greenworks TBMS-MCS60060 Gwu Greene System Installation Guide
- June 1, 2024
- Greenworks
Table of Contents
TBMS-MCS60060 Gwu Greene System
“`html
Product Information
Specifications:
-
Brand: GWU-GreenE SYSTEM
-
Manufacturer: Greenworks North America, LLC
-
Address: 500 South Main Street, Suite 450 Mooresville, NC
28115 -
Contact: Tel: 1-888-909.6757, E-mail:
PowerHub@greenworkspower.com -
Model Number: 320102087402
-
Certification: UL
Product Usage Instructions:
Packing List:
When unpacking your GWU-GreenE SYSTEM, ensure you have all the
following items:
- Inverter X1
- Mental cover X1
- Bracket X1
- Self-tapping screw X12
Installation Guide:
- Attach the mental cover to protect the inverter.
- Fix the bracket using the provided self-tapping screws and
expansion bolts.
BMS (TBMS-MCS60060):
The BMS is essential for guiding the installation and
maintenance of your battery module.
Accessories for Both Floor and Wall Mounting:
The separate accessory box contains items like base support,
transverse plate, screws, and washers for mounting purposes.
Frequently Asked Questions (FAQ):
Q: Can I mount the battery module on both floors and
walls?
A: Yes, the accessories provided allow for mounting on both
concrete and wooden walls as well as floors.
“`
QUICK INSTALLATION GUIDE
GWU-GreenE SYSTEM
Greenworks North America, LLC
Add: 500 South Main Street, Suite 450 Mooresville, NC 28115 Tel:
1-888-909.6757 E-mail: PowerHub@greenworkspower.com
320102087402
UL
Copyright Declaration
The copyright of this manual belongs to Greenworks North America, LLC. Any
corporation or individual should not plagiarize, partially or fully copy
(including software, etc.), and no reproduction or distribution of it in any
form or by any means. All rights reserved. Greenworks North America, LLC
reserves the right of final interpretation.
www.greenworkstools.com
1. Packing List
· Packing list of inverter
Packing list
A
D
B
E
F
I
G
H
J K
C
L
M
N
O
P
Q R
Item Name
A Inverter X1
B Mental cover X1
C Bracket X1 D Self-tapping screwX12 E Expansion boltX12 F WasherX12 G M5X10
screwX10 H Grounding terminalX5 I PE cableX1 J 8 AWG ferrules X3 K 10 AWG
ferrules X6 L DocumentsX3 M Circuit breakerX1 N Communication dongleX1
(Optional) O Cable protective guardX1
P Fixing plate of coverX2
Q
8-pin female terminal block with terminating resistorX1
R M4X10 screwX2
Description
Product Protect the inverter Support the inverter Fix the bracket Fix the
bracket Fix the bracket Fix the cover, cable protective guard and cover fixing
plate For grounding Grounding cable between inverter and BMS For AC cable For
PV cable User manual, installation guide and quick installation guide Mount it
on the BI For communication
Protect the cable between inverter and BMS Connect the cover and the bracket
Additional 8-pin female terminal block with terminating resistor
Fix the fixing plate between inverter bracket and BMS 1
Packing List
· Packing list of battery
BMS (TBMS-MCS60060)
A
B
Item A B
Name and Quantity BMS User ManualX1
One Battery Module (TP-HS50×1):
Description Product Guide the installation and maintenance
B
C
D
E
F
A
G
H
I
Item Name and Quantity
A Battery moduleX1 B BracketX2 C Expansion boltX4 D Expansion boltX2 E
WasherX2 F Fixing plate (3 holes)X2 G Fixing plate (2 holes)X2 H M5*10 cross
screwX10 I Quick Installation GuideX1
Description
Product Support battery module to be mounted on the wall Fix the bracket Fix
the bracket Fix the bracket Connect two battery modules with bracket Connect
two battery modules Fix the fixing plate Guide the installation
NOTE! The above-mentioned accessories are only for one battery module.
2
Packing list
Accessories for Both Floor and Wall Mounting (Separate Accessory Box)
A
B
C
D
E
F
G
H
Item Name and Quantity
A Base supportX2 B Transverse plateX1 C Expansion screwX6 D M58 countersunk
screwX4 E M520 countersunk screwX6 F Adjustment screwX2 G Self-tapping
screwX6 H WasherX6
Description Support the base Support the base Fix the base support in case of concrete wall Fix the transverse plate with base support Fix the two sides of base Adjust the base to be leveled Fix the base support in case of wooden wall Fix the base support in case of wooden wall
Base for Battery:
Item /
Name and Quantity Base
Description Product
3
Packing List
· Packing list of BI
A
B
C
D
E
F
K
G H
I
J
L
Item Name and Quantity
Description
A Backup intefaceX1
Product
B BracketX1
Support the BI to be mounted on the wall
C Expansion boltX5
Four for fixing the bracket and one for fixing the BI
D Self-tapping screwX5
Four for fixing the bracket and one for fixing the BI
E WasherX5
Four for fixing the bracket and one for fixing the BI
F 551323.7mm Copper barX4 For parallel connection with inverter
G M4*12 cross screwX1
Fix the circuit breaker
H M5*12 cross screwX8
Fix the part when parallel connection with inverter
I 40137.9mm Copper barX4 For parallel connection with inverter
J Communication cableX1
Communicate with inverter
K Cable tieX5
Fix the cable
L Punching reference paperX1 For hole location
4
2. Overview of Terminals
· Terminals and breaker of inverter
Overview of Terminals
5
6 4
2 1 7
3
Inverter power terminal (Purchased by customer)
No. Terminals 1 PV terminals 2 AC terminals
Type 90°C(194°F), 600 V, copper 90°C(194°F), 600 V, copper
3
Ground terminals 90°C(194°F), 600 V, copper
Cross-sectional Area Range Strip Length
10-8 AWG
0.47 in / 12 mm
12-8 AWG (3.8KW), 10-8 AWG (5/6/7.6KW)
0.47 in / 12 mm
8 AWG
0.47 in / 12 mm
Inverter communication terminal (Purchased by customer)
No. Terminals
Port Pin Pin 1: RS485_METER_A Pin 2: RS485_METER_B
Type Range
CAT5 or better
Strip
Length
Torque (in-lbs)
4 AUX terminal
Pin 3: GND Pin 4: +12V_RELAY_OUT Pin 5: DRM0
24-18 AWG 0.24 in / 6 mm 1.8
Pin 6: +12V_COM
Pin 7: STOP_NO+ Pin 8: STOP_NO-
5
Overview of Terminals
Inverter communication terminal (Purchased by customer)
No. Terminals
Port Pin Pin 1: SYSR_L
Type Range
Strip Length
Torque (in-lbs)
Pin 2: SYSR_H
5
COMM in terminal
Pin 3: CAN_L Pin 4: CAN_H Pin 5: RS485_BI_A
CAT5 or better
24-18 AWG
0.24 in / 6 mm 1.8
Pin 6: RS485_BI_B
Pin 7: +12V Pin 8: GND
18-16 AWG
Pin 1: SYSR_L
Pin 2: SYSR_H
6
COMM out terminal
Pin 3: CAN_L Pin 4: CAN_H Pin 5: RS485_BI_A
CAT5 or better
24-18 AWG
0.24 in / 6 mm 1.8
Pin 6: RS485_BI_B
Pin 7: +12V Pin 8: GND
18-16 AWG
7
MLPE terminal Pin 1: GND
Pin 2: RS485_MLPE_A
CAT5 or better
24-18 AWG
0.24 in / 6 mm
1.8
Pin 3: RS485_MLPE_B
Inverter breaker and switch
No. Component Description
1
AC Breaker
3.8 KW: Noark # B1N2C20: 20 A Circuit Breaker; 2-Pole, 240 V, 10 kAIC 5 KW: Noark # B1N2C30: 30 A Circuit Breaker; 2-Pole, 240 V, 10 kAIC 6 KW: Noark # B1N2C35: 35 A Circuit Breaker; 2-Pole, 240 V, 10 kAIC 7.6 KW: Noark # B1N2C40: 40 A Circuit Breaker; 2-Pole, 240 V, 10k AIC
Source
Can be purchased from the manufacturer
2
Emergency stop switch
Normally closed (NC) contact The UL certification is required for the emergency stop switch.
Purchase by customer
6
· Terminals breaker of battery
COMM
DIP
terminal
BMS DIP
GND
Overview of Terminals
BAT+
BAT-
POWER
BAT+
Power button
BAT-
Right side view
Circuit breaker Left side view
7
Overview of Terminals
· Terminals breaker of BI
13
20 21 22
19
14
16 17 18
15
1
8
2
4
7
3
5 6
12
10
9
11
BI power terminal (Purchased by customer)
No. Terminals 1 INV terminals 2 GEN terminals
Cross-sectional Area Range 12-8 AWG (3.8 KW), 10-8 AWG (5/6/7.6 KW)
8-4 AWG
Strip Length 0.67 in / 17 mm 0.67 in / 17 mm
Torque (in-lbs) 30 /
3 Load terminals 4 Grid terminals 5 INV Neutral terminals 6 GEN Neutral terminals 7 Load Neutral terminals
3 AWG-4/0 AWG
3 AWG-4/0 AWG 12-8 AWG (3.8 KW), 10-8 AWG (5/6/7.6 KW) 8-4 AWG 3 AWG-4/0 AWG
1.25 in / 32 mm 275 1.25 in / 32 mm 275 0.79 in / 20 mm 275 0.79 in / 20 mm / 1.77 in / 45 mm 275
8 Main Neutral terminals 3 AWG-4/0 AWG
1.77 in / 45 mm 275
9 INV Ground terminals 8 AWG
0.79 in / 20 mm 30
10 GEN Ground terminals 11 Load Ground terminals
8-6 AWG 6-4 AWG
0.79 in / 20 mm 30 1.77 in / 45 mm 30
12 Main Ground terminals 6-4 AWG
1.77 in / 45 mm 30
- The type of BI power cable shall be 90°C(194°F), 600 V, copper.
8
Overview of Terminals
BI communication terminal (Purchased by customer)
No. Terminals Port Pin Pin 1: RESERVE
Type
Range
Strip Length
Torque (in-lbs)
Pin 2: RESERVE
Pin 3: CAN_L
INV
Pin 4: CAN_H
13 Communicatio
n terminal
Pin 5: RS485_BI_A
Pin 6: RS485_BI_B
CAT5 or better
24-18 AWG
0.24 in / 6 mm 1.8
Pin 7: +12 V Pin 8: GND Pin 1: DRY_GEN Pin 2: GEND_GEN
18-16 AWG 24-16 AWG
14
AUX1 terminal
Pin 3: RS485_RESERVE_A Pin 4: RS485_RESERVE_B Pin 5: RESERVE Pin 6: RESERVE
CAT5 or better
0.24 in / 6 mm 1.8
24-18 AWG
Pin 7: STOP_NO+
Pin 8: STOP_NO-
Pin 1: NO_1
Pin 2: COM_1
Pin 3: NC_1
Pin 4: NO_2 15 AUX2terminal
Pin 5: CON_2/3
24-16 AWG 0.24 in / 6 mm 1.8
Pin 6: NC_2
Pin 7: NO_3 Pin 8: NC_3 16 CT1 terminal Pin 1: CT1+ Pin 2: CT117 CT2 terminal Pin 1: CT2+ Pin 2: CT218 CT3 terminal Pin 1: CT3+ Pin 2: CT319 CT L1A terminal Pin 1: CT L1A+ Pin 2: CT L1A-
Shielded, twisted pair
/
Shielded, twisted pair
/
Shielded, twisted pair
/
Shielded, twisted pair
/
/
/
/
/
/
/
/
/
9
Overview of Terminals
No. Terminals
Port Pin
20 CT L1B terminal Pin 1: CT L1B+ Pin 2: CT L1B-
21 CT L2A terminal Pin 1: CT L2A+ Pin 2: CT L2A-
22 CT L2B terminal Pin 1: CT L2B+ Pin 2: CT L2B-
Type
Range
Shielded, twisted pair
/
Shielded, twisted pair
/
Shielded, twisted pair
/
Strip Length
Torque (in-lbs)
/
/
/
/
/
/
BI breaker and switch (Purchased by customer)
No. Component Description
Amps Part Number Description
100 CSR2100 Eaton # CSR2100: 100 A / 240 V, 25 kAIC, 2-Pole
125 CSR2125N Eaton # CSR2125N: 125 A / 240 V, 25 kAIC, 2-Pole
150 CSR2150N Eaton # CSR2150N: 150 A / 240 V, 25 kAIC, 2-Pole
175 CSR2175N Eaton # CSR2175N: 175 A / 240 V, 25 kAIC, 2-Pole
200 CSR2200N Eaton # CSR2200N: 200 A / 240 V, 25 kAIC, 2-Pole
100 BW2100 Eaton # BW2100: 100 A / 240 V, 10 kAIC, 2-Pole
125 BW2125 1 Grid breaker
150 BW2150
Eaton # BW2125: 125 A / 240 V, 10 kAIC, 2-Pole Eaton # BW2150: 150 A / 240 V, 10 kAIC, 2-Pole
175 BW2175 Eaton # BW2175: 175 A / 240 V, 10 kAIC, 2-Pole
200 BW2200 Eaton # BW2200: 200 A / 240 V, 10 kAIC, 2-Pole
100 BWH2100 Eaton # BWH2100: 100 A / 240 V, 25 kAIC, 2-Pole
125 BWH2125 Eaton # BWH2125: 125 A / 240 V, 25 kAIC, 2-Pole
150 BWH2150 Eaton # BWH2150: 150 A / 240 V, 25 kAIC, 2-Pole 175 BWH2175 Eaton
BWH2175: 175 A / 240 V, 25 kAIC, 2-Pole
200 BWH2200 Eaton # BWH2200: 200 A / 240 V, 25 kAIC, 2-Pole
2
Emergency Normally closed (NC) contact stop switch The UL certification is required for the emergency stop switch.
10
1863 mm 73.35 in 1408 mm 55.43 in 1563 mm 61.54 in 1108 mm 43.62 in
Mechanical Installation
3. Mechanical Installation (Floor-mounting)
· Weight and mounting height instructions
4 Batteries
844 mm 33.23 in
Inverter
BMS Battery
Battery
Battery
Battery Base Weight(lb/kg): 591/268
3 Batteries
844 mm 33.23 in
Inverter
BMS Battery
Battery
Battery Base Weight(lb/kg): 472/214
1263 mm 49.72 in
808 mm 31.81 in
2 Batteries
844 mm 33.23 in
Inverter
BMS Battery Battery Base Weight(lb/kg): 353/160
11
Mechanical Installation
· Mount the battery
Step 1 Mount the base
1
Step 2 Mount the battery module
Hand remove
1
Bottom view
Top view
2
M8*85 × 4
2
Marker Measuring tape
Mark
1.57 in 40 mm
1.57 in
40 mm
12 3
3
Mechanical Installation Hand remove
M5
8.8 lbf.in /
1.0 N·m
13
Mechanical Installation
4
Mark Attach screw but
not tighten
14 5
M5
8.8 lbf.in / 1.0 N·m
Mechanical Installation
Ø 0.39 in./10 mm for Wall Bracket
3.54 in 90°
/90 mm
CAUTION! Please re-mount the dust cover to the battery module before drilling
holes to avoid dust falling into the interface and do remember to remove the
dust cover again after the installation wall bracket completed.
6
32 in /812.8mm
7
15
Mechanical Installation
Mark
Attach screw but not tighten, and align the
hole location of battery Tapping Screw × 2 Washer × 2 Wall Bracket × 2
8
Let the Platen down
16 9
Mechanical Installation
Platen (3 holes) × 2 M5*10 Screw × 6
2.2-2.5 N·m
10
Mark
Let the Platen down
Tapping Screw × 2 Washer × 2
Wall Bracket × 2
11
17
Mechanical Installation
Step 3 Mount the BMS
Mechanical Installation
· Mount the inverter
Screw in the two M4 screws, adjust the bracket to be firmly attached on the
wall surface and tignen M4 screws
Hand remove
1
1
M5
8.8 lbf.in / 1.0 N·m
18 2
2
M4 4.4 lbf.in / 0.5 N·m
Round holes
19
Mechanical Installation
4 drill for wooden wall 10 drill for concrete wall
Depth: 2.16 in / 55 mm
CAUTION!
