Danfoss FCM 106 VLT Drive Motor Instruction Manual

June 1, 2024
Danfoss

**Danfoss FCM 106 VLT Drive Motor Instruction Manual

**

Installation Instructions

Introduction

The instructions provide information about the replacement of memory module (ordering number: 134B0791).
A memory module is a component that stores motor and pump data, as well as rmware and parameter settings of a frequency converter. If a frequency converter malfunctions, the motor and pump data, rmware, and parameter settings on this frequency converter can be copied to new frequency converters of the same power sizes. Doing this saves the time for setting up the frequency converters for the same applications.

A memory module is pre-installed on the frequency converter.
The data and parameter settings on a memory module are encoded les that are protected from direct viewing.

To access les in a memory module, or transfer les between a memory module and a PC, a memory module programmer is required. It is not included in this package and needs to be ordered separately (ordering number: 134B0792).
Memory Module Programmer

1 Memory module
2 Status indicator light
3 Socket for memory module
4 Memory module programmer
5 USB Type-B receptacle

Illustration 1.1 Memory Module and Memory Module Programmer

Items Supplied

Ordering number Items supplied
134B0791 Memory module

Safety Instructions

Only qualied personnel is allowed to install or operate this equipment. Qualied personnel is dened as trained sta, who are authorised to install, commission, and maintain equipment, systems and circuits in accordance with pertinent laws and regulations. Additionally, the personnel must be familiar with the instructions and safety measures described in the operating instructions.

WARNING

DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. High voltage can be present even when the warning LED indicator lights are o. Failure to wait the specied time after power has been removed before performing service or repair work can result in death or serious injury.

  • Stop the motor.
  • Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DClink connections to other frequency converters.
  • Disconnect or lock PM motor.
  • Wait for the capacitors to discharge fully. The minimum duration of waiting time is specied in Table 1.1.
  • Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.

Table 1.1 Discharge Time

Voltage [V]| Power range [kW (hp)]| Minimum waiting time (minutes)
---|---|---
380–480| 0.55–7.5 (0.75–10)| 4

Memory Module Replacement

Tools required

  • Tor x 20 screwdriver

Complete the following steps to replace the memory module:

  1. Stop the motor and the frequency converter, and wait for the capacitors to discharge completely. The discharge time is specied in Table 1.1.
  2. Remove the front cover. Refer to the operating instructions for instructions of removing the front cover.
  3. Remove the memory module from the frequency converter, as shown in Illustration 1.2.
  4. If applicable, transfer les to the new memory module. Refer to the Memory Module Programmer Installation Instructions for details.
  5. Install the new memory module.
  6. Mount the front cover. Refer to the operating instructions for instructions of mounting the front cover.
  7. When the frequency converter powers up, the data on the memory module is downloaded to the frequency converter and takes eect.

Illustration 1.2 Remove the Memory Module from the Frequency Converter

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals