Danfoss FCM 106 Drive Motor Instruction Manual

June 1, 2024
Danfoss

Danfoss FCM 106 Drive Motor

Danfoss-FCM-106-Drive-Motor-product

Specifications

  • Model: MI03L302
  • Power Supply: 3×400 V
  • Power Range: Minimum 4 kW (5.36 hp)

Installation Instructions

Follow the steps below for proper installation:

  1. Stop the motor.
  2. Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies.
  3. Wait for the capacitors to discharge fully before performing any service or repair work.

Connection to FCP 106 or FCM 106

  1. Connect the LOP as shown in Table 1.2 and Illustration 1.3.
  2. Cut off or isolate excess wire after completing connections.
  3. Connect terminal 27 to +24 V or follow parameter settings for Terminal 27 Digital Input.

Set-up

  1. Perform set-up according to Table 1.3.
  2. Use the [+]/[-] keys to set reference.
  3. To set up permanent start mode, connect terminal 12 to terminal 18 and do not connect purple/orange/gray wire to terminal 18.

Function
Select the modes of operation as per the settings provided in Table 1.3.

FAQ

Q: What should I do if the warning LED indicator lights are off?
A: Even when the warning LED indicator lights are off, wait for the specified time after power has been removed before performing any service or repair work to ensure safety.

Installation Instructions

LOP Connection and Set-up
VLT® DriveMotor FCP/FCM 106

Items Supplied

  • Local operating panel (LOP), 175N0128 IP65, see Illustration 1.1.
  • Fixture for LOP, 175N2717 (included in 175N0128), see Illustration 1.2.
  • LOP cable.

Danfoss-FCM-106-Drive-Motor- \(2\)

Safety Instructions

Refer to VLT® DriveMotor FCP 106 and FCM 106 Operating Guide for detailed information about safety precautions for installation.

WARNING

DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. High voltage can be present even when the warning LED indicator lights are off. Failure to wait the specified time after power has been removed before performing service or repair work can result in death or serious injury.

  1. Stop the motor.
  2. Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
  3. Wait for the capacitors to discharge fully, before performing any service or repair work. The waiting time is specified in Table 1.1.

Voltage [V]| Power range 1) [kW (hp)]| Minimum waiting time

(minutes)

---|---|---
3×400| 0.55–7.5 (0.75–10)| 4

Table 1.1 Discharge Time

  1.  Power ratings relate to NO, see VLT® DriveMotor FCP 106 and FCM 106 Operating Guide.

Connection to FCP 106 or FCM 106

  1. Connect the LOP as shown in Table 1.2 and Illustration 1.3.
  2. After completing connections, cut off or isolate excess wire.
  3. Connect terminal 27 to +24 V or set parameter 5-12 Terminal 27 Digital Input to [0] No operation or [1] Reset, see footnote 2 in Table 1.3.

Terminal| Dual-speed

operation

| Dual-mode

operation

| Dual-direction

operation

---|---|---|---
18| Purple or orange| Gray
27| Brown
29| Green
12| Red
50| Yellow
53| White
55| Blue        __

Table 1.2 Electrical Connections

Danfoss-FCM-106-Drive-Motor- \(1\)

Set-up

  1. Perform set-up according to Table 1.3.
  2. Use the [+]/[-] keys to set reference.
  3. At power-up, the unit is always in stop mode. The set reference is stored during power down. To set up permanent start mode, connect terminal 12 to terminal 18 and do not connect purple/orange/gray wire to terminal 18. Permanent start mode disables the stop function on the LOP.

Function| Settings| Key I (Start)| Key II (Start)|

Key (Stop)

---|---|---|---|---
Default – Dual speed operation

(connect purple or orange wire)

| No changes to factory setting.| Run on set

reference (+/-)

| Run on 5 Hz1)

jog speed

| Stop (and reset2)

– if trip)

Function 2 – Dual-mode operation

(connect purple or orange wire)

| Select the modes of operation in set-ups 1 and 2.   Set parameter 0-10 Active Set-up to [9] Multi Set-up.

Set parameter 5-13 Terminal 29 Digital Input to [23] Set-up

select bit 0.

| Run with set-up 1| Run with set-up 2| Stop (and reset2)

– if trip)

Function 3 – Dual direction operation (connect gray wire)| Set parameter 4-10 Motor Speed Direction to [2] Both directions.

Set parameter 5-13 Terminal 29 Digital Input to [11] Start

reversing.

| Run forward| Run reverse| Stop (and reset2)

– if trip)

Table 1.3 LOP Operating Mode

  1. Set jog speed in parameter 3-11 Jog Speed [Hz].
  2. When reset is required, set parameter 5-12 Terminal 27 Digital Input to [1] Reset.

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.