use shielded cables for signals;
– connect the shield to a preferred instrumentation ground;
– Keep shielded cables away from other cables used for power installations
(transformers, inverters, motors, etc.).
POWER SUPPLY| ANALOGUE OUTPUT| DIGITAL OUTPUT| RS485|
MEASUREMENT INPUT
---|---|---|---|---
| | | |
CAUTION
Make sure that the direction of the current flowing through the cable is that
shown in the figure (incoming).
To increase the sensitivity of the current measurement, insert the cable
several times into the central hole of the instrument, creating a series of
loops.
The current measurement sensitivity is proportional to the number of cable
passages through the hole.
CONTACT INFORMATION
Technical support| support@seneca.it| Product
information| sales@seneca.it
---|---|---|---
www.seneca.it/products/t203pm300-mu
DOCUMENTATION
SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY;
Tel. +39.049.8705359 –
Fax +39.049.8706287
MI00562-3-EN
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>