legrand BCS-WS-UM-LMCP-24811r5 DLM 8 Relay 010V Dimming Panel Instruction Manual

June 1, 2024
Legrand

legrand-logo

legrand BCS-WS-UM-LMCP-24811r5 DLM 8 Relay 010V Dimming Panel

legrand-BCS-WS-UM-LMCP-24811r5-DLM-8-Relay-010V-Dimming-Panel-
image

Specifications

  • Input voltage: 115/277V, 120/347V, 240V Single Phase, 50/60 Hz
  • For 0-10V models:

Product Information

The Relay Panel Interiors Panel with Digital Lighting Management Support is designed for dimming or switching control of lighting and plug loads. The panels can be networked together to automate operations throughout a facility. The HDR panel relays respond to inputs from DLM switches, occupancy sensors, daylight sensors, input modules, and 0-10V outputs on dimming panel models. The panels provide native BACnet integration solutions via BACnet MS/TP or optional NB-ROUTER, BACnet/IP.

Usage Instructions

Load Control Arbitration

Ensure proper load control arbitration by setting up groups to control one or more relays in one or more panels. Groups allow for quick assignment of parameters to multiple loads. Be aware that group settings may override individual relay settings if programmed differently.

Occupancy Sensor Status

Monitor and manage occupancy sensor status to optimize energy efficiency and lighting control. Utilize the panel’s ability to provide occupancy sensor status as BACnet objects for comprehensive monitoring.

Connecting Multiple LMCP Panels in a Network

To expand control capabilities, connect multiple LMCP panels in a network without the need for a Network Controller or BAS. Utilize BACnet integration solutions for seamless network communication and automation.

FAQs

  • Q: Can DB9 cables be plugged in or unplugged without powering down the panel?
    • A: No, it is advised to power down the panel before plugging or unplugging DB9 cables to prevent any potential damage.

“`

No: 24811 ­ 07/23 rev. 5

Wattstopper ®
Relay Panel Interiors Panel with Digital Lighting Management Support
User Manual

Catalog Numbers · Les Numéros de Catalogue · Números de Catálogo: LMCP8-10V/LMCP24-10V/LMCP48-10V LMCP8/LMCP24/LMCP48
Country of Origin: Made in China · Pays d’origine: Fabriqué en Chine · País de origen: Hecho en China

SPECIFICATIONS

Input voltage …………….. 115/277V, 120/347V, 240V Single Phase, 50/60 Hz For 0-10V models:
Sinks up to 100 mA per 0-10V input (50 fixtures at 2mA each) 0-10V signal will open on loss of power to panel Class 2 connection to two independent DLM local networks 24VDC output ……………up to 250mA across 2 RJ45 ports per local network …………………………………………………………(A and B networks, 250 mA each) Free-topology DLM local network may include Digital Lighting Management (DLM) switches, occupancy sensors, daylight sensors, load controllers, and input modules. Category 5e cable, 150′ per device, up to 1,000 ft. total per local network Terminals for connection to DLM segment network (BACnet MS/TP) Segment network parameters Wattstopper LM-MSTP wire Linear topology, 4000 ft. maximum per segment Accessory power (jumper selectable) LMCP8/LMCP8-10V ………………………………………………………………….N/A LMCP24/LMCP24-10V ……………. 650 mA @ 15VDC, 400 mA @ 24VDC LMCP48/LMCP48-10V ……………. 650 mA @ 15VDC, 400 mA @ 24VDC ………………………….15VDC to power optional internal Network Controller ……………………………………………… 24VDC for Class 2 accessory devices HDR relays (used in both On/Off and 0­10V panels): Coil voltage, 24VDC, pulse ON and pulse OFF Mechanically latched contacts ½” K.O. mounting, LV plug-connection, individually replaceable HDR Heavy Duty Relay contact ratings: 30 A ballast ………………………………………………………………………. @ 277V 20 A ballast ………………………………………………………………………. @ 347V 16 A, E-Ballast ………………………………………………………………….. @ 120V 10 A, E-Ballast ………………………………………………………………….. @ 277V 20 A tungsten……………………………………………………………………. @ 120V 30 A resistive ……………………………………………………………………. @ 347V 20 A receptacle load ………………………………………………………….. @ 120V 1.5 HP……………………………………………………………………………… @ 120V SCCR (short circuit current rating) ……………………..14,000 A @ 347VAC Operating conditions: for indoor use only …………………………………………… 32­140° F (0­60° C) ……………………………………………………………. 5-95% RH, non-condensing Upon loss of power, date and time info is maintained for 14+ days. Programming info (including schedules) is maintained for the life of the product. UL and cUL listed (E207852). Listed for receptacle rated circuit control Complementary Listed to Emergency Lighting Equipment, UL924 OSHPD (OSP) Approved (Certification No: OSP-0257)
WARNING: The DB9 cables cannot be plugged in or unplugged without powering down the panel.
3

INTRODUCTION

The LMCP series panels are available for Dimming (LMCPx-10V) or Switching (LMCPx) control of lighting and plug loads. The panels can be networked together to enable automation through out an entire facility.

INTERIOR

ENCLOSURES

With LMCP panels, you can maintain code-compliant control of building exterior lighting as well as larger interior areas. Recommended applications include office building lobbies, corridors, loading docks, school gymnasiums, commons areas and hallways. LMCP panels are also ideal for retrofit scenarios where mounting control equipment near existing branch circuit breakers is beneficial, and digital switches, sensor devices, and load parameter configuration are required to meet complex operational sequences.

The HDR panel relays respond to inputs from Digital Lighting Management (DLM) switches, occupancy sensors, daylight sensors, input modules and 0-10V outputs on dimming panel models.

Multiple panels may be networked together for global control operation

without the use of a Network Controller or BAS. The LMCP panel also

provides a native-BACnet integration solution via BACnet MS/TP, or with

optional NB-ROUTER, BACnet/IP. Relay, group, and control device status,

including occupancy sensor status, are available as BACnet objects. When a

Figure 1: Panel interior and enclosures

Wattstopper Network Controller is used, it will automatically recognize LMCP

panels and map them to the browser-based user interface so that they can be configured with minimal additional setup.

Features and Basic Terminology

Groups A group allows you to control one or more relays in one or more panels. Groups provide an easy way to assign parameters quickly to multiple loads.
Each group has seven parameters that will determine the behavior of the relay. In a typical application each relay in a group will be set to the same parameters, so that lighting in multiple areas, controlled by different panels can all be set to follow the same schedules and behavior. However, it is also possible to program a relay in a group to different behavior, if needed. So, for example, if a relay controls a hallway or corridor that needs a different time delay before turning off, you can change the value for that relay while still having it follow all of the other behaviors of other relays in the group. A panel can store information for up to 99 groups, but when panels are networked together more groups are available. Each relay can belong to one or more of those groups. Groups are discussed in detail in the section “Groups, Scenes, Schedules, and Macros” on page 9.
NOTE: If a relay in a group has been programmed to different behavior, it is possible for the group settings to override the individual relay settings. See “Group Settings vs. Individual Relay Settings” on page 10 for details.
NOTE: If using the LMCP in conjunction with an LMSM-3E or LMSM-6E Segment Manager, it is important to understand that groups in the LMCP are separate from Segment Manager groups, which can only be accessed by the Segment Manager itself.

Channels A channel is a label for a BACnet data object. A BAS integrator sends messages to a channel to schedule After Hours (AH) and Normal Hours (NH). Channel is a binary value. Note that a value of “Active” sets the channel to AH while a value of “Inactive” sets it to NH.
Part of what a group does is to respond to scheduled events that determine when Normal Hours and After Hours begin. Because a channel message also determines Normal Hours and After Hours, it is important to understand the difference between groups and channels. As mentioned above, a panel has 99 memory locations for groups. But since panels can be connected, the total number of groups is much larger. Therefore a group number can be higher than 99, but it is still stored in one of the 99 slots. The channel number will correspond to the slot number where the group number is stored.
Groups 1-8 will always correspond to Channels 1-8. Above number 8, the group numbers are stored into the slots in the order they are created. So, for example, if group 52 is the first group that you program on a panel, it will be stored in memory location 9 and therefore, you would send a message on channel 9 to affect Normal Hours or After Hours for group 52.
NOTE: Assigning group numbers above 99 requires LMCS-100 software, and in the software, you will view the groups in the order they were created, so are able to determine the channel number.

Smartwire Smartwire provides a quick and easy way to assign loads (relays) to groups, using the buttons on the panel. When programming directly on the panel, Smartwire applies only to groups 1­8. However, if using the LMCT-100-2 to program the panel, you can use Smartwire with groups 1­99. See “Load Binding to Groups 1­8 (Smartwire)” on page 16 for details.

Push n’ Learn Push n’ Learn (PnL) is the method used to bind loads to sensors and switches, via button pushes. See “Push n’ Learn” on page 16 for details.

Schedules Schedules allow you to turn loads on or off at specific times. There are 254 schedules available per panel. A group can also respond to schedules sent from an LMSM Segment Manager or BACnet-enabled BAS. See “Schedules” on page 11 for details.

Dark/Light Dark/Light settings allow you to specify turning a group on or off based the amount of outside light. This can be done either with an astronomical schedule that calculates sunrise and sunset based on your latitude and longitude, or else based on an LMIO-301 photocell input module or LMIN-104 set to it’s photocell function. Up to 32 dark/light settings can be stored per panel. For details, see “Dark/Light Events” on page 12.
4

PANEL CIRCUIT BOARD LAYOUT AND CONNECTION
The LMCP contains two types of circuit boards: · The LMRD board is the relay control board. There are two different versions–one for LMCPx switching panels and one for LMCPx10V dimming panels (see Fig. 2a and 2b). A single board can control 12 relays. · The LMPI board is the main “Panel Intelligence” for the panel. It connects to the Local DLM network and to other panels or other BACnet devices (see Fig. 3a and 3b).
NOTE: The LMCP-8 contains a single LMRD board (only 8 of the 12 connections are used). The LMCP-24 contains two LMRD boards. The LMCP-48 has four LMRD boards, with 2 boards placed above and 2 boards placed below the LMPI.
The LMRD boards connect to the LMPI board other with DB9 cables. They must be connected as follows: · LMCP 8 ­ Use the top left(#1) DB9 jack. · LMCP 24 ­ Use the top left (#1) DB9 jack for the left LMRD board and the top right (#2) jack for the right LMRD board. · LMCP 48 ­ Use the top left (#1) DB9 jack for the top left LMRD board, the top right (#2) jack for the top right LMRD board, the bottom left (#3) jack for the bottom left LMRD board, and the bottom right (#4) jack for the bottom right LMRD board.
Power to the relays comes from the transformers through the LMPI and into the LMRD boards.
Figure 2a: LMCPx ­ Switching Panel LMRD Board

Relay Connection Header

Relay Status LEDs ­ The LED will be ON when the relay turns on, and OFF when the relay turns off. It will blink during the transition between Normal Hours and After Hours, for the amount of time specified with the Blink parameter. (If blink time is set to 0, it will not blink.) In Smartwire mode, the LED will BLINK on and off when relay is included in Group, and OFF when relay is excluded from
Group.
In PnL mode, the LED will be ON when relay is selected for
binding with buttons, and OFF when not selected.

Figure 2a: LMRD Circuit Board

Override Buttons and Status LEDs 1­6
Power Indication LED DB9 Jack ­ For connection to LMPI card 12/8 Jumper ­ For configuring whether the card drives 8 or 12 relays (jumpered by default in LMCP8 panels)
Service LED ­ Blinks once per second if there is proper communication between LMRD and LMPI boards. If you press and hold the button next to the LED, the LED will remain on instead of blinking.
Override Buttons and Status LEDs 7-12
Relay Override Buttons ­Toggle relay ON or OFF depending on the state of LED. In Smartwire mode, selects or deselects relay to be included into a Group. In PnL mode, selects relay to be bound to a DLM device.
Remote Override Terminal (available on switching LMRD boards only)
P: Pilot signal C: Pilot common S: Override signal C: Override common
5

Relay Connection Header

Figure 2b: LMCPx-10V ­ Dimming Panel LMRD Board
Override Buttons and Status LEDs

0-10V Connections Connect purple wire on “+” terminal, and pink wire on “-” terminal on the removable connector
+ ­

DB9 Jack ­ For connection to LMPI card

Service LED ­ Blinks once per second if there is proper communication between LMRD and LMPI boards. If you press and hold the button next to the LED, the LED will remain on instead of blinking.
6

The photo below shows the current version of the LMPI board. An older version of the board is shown on the following page.

Figure 3a: LMPI Circuit Board rev 7

Microcontoller activity indication LEDs (2 blue). The LEDs toggle every half second while the microcontroller is operating. They will both be on solid when AC power is lost and all power down data has been saved. They will stop blinking when Factory Defaults Request is happening, or when first powered from the factory, until all the data is initialized.

DIP Switches (see details below)

DB9 Connections to LMRD Cards
Reset Button ­ resets micro-controller chip and is similar to cycling power on and off

Micro USB Port ­ used for updating firmware
SD Card Slot ­ For future use

Room Bus Network Communication Activity LEDs ­ Light when communication is active on room bus A or B.

IR Interface ­ used for communication with LMCT-100

RJ-45 jacks for Connection to DLM Devices

Transformer Power Connector
Aux Power Jumper Selection

Aux Power Connector

SW2 ­ 511 ohm Bias Up SW3 ­ 511 ohm Pull down (behind MS/TP Connector)

LMRD Communication Activity LEDs ­ Light when communication occurs between one of the four LMRD cards.

SW4 ­ 120 ohm Termination Resistor (behind MS/TP Connector)

Group LEDs ­ Indicates the Group Buttons ­ Toggles Group 1 to 8

status for Group 1 to 8 for

when pressed and released. Also used to

loads in this panel only, where enter and exit Smartwire mode.

any member load ON indicates

ON, and all member loads

OFF indicates OFF. Blinks

during Smartwire mode.

MS/TP Connector ­ For connection to other panels – 3 connections available

Panel Config Button and LED

Dip Switches

The default for all dip switches is OFF.

1-4: Not currently used
5: OFF is used with HDR relays and provides a 20ms pulse. ON is used with RR-7 and RR-9 relays, and provides a 50ms pulse.
6: OFF routes unicast DLM Network messages internally. ON routes unicast DLM Network messages out the RJ-45 jacks. Set this to ON only if using an external diagnostic tool to view those messages. This will slow down DLM Network communications.
7: OFF turns the relay status LEDs on and off during PnL (but not the relays). ON turns both the relays and status LEDs on and off during PnL.
8: OFF=Relay status LEDs follow Pilot. ON=Relay status LEDs follow logic (for use with RR-7 relays, which have no pilot wires). 7

Differences between the rev 3 LMPI board and the rev 7 LMPI board: · The Pull Down, Pull, Up, and Termination Resistor are jumper plugs instead of dip switches. · There is no SD Card Slot (not currently used) · Microcontroller and LMRD Status LEDs silk screen labeling changed on rev 7 board · Group button silk screen labeling simplified on rev 7 board
Figure 3b: LMPI Circuit Board rev3

J11 ­ 511 ohm Pull Up

J12 ­ 511 ohm Pull down

J13 ­ 120 ohm Termination Resistor

Connecting Panels to Other DLM Devices, and Panels to Panels
There are two DLM local networks (labeled A & B) used to connect DLM devices such as switches, sensors, photocell input modules, and room controllers. The networks are labeled A and B. Each network has two RJ-45 jacks, for connecting Cat5 cable. Only LMRJ cable should be used. It is not important which jacks are used. For more details, see “Connecting Switches, Sensors, Photocells, and Other DLM Accessory Devices” on page 13.
Panels can also be connected to each other, using the MS/TP connectors and LM- MSTP wire.
NOTE: Do not connect panels together with Cat 5e cables.
Connecting Override Switches Directly to a Panel
Non-DLM switches can be connected directly to the non-dimming version of the LMCP, using the Remote Override Terminals next to the Relay Connection Headers. Only a 2 wire momentary switch, with or without a pilot light, can be connected. If both the pilot light and the momentary switch are part of the same device, then it is likely that there will be a single “common” or “ground” signal; it can be wired to either of the terminals labeled C.

P: Pilot Signal C: Pilot common

Pilot Light 24VDC (max 5mA)

PC SC

S: Override Signal C: Override common

Momentary Push Button

NOTE: These connectors are only found on LMCPX switching panels, and not on the LMCPx-10V dimming panels.

Load Numbering

Load IDs are assigned on the panel based on the LMRD cards. Loads are numbered on a single card from top to bottom. With multiple cards, numbering continues from left to right, top, then bottom. So on an LMCP-48, loads are numbered as follows:

· Top Left Card ­ Loads 1­12

· Top Right Card ­ Loads 13­24

· Bottom Left Card ­ Loads 25­36

· Bottom Right Card ­ Loads 37­48

8

GROUPS, SCENES, SCHEDULES, AND MACROS

A group allows you to control one or more relays in one or more panels. Each group has seven parameters that will determine the normal hours/after hours behavior of the relay(s):

Parameter Blink
Time Delay NH Time Delay AH Transition AH > NH
Transition NH > AH Sensor NH
Sensor AH