Remove the screws on the bracket and disassemble the bracket before drill
holes.
3
5
Mechanical Installation
10 mm 26.5 lbf.in / 3.0 N·m
20 4
For wooden wall, this step is not required
For solid concrete wall, this step is required
Back view
6
Front view
21
Mechanical Installation
7 22 8
M5 8.8 lbf.in / 1.0 N·m
9
Mechanical Installation
Inverter BMS
Dowel pins Pins holes
M5
8.8 lbf.in / 1.0 N·m
Left side view
Right side view
M5
8.8 lbf.in / 1.0 N·m
10
23
Mechanical Installation
· Mount the BI
16 in/406 mm
1 24 2
3
4 drill for wooden wall 10 drill for concrete wall
Depth: 2.16 in / 55 mm
4
Mechanical Installation
This step is not required in case of wooden wall.
10 mm 26.5 lbf.in / 3.0 N·m
25
Mechanical Installation
Hang the BI on the bracket
5
Secure the BI on the wall
26 6
10 mm
26.5 lbf.in / 3.0 N·m
· Drill a hole in the back (Not recommended)
Mechanical Installation
Corresponds to the holes below the perforated paper
1
Drill the hole with a hole cutter. Choose 1 inch or 2inch size (Metal chips must be cleaned after drilling)
2
27
Mechanical Installation
Lock nut, waterproof gasket(outside), conduit
NOTE! Prohibit the flow of water inside the tubing water into the machine! 3
28 4
The top of the nut and contact surface of the threads must be cleaned after
locking the nut, as well as the contact surface between the nut and the box.
TSE-382 waterproof adhesive or a similar performance glue.
NOTE! Drilling a hole in the wall is required before cutting a hole in the
rear. To guarantee easy installation of the conduit and sealing with the
chassis, the hole’s size must be greater than the conduit’s outside diameter.
Mechanical Installation
4. Mechanical Installation (Wall-mounting)
32 28
in/ in/
781112..28
mmmm
M5 17.7 lbf.in / 2.0 N·m
1
32 in/ 812.8 mm
Cylindrical plastic bubble spirit level
Ground
Note: The distance from the Base to the ground is decided according to the local regulations.
8 drill for wooden wall
12 drill for concrete wall
Depth:
Depth:
1.97 in/ 50 mm
3.54 in/ 90 mm
2
29
Mechanical Installation
32 in/ 812.8mm
Cylindrical plastic bubble spirit level
3
26.5 lbf.in / 3.0 N·m
x 4
x 4
For solid wood wall For concrete wall
M5
8.8 lbf.in / 1.0 N·m
The steps of mounting battery modules, BMS and inverter are same as the
floormounting’s. Please refer to Chapter 3. 30 4
Wiring Connection on the Inverter
5. Wiring Connection on the Inverter
· AC cable
ABC
128 AWG (for GWU-HYB 3.8 DH) 108 AWG (for GWU-HYB 5.0 DH / 6.0 DH / 7.6 TH)
A: L1 terminal B: L2 terminal
C: N terminal
0.47 in / 12 mm Wirings
· PV cable
AB C D E F
A,C and E: PV+ terminal B, D and F: PV- terminal
2 MPPTs(for GWU-HYB 3.8 DH / 5.0 DH / 6.0 DH) 3 MPPTs (for GWU-HYB 7.6 TH)
10-8 AWG 0.47 in / 12 mm
Wirings
31
Wiring Connection on the Inverter
· GND cable
for PV connection
for AC connection
8 AWG 0.47 in / 12 mm Wirings
32
· Communication cable
Wiring Connection on the Inverter
Inverter
Inverter
BI
120-Ohm terminating resistor
ON ACT
321 MLPE
Inverter
321 MLPE
Inverter
COMM IN 12345678
COMM OUT 12345678
AUX 12345678
COMM IN 12345678
COMM OUT 12345678
AUX 12345678
23 456
INV AUX1
12345678 12345678
BI
EPO
AUX2
12345678
CT1 CT2 CT3
33
Wiring Connection on the Inverter
Diagram for communication connection steps between inverters
Step 1
8-pin
Step 2 Strip Length 0.24 in / 6 mm
24-18 AWG 18-16 AWG
Conduit
Step 3
Step 4
Wiring Connection on the Inverter
Diagram for communication connection steps between inverter and BI
Step 1
Step 2
Strip Length 0.24in./6mm
8-pin
24-18 AWG 18-16 AWG
Conduit
Step 3
Step 4
Step 5
Step 5
1
8
1
8
On the side of the first inverter
34
On the side of the second inverter
Step 5
1
8
On the side of inverter
Step 5
1
8
On the side of BI
35
Wiring Connection between Inverter and Battery
6. Wiring Connection Between Inverter and Battery
· BAT+, BAT- and COMM cable
BAT+, BAT- and COMM cable originally connected on side of inverter.
BAT+ COMM BAT-
On the side of inverter
BAT+
COM BAT-
BMS DIP
BAT+
BATPOWER
36
On the side of battery
Wiring Connection between Inverter and Battery
Inverter Battery
Connection between inverter and battery · GND cable
M5
17.7 lbf.in / 2.0 N·m
8 AWG 0.47 in / 12 mm Wirings
For easier connection, please connect the grounding cable on the BMS first. 37
Wiring Connection on the BI
7. Wiring Connection on the BI
7.1 Connect Inverter Conductors to BI · AC cable
L1 L2 L1 L2 L1 L2 L1 L2
128 AWG(for GWU-HYB 3.8 DH) 108 AWG(for GWU-HYB 5.0 DH / 6.0 DH / 7.6 TH)
N bus GND bus
0.67 in / 17 mm Wirings
AC cable 8 AWG 0.79 in / 20 mm
Wirings GND cable
Wiring Connection on the BI
· Neutral-Ground Bonding Strap-factory installed Remove Neutral-Ground bonding
strap from BI if not installed as service equipment. Proper earth connection
and Neutral-Ground bonding strap is required for safe operation of the system
and for compliance with local code requirements.
Neutral-Ground bonding strap
N bus GND bus
38
39
Wiring Connection on the BI
7.2 Connect Generator and EPO Conductors to BI · AC cable of generator
L2 L1
8-4 AWG 0.67 in / 17 mm Wirings
AC cable 8-6 AWG 0.79 in / 20 mm
Wirings GND cable
Wiring Connection on the BI
· Communication cable of generator and EPO
Step 1
8-pin
Step 2
Strip Length 0.24 in / 6 mm
24-16 AWG 24-18 AWG
Generator EPO
Conduit
Step 3
Step 4
1
8
On the side of BI
40
41
Wiring Connection on the BI
7.3 Connect Load Conductors to BI
· AC cable
L1 L2 N
6-4 AWG 1.77 in / 45 mm Wirings
GND cable
4/0 AWG 1.25 in / 32 mm Wirings
AC cable
7.4 Connect Grid Conductors to BI
Before installing a main breaker
Wiring Connection on the BI N L1 L2
6-4 AWG 1.77 in / 45 mm Wirings
GND cable
4/0 AWG 1.25 in / 32 mm
Wirings AC cable
After installing a main breaker
N L2 L1
6-4 AWG 1.77 in / 45 mm
4/0 AWG 1.25 in / 32 mm
Wirings
Wirings
42
GND cable
AC cable
43
Wiring Connection on the BI
7.5 Connect CT to BI
A set of CTs (CT L1A , CT L2A,200A) has been built in the BI. In some
application scenarios ,it can measure both load and generation and there is no
need to connect external CTs.But in some application scenarios,such as
Partial-Home Backup solution,connecting external CTs (CT L1B , CT L2B) to
measure total current both load and generation is needed. In addition,if the
site includes solar equipment, a solar CT is placed after the solar inverter
to measure the solar output. CT L1A terminal and CT L1B terminal have been
connected in parallel on PCB. CT L1A and CT L1B are used to measure total
current both load and generation of the same phase L1. CT L2A terminal and CT
L2B terminal have been connected in parallel on PCB. CT L2A and CT L2B are
used to measure total current both load and generation of the same phase L2.
NOTE! For detailed information about how to configure external CT, please
refer to “BI CT configuration for GWU-GreenE”.
44
References