Definition
Amount of minutes load stays ON, when a scheduled event occurs that switches the load OFF when transitioning from Normal Hours to After Hours. The relay will turn off and on once, then the Override LED for that relay will blink continuously for the time period. The LEDs for all switches bound to that group will also blink continuously. Pressing the button will keep the load ON and the time delay countdown will start. When the countdown reaches 0, the blink function re-occurs.
NOTE: Blink does not apply when transitioning from After Hours to Normal Hours.
Possible values are:
· None · 1­240 minutes · Use Load ­ If set to this value , each individual load will use the value of the same parameter found
under the Load Settings menu. · Reset to Load ­ This value is identical to “Use Load”.
If a load is commanded to turn ON when the schedule switches to Normal Hours, the load will automatically turn OFF after the time delay expires. If the load is turned on manually by a switch after the schedule switches to Normal Hours, the load will again automatically turn OFF after the time delay expires.
Possible values are the same as Blink. Default is “None”
Identical to Time Delay NH, but the behavior occurs when the schedule switches to After Hours. Works in conjunction with Blink.
Possible values are the same as Blink. Default is “120 minutes”.
Behavior of the relay when Normal Hours begins.
Possible values:
· 0­100% · LNZ ­ Returns to load to the last value that was not 0 (completely off) · Do Nothing ­ No change occur · LNZ Occupied ­ Returns to load to the last value that was not 0 (completely off) if the room has an
occupancy sensor and the sensor indicates the room is occupied. If the room is unoccupied or if there no sensor in the room, there is no change to the load. · Use Load ­ This uses the value for each individual load instead of a group value. Setting this value for individual loads is only possible if using LMCS-100 software. · Turn Off ­ Turns the load Off
Behavior of the relay when After Hours begins.
Possible values are the same as AH­>NH.
Determines how the relay responds to sensor input during Normal Hours. Possible values are:
· Nothing ­ Load does not respond to occupancy sensor · Off Only ­ Responds to sensor input when vacancy is detected but not when occupancy is detected · On Only ­ Responds to sensor input when occupancy is detected but not when vacancy is detected · On/Off ­ Responds to sensor input for both occupancy and vacancy detection · Off Only Internal ­ Responds to vacancy commands only. Instead of using the default value of one
minute for the blink warn feature, the sensor will use the amount of time entered in the Blink parameter. · On Only Internal ­ The load responds only to Occupancy commands and once the load is on, it will
not shut off for the length of time entered in the Time Delay NH parameter. Instead of using the default value of one minute for the blink warn feature, the sensor will use the amount of time entered in the Blink parameter. · On/Off Internal ­ Responds to both occupancy and vacancy commands. Instead of using the default value of one minute for the blink warn feature, the sensor will use the amount of time entered in the Blink parameter. · Use Load ­ This uses the value for each individual load instead of a group value. Setting this value for individual loads is only possible if using LMCS-100 software. NOTE: Keep in mind that this parameter determines whether the loads assigned to the group will respond
to sensor input. It does not determine whether the loads will turn on or off. That is set within the sensor programming (either on the sensor itself, or by using the LMCT-100-2 remote or LMCS-100 software).
Determines how the relay responds to sensor input during After Hours. Possible values same as above

NOTE: The start times for normal hours and after hours are determined by a Schedule. For details on Schedules, see “Schedules” on page 11.
9

A group can be set to one of six macros, which contain pre-defined values for each of the seven parameters. Or, you can customize the setting for your own specific needs. For details, see “Macros” on page 12.
Group Settings vs. Individual Relay Settings As was mentioned in the introduction, it is possible to assign different parameter values to one or more relays that are part of a group. Example: You want to assign all offices on a floor to a single channel, so you can schedule all lights to be manual on and off at 7:00 pm, with a one hour override. However, the owners want to have a two hour override for their own offices. So a group of all relays can be set up and scheduled to have a 1 hour override, but then the two individual relays for the owners office can be set to 2 hours. Without this feature, you would need two groups–one for the owners’ office and a second for the rest of the offices–and would have to schedule each group separately.
Programming Individual Relays and Overriding Them LMCS-100 software is required to program the individual loads (relays) separate from the group. (The LMCT-100-2 remote provides access to the Blink parameter but not the others). Under certain circumstances, the group settings will override the previously programmed settings for an individual load:
· LMCS-100 provides an option when loading group settings into the panel to override the individual settings. If you don’t select this option, the individual load settings remain.
· When using an LMCT-100-2 to send group information to the LMCP, the group settings will override the individual load settings. Therefore, you should not use the LMCT-100-2 to send group information if you have previously programmed individual settings.
If using the Smartwire functionality to add a load after groups have been programmed, the group parameters will be applied to the new load as follows:
· If all of the loads currently assigned to the group have the same parameter values, those values will be applied to the new load. · If one or more loads currently assigned to the group have different parameter values than the other loads in the group, no
parameter values will be applied to the new load. So if that load had been previously programmed, its values will remain. If no values were previously programmed, the default values will be applied.
Group Functionality
Group Numbers and Memory Locations Each panel has 99 memory locations for storing group parameters. Groups 1­8 can be set up and controlled by buttons on the LMPI board. Groups 1­99 can be accessed from the LMCT-100-2 wireless configuration tool or LMCS-100 software. If multiple panels are networked together, all loads from different panels that are assigned to the same group will respond to commands sent to that group. So, for example, you might have panels on three different floors and assign the relays controlling the corridors on each floor to the same group number. You can then control all corridors on those floors together. Even though each panel has only 99 memory locations for storing group information, it is possible to “rename” a group to a different number. There are a total of 65,534 group numbers available. In this way multiple panels can be networked together and allow both coordinated relay behavior (when the group numbers match between panels) and independent behavior (when the group numbers are unique to a panel). NOTE: LMCS-100 software or control via a BAS is required in order to set up and use group numbers higher than 99.
Group Status Indicators The LMCP provides an easy visual indication of the status of the group. For Groups 1­8, If any relay assigned to a specific group is ON, then the Group LED for that group will also be ON. So for example, if a group is controlling several different rooms, and an occupancy sensor in one room has turned on the lights for that room, the associated group button LED will be ON. Additionally, if a DLM switch is connected to a panel and programmed to control a multiple loads, then the LED for the button controlling those loads will be ON, if any relay connected to one of those loads in any networked panel is ON.
BACnet Control Groups also allow BACnet control of relays in multiple panels, as well as all DLM devices connected to those panels. The only panel-specific BACnet objects are Binary Value (BV) 201­299, for Channel Occupancy Control. Sending a value of TRUE to a channel BV will set the Group to Unoccupied, also referred to as After Hours operation. Sending a value of FALSE to a channel BV will set Group to Occupied, also referred to as Normal Hours operation. The reason that After Hours corresponds to True instead of False is that Normal Hours operation is the default state for a given channel. Therefore setting a group to After Hours requires activation (in essence, turning After Hours “on”). Since a panel only has 99 group memory locations, only 99 Channels are available. But as mentioned previously, groups can be renamed, so you have the ability to control up to 65,534 possible groups. NOTE: Object support for accessory devices connected to panels is described in Technical Bulletin TB-175, available at
http://www.wattstopper.com/resources/download-center/tech-bulletins- whitepapers.aspx. A group action (button press, etc.) will always broadcast across the network. Every panel that has a group configured with the target group number responds to the action. Group set up is a local function that is conducted at each panel location. For more details about BACnet, see “Connecting Multiple LMCP Panels in a Network” on page 33.
10

Occupancy Sensor Events for Groups
An occupancy sensor event determines how loads assigned to a group will respond, based on input from an occupancy sensor. You can program up to 99 events. A single event will be assigned to a group.
NOTE: If using multiple occupancy sensors, when programming with the LMCT-100, you should only assign ONE sensor input to a group. Assigning more than one sensor to a group will lead to inconsistent response (but you can assign different sensors to different groups). If you need to assign multiple sensors to a group, use the LMCS-100 software to program the actions. The LMCS software has additional capabilities for programming input from multiple sensors.
NOTE: Occupancy sensor events can be assigned to either a group or a scene. For details on scenes, see below.
For each group, there is an Occupancy parameter (triggered when the sensor detects occupancy) and a Vacant parameter (triggered when it detects vacancy). For group events, the available values for both occupancy and vacancy are:
· 0­100% ­ Load goes to the specific value selected · LNZ ­ Set the load to the last non-zero level. · Turn Off ­ This relinquishes the load–it doesn’t actually “turn off” the load. The loads will still wait for the sensor delay timers to
expire before turning off. If the Partial Off parameter on the Load Settings menu is a value other than 0, the load will go to that level. · Do Nothing ­ No change to the load.
· NH Ovrride ­ Set the load to Normal Hours. The value of the AH­>NH parameter for the group will be applied.
· AH Ovrride ­ Set the load to After Hours. The value of the NH­>AH parameter for the group will be applied. · Normal Hrs ­ Set the load to Normal Hours. All settings found on the Normal Hours tab within LMCS-100 for loads and sensors will
be applied. (These settings are only available if you are using LMCS-100 software.) · After Hrs ­ Set the load to After Hours. All settings found on the After Hours tab within LMCS-100 for loads and sensors will be
applied. (These settings are only available if you are using LMCS-100 software.)
Scenes
The LMCP also has the ability to control Scenes (but only on the panel’s Cat 5e local network). Scenes are similar to Groups in that they control group of loads but also provide the ability to fade between one value and another when the scene is changed. For a switching LMCP, if assigning relays within the LMCP to a scene, it will switch relays on or off, since no dimming is possible.
There are sixteen possible scenes per “room” (or in this case a panel). When a scene is activated (typically by assigning it to a switch), all loads assigned to that scene will respond. You can select which loads are included in the scene.
Scenes are normally assigned to a button switch (the LMSW-105 5-Button Switch is commonly used for this but any button can be set as a scene button).
Scenes can also be triggered by Occupancy Sensors and Dark/Light events. The load control is similar to that of Occupancy Sensors and Dark/Light events for groups, but for scene events, you determine whether to turn the scene On or Off.
NOTE: Even though Scene events are separate from Group events, in the LMCT-100-2, you access these events from the Group Occ Sensors and Group Dark/Light screens within the Group Setup menu
Schedules
You can schedule up to 254 date and time based events per panel. Each event is assigned to a group, and determines one action for the group. For each event, you specify the time the event occurs. You also specify the days of the week in which the event will occur. Additionally, you specify whether the event will occur on any day designated as a holiday.
The possible actions sent to the group include:

Schedule Type After Hours Normal Hours On Off Do Nothing

Action Description Transitions Groups to After Hours (unoccupied) state Transitions Groups to Normal Hours (occupied) state Turns group loads ON without changing the current occupancy status Turns group loads OFF without changing the current occupancy status No action

If panels are networked and multiple panels use the same group number to control relays in those panels, then any events scheduled in one panel will affect the other panels (since events are always assigned to a group number). By using different group numbers in different panels, you can limit which panels will respond to those scheduled events.
Assigning a Panel to be the Master Clock
Every LMCP has a clock in it, which allows you to set time and date for controlling schedule events and calculating sunrise and sunset for Dark/Light events. To set the clock, use the LMCT-100-2 hand held remote, LMCS-100 software, or BACnet Time Synchronization via a BAS.
Additionally, if you have more than one panel networked together, any panel can be set to be the master clock. It will periodically send out clock information to the other panels so that they remain synchronized. You can set how often the master sends the clock message. The advantage of having any panel act as a master is that if the master panel is taken off-line for any reason, any other panel can be easily set to be master and all panels will still remain in sync. (Note that if the original panel is put back on-line you will want to revert the replacement master or the original panel to back to being a slave, so that you don’t have two master clocks on the network.)
To assign a panel as the master, you need LMCS-100 software. For more information on LMCS-100, see “Programming the LMCP” on page 15.

11

Macros
A macro is a set of pre-defined values for the seven parameters that are part of a group. Each group can be set to a specific macro, or to use no macro and instead use a customized set of values. There are six macros in the LMCP. Following is a description of the intended use for each macro, followed by a list of all parameter values:
NOTE: If you want to set up custom parameters that are similar to one of the macros, select that macro first, then go into Custom mode and change only the value that different from the macro default.
· Manual ­ This macro should be used when there are no occupancy sensors or switches associated with the Group and only on/off actions from schedules or dark/light are intended. Since On/Off changes are based only on schedules and dark/light sensors, the only parameter in the macro that has any effect is Blink, which will provide a warning to occupants by momentarily shutting the load off and then back on.
· Override Time AH ­ This macro is designed for situations where only switches are used (no occupancy sensors). An override time delay is set so that if a switch is used to keep the light on during after hours, the load turns off after two hours. The load is set to turn ON when entering Normal Hours. If you instead want to require that the load be manually turned on, start with this macro when creating the group, select CUSTOM, and modify the Transition AH > NH action to a value of “Do Nothing.” Additionally, adjust Time Delay AH if you want a different amount of time before the load turns off.
NOTE: The settings in this macro are used for Groups 1­8, when you use Smartwire to assign relays to a group. · Sensor Day Disable ­ For use with occupancy sensors, this macro turns all loads ON during Normal Hours; they can be turned off
or back on manually, with no override time delay. When After Hours begins, loads are turned OFF and sensor functionality is set to Auto On/Off. A two hour time delay is set for cases in which some loads in the group are not bound to sensors, but only to switches. · Sensor Man-On NH ­ In this macro, relays are left OFF when Normal Hours begins. Occupancy sensors trigger loads on occupant arrival, but do not time out until after hours. When After Hours begins, loads turn OFF and sensors switch to Auto On/Off. As with the Sensor Day Disable macro, a two hour time delay is set for cases in which some loads in the group are not bound to sensors, but only to switches. · Sensor Auto ­ This macro sets sensors to Auto On/Off for both Normal Hours and After Hours operation, so loads turn ON only based on sensor or switch input. A 120 minute override time delay is used during the After Hours period. This allows for consistent functionality in response to sensors at all times, while accommodating the inclusion of relays not bound to sensors that share the same operational time window. · Auto Switch-1xx ­ This macro is designed to work with the AS-100 Automatic Control Switch. The AS-100 is a switch that controls the line voltage (instead of sending a low voltage control message to the panel or other room controller). Instead, the AS-100 responds to timed power interrupt signals coming from a relay in the panel, providing automatic shutoff with a blink warning when transitioning between normal hours and after hours. Other timed interrupt signals can turn the power on or off. You assign a relay to “AS-100” mode using LMCS-100 software or on the Load Config (PnL) menu in the LMCT-100-2. All relays in “AS-100 mode” remain closed except for the timed interrupts. If this macro is assigned to a group, you should only assign relays in “AS-100” mode to that group. When using this Macro, none of the seven group parameters apply. (Although Blink is set to 5 minutes, the blink time is actually controlled by the AS-100, not the LMCP.) NOTE: Since selecting this mode puts all relay in the associated group into “AS-100” mode, you should not assign those relays to
another group set to a different macro.
NOTE: Keep in mind that Macros only affect the behavior during the transitions to Normal Hours and After Hours, plus the response to occupancy sensors. Any scheduled events and input from photocell sensors will still affect the loads.
NOTE: The values for the seven parameters are only applied to the Group when the Macro (or custom) information is sent to the LMCP from the LMCT-100-2 remote or LMCS-100 software. If a subsequent message is sent to the LMCP with a different value for a parameter, the original value is overwritten, and will only change back to the original value if the Macro is sent again to the group. So for example, if a relay is assigned to two different groups, and each group has been assigned a different Macro, the last macro sent to the LMCP will determine the behavior of that relay.

Macro Manual Override Time AH Sensor Disable Day
Sensor Man-On NH Sensor Auto Auto Switch-1xx

Blink 5 min 5 min 5 min
None 5 min 5 min

Macro Values

General Settings

Transition Settings

Time Delay NH Time Delay AH NH>AH

AH>NH

None

None

Do nothing Do nothing

None

120 min

Turn off

Turn on

None

120 min

Turn off

Turn on

None None None

120 min 120 min
None

Turn off Do nothing Do nothing

Do nothing Do nothing Do nothing

Sensor Behavior

NH

AH

Off Only

Off Only

Off Only

Off Only

Follow On Only

Auto

Off Only

Auto

Auto

Auto

Do nothing Do nothing

DARK/LIGHT EVENTS

The LMCP can be programmed to turn relays on or off based on when it becomes dark outside (night) or light (day). You can program up to 32 separate dark/light events, and each event is assigned to a group or a scene. For each event, you can select whether to base the change from dark to light and light to dark on either an astronomical calculation of sunrise and sunset, or from a photocell connected to an LMIN-104 or LMIO-301. You can have multiple LMIN- 104s/LMIO-301s connected to the network and assign different groups to different LMIN-104 or LMIO-301s, or you can have a single LMIN-104 or LMIO-301 but assign different light thresholds to different groups.
NOTE: You can only select a single LMIN-104 or LMIO-301 if programming with the LMCT-100-2. To use multiple LMIN-104s/LMIO301s, you must program with the LMCS-100 software.
12

Each Dark/Light event has a Dark parameter and Light parameter.
If the event is assigned to a group, then for each parameter you can choose the following:
· 0­100% ­ Load goes to the specific value selected · LNZ ­ Set the load to the last non-zero level. · Turn Off ­ This relinquishes the load–it doesn’t actually “turn off” the load. The loads will still wait for the sensor delay timers to
expire before turning off. If the Partial Off parameter on the Load Settings menu is a value other than 0, the load will go to that level. · Do Nothing ­ No change to the load.
· NH Override ­ Set the load to Normal Hours. The value of the AH­>NH parameter for the group will be applied.
· AH Override ­ Set the load to After Hours. The value of the NH­>AH parameter for the group will be applied. · Normal Hrs ­ Set the load to Normal Hours. All settings found on the Normal Hours tab within LMCS-100 for loads and sensors will
be applied. (These settings are only available if you are using LMCS-100 software.) · After Hrs ­ Set the load to After Hours. All settings found on the After Hours tab within LMCS-100 for loads and sensors will be
applied. (These settings are only available if you are using LMCS-100 software.) If the event is assigned to a Scene, then for each parameter you choose whether to turn the Scene On or Off.

Astronomical Dark/Light Switching
When you use astronomical control, of dark/light events, Dark is triggered by sunset and Light is triggered by sunrise, based on your location.
Additionally, you have the ability to select More Light or Less Light. This parameter, in conjunction with a Time parameter, determines when the event will be triggered in relation to the actual sunrise and sunset time. More/Less light refers to the amount of “daytime”/”nighttime”. The time parameter can be selected in two minutes increments, and is equally divided between before and after the actual sunrise/sunset time. The More Light parameter acts as if the time between sunrise and sunset was longer (more daytime), and Less Light acts as if there were less time between sunrise and sunset (less daytime). So if you select Less Light with a time value of 20 minutes, the Dark event will trigger 10 minutes before sunset and the Light event will trigger 10 minutes after sunrise. The diagram below shows the exact time the events will be triggered based more or less light with different time values.

Dark/Light Event Triggering

7:15

7:00

7:25

18:07 17:57

18:22

Daylight Level

Time ~Midnight

15

10

Min

Min

Light

aka Sunrise aka Dawn

More

Less

Nighttime/Daytime

~Noon

10

15

Min

Min

Dark

aka Sunset aka Dusk

Less

More

Daytime/Nighttime

~Midnight

Astro “Less 20 min”
Dark ON ­ Lights turned on at 17:57 Light OFF ­ Lights turned off at 07:25

Ex: Dallas Astro on 2/9/15
Sunset = 18:07 Sunrise = 07:15

Astro “More 30 min”
Dark ON ­ Lights turned on at 18:22 Light OFF ­ Lights turned off at 07:00

Switching Based on Input From an LMIO-301 or LMIN-104 and Photocell
If you control dark/light events from an LMIO-301 or LMIN-104, you can select the amount of light, in footcandles that will trigger the events. If the light rises above the footcandle amount, a light event will trigger, and if it drops to the exact footcandle amount, a dark event will trigger.
A Time Delay feature allows you to set the number of minutes after the specified footcandle amount is reached before triggering the event. This helps prevent unwanted event triggering, for example, when the light temporarily gets darker because of a cloud passing over the sun.

CONNECTING SWITCHES, SENSORS, PHOTOCELLS, AND OTHER DLM ACCESSORY DEVICES

Accessory Device Support
Each Cat5 Local DLM Network port, labeled A and B, supports a maximum of 48 communicating devices. Note that the panel itself counts as one device in each network, so this allows for a maximum of 94 possible accessory devices per panel (2 x (48-1) = 94).

13

The maximum cable run for a network depends on the number of devices. 150′ of cable is allowed per device; a two device network is allowed 300′, 3 devices 450′ etc., up to 1,000′ maximum. For example a network that has 6 devices supports a maximum of 900′ of total CAT 5e cabling with no minimum or maximum spacing between devices. The first five 5 devices could be separated by a 10′ LMRJ (4 total) and the first switch could then be 860′ from the first panel. Since the maximum length is 1000′ for the network, adding additional accessory devices beyond 6 total will increase the length by 100′ more, no matter how many devices are added. NOTE: Although the two networks are independent for wiring length purposes, all devices on both networks have the ability to
communicate with each other. This provides the end result of a total of 2000′ of cable between all DLM devices connected to the panel via CAT 5e cables. Additionally, if connecting two or more panels via MS/TP, each of those panels has 4000′ feet of connection possible.
Additionally, each network can draw a maximum of 250mA, so the number of devices on a network will be determined by the amount the devices draw. However, if you add room controllers or plug load controllers to the network, they provide additional amperage for the other connected devices, up to a maximum of 800mA.
Switches The panel’s local DLM network supports all models of DLM switches. Switch buttons may be bound to an individual relay (load), scene, or network group in the panel. If a switch is bound to a group and any load assigned to that group is ON, the LED on that switch will indicate ON.
There are several advantages to binding a switch to a group:
· If you add a load to a group, that switch will immediately control that load without having to re-program the switch. · You can assign a switch to the same set of loads controlled by a schedule or dark/light event · If you have multiple panels connected, and the same group number assigned to loads in those panels, the switch will control the
loads from those other panels in addition to the panel in its local network. This allows you to program a single switch that can be used as a master, to turn all lights on or off in the case of an emergency or other special circumstance.
Occupancy Sensors The panel’s local network supports all models of DLM occupancy sensors. Using Push n’ Learn, any number of occupancy sensors can control the same relay(s) in the local panel. In this case, all sensors must be in the unoccupied state before the relay(s) turn off.
A maximum of 32 sensors can control an individual load. (The total number of sensors controlling various loads is limited only by the network limitations described above.)
Daylight Sensors The LMLS-400 and LMLS-500 daylight sensors are capable of controlling relays in the panel as switching loads, or dimming loads if a dimming capable room controller is connected to the local DLM network.
Analog Photocells As described in the previous section on Dark/Light Events, the panel’s local network supports the LMIO-301 Analog Photocell Module or LMIN-104. This module supplies the “light” and “dark” trigger. The panel has user settings for foot candle levels and time delay. The time delay is used before triggering “light” and “dark” events to establish a dead band and prevent nuisance switching. Only one LMIO-301 per panel can be programmed via the LMCT-100; more can be connected if using LMCS-100 software.
Two types of photocell sensor heads can be used. The LMPO-200 is intended for outdoor use, while the LMPS-6000 is intended for indoor use where there is direct exposure to high light levels, as would be present adjacent to the glass in an atrium, skylight, or clearstory.
Using the LMIN-104 to Interface with Third Party Devices The LMIN-104 Digital Input Interface Module allows integration of 3rd party devices to control LMCP relays or other loads in the DLM Local Network. The LIN-104 has four input terminals. In addition to On/Off control of loads, it can dim loads up and down, or send messages such as After Hours, Shed, or Force On to the DLM local network based on external inputs.
The LMIN-104 has three operating modes: Normal, Partition, and Photocell. The LMCT-100-2 or LMCS-100 software is required to program the modes.
In Normal mode, the LMIN-104 can provide control for up to four 2-wire input or two 3-wire input non-DLM switches or sensors.
Partition mode provides the ability to control partitions in multi-use spaces that are frequently reconfigured. Applications include hotel and conference center ballrooms and meeting rooms, school multi-use rooms, and other spaces with movable walls.
Photocell Mode ishould be used n for any application where exterior lighting needs to be controlled based on actual ambient exterior light levels such as parking, site and landscape lighting. Applications with large expanses of skylight, clearstory or atrium glazing can also benefit from controlling lighting based on ambient light entering the building through the glazing.
USING AN LMCP WITH ROOM CONTROLLERS AND PLUG LOAD CONTROLLERS
By connecting room controllers and plug load controllers to the DLM local network, you can increase the number of loads in the network. The maximum number of loads, including all the loads within the panel, is 64. Since the maximum number of devices on a single network is 48, the total number of additional controllers possible will also be dependent on the number of other DLM devices on that network. The same cable length requirements apply as with other DLM devices.
Connecting additional controllers to the panel provides several advantages:
· The loads connected to those controllers can be assigned to groups, the same as the relays in the panel. This allows for scheduling of those loads and all other group features.
· Dimming loads can be added to the network, provided you have a room controller with dimming capability.
14

· Current monitoring of plug loads and dimming loads is possible as part of the network control. (Note that current monitoring of dimming loads within the panel is not available.)
NOTE: There is a maximum of 4 LMRC-10x room controllers, LMPL-101 plug load controllers, and/or LMPB-100 power boosters allowed per network (A or B), for a maximum total of 8. This applies only to the 10x series and not the 2xx series.

Room Controllers

Connecting Room and Plug Load Controllers

Plug Load Controller

Network A 213

102

211

213

LMPL-

221

101

LMCP-24
Network B

Maximum # of connected devices per network: 48 (including 1 for LMCP), for a total of 96. In this example there are 10 devices on Network A and 12 on Network B.
Maximum number of loads, including those in the panel, and on both networks: 64. In this example, there are 50 loads (24 in the panel, 11 on Network A, and 15 on Network B).
Maximum of 4 LMRC-10x or LMPL-101 allowed in a network. In this example, you could add two more 10x controllers to Network A, but none to Network B.

102

102

102

213

212

213

101

Load Control Arbitration
After the room or plug load controllers are connected to the DLM Local Network and powered up, they automatically negotiate to determine which controller becomes the Master. This is referred to as load arbitration. The controllers also determine the load numbers for each relay on the DLM Local Network. By design, the Master is the controller powering the bus with the highest serial number. The panel will have the highest serial number and therefore be the Master. As a general rule, controllers with more loads have a higher serial number than lower ones, and room controller have higher numbers than plug load controllers.
Example: The LMCP-24 is connected to an LMRC-101, LMRC-212, and LMPL-201. The panel uses load IDs 1­24, the LMRC-212 uses IDs 25 and 26, the LMRC-101 uses ID 27, and the LMPL-201 uses ID 28.
NOTE: The panel will reserve IDs based on the number of slots on the LMRD card, not the number of relays installed. So an LMCP-24 with only 16 relays installed will still reserve IDs 1-24.
PROGRAMMING THE LMCP
There are five methods for programming the behavior of the relays in the LMCP. All programming is stored in the memory of the LMCP.
· Directly on the LMCP, using Smartwire, to bind loads to groups 1­8 · Directly on the LMCP and connected switches and sensors, using Push n’ Learn, to bind loads to individual switches and sensors · Using the LMCT-100-2 hand- held remote. This provides all the functionality as Smartwire, but allows you to program all 99 groups
in a panel, instead of just groups 1­8. It also provides the ability to program connected switches and sensors to groups. Additionally, you can use the LMCT-100-2 to bind switches and sensors to individual loads, the same as using Push n’ Learn. · Using the LMCS-100 software. You can connect a PC running LMCS-100 to the panel directly, using an LMCI (USB to LMRJ adapter), or via BACnet. LMCS-100 provides the largest amount of control. If using multiple panels networked together, this is the recommended method. Programming using LMCS-100 is not described in this guide, but instead in the LMCS-100 User Guide. For the latest version, go to https://www.legrand.us/wattstopper/software. · Using an LMJA-8125-AX or LMJA-8300-AX Network Controller or other BAS application through BACnet. A limited number of parameters are exposed directly through BACnet. For details, see “Appendix A” on page 35. Also see the Segment Manager User’s Guide. NOTE: It is strongly recommended that if you are using LMCS-100 software, you do not use the LMCT-100-2 to program the panels or
any connected devices. In a distributed network situation where groups might be assigned across more than one panel, LMCS100 will determine which panel’s memory will store the schedules. Sending information to the panels via the LMCT can create conflicting messages between panels.
15

NOTE: Upon loss of power, date and time info is maintained for 14+ days. Programming info (including schedules) is maintained for the life of the product.
Load Binding to Groups 1­8 (Smartwire)
Smartwire provides a quick and easy way to assign loads (relays) to groups, using the buttons on the panel. If programming from the panel, Smartwire applies only to groups 1­8. Once assigned to the group, pressing the group button to turn that group ON or OFF will turn the associated loads ON or OFF.
NOTE: If using the LMCT-100-2 to program the panel, you can use Smartwire with groups 1­99.
Keep in mind that if panels are networked together, then once a load is assigned to a network group, turning ON that network group in any panel will turn ON the associate loads for that group number, even if it is a different panel.
To program using Smartwire:
1. Press and hold a group button for at least five seconds, until the LED next to the group button begins blinking. At this point, all of the Relay Override LEDs will turn OFF (unless the relay is already bound to the group you are programming, in which case it will blink).
2. Press the buttons for each load that you want bound to that group, so that their LEDs blink. If a load is currently bound to the group and you do not want it part of the group, press the button to turn the LED OFF.
3. Press and release the Group button to exit Smartwire mode. At this point, any Relay Override LEDs that were ON previous to entering Smartwire mode will turn back ON.
4. To test your programming, press the group button to turn it ON. The relays associated with that group will turn ON. You can turn the group back OFF, by pressing the button again.
Push n’ Learn
You can bind a load to specific controllers such as switches or sensors using Push n’ Learn (PnL). The important distinction between PnL and Smartwire is that with Smartwire, you are connecting individual loads to a group rather than binding individual loads to controllers..
PnL vs. Groups
It is possible to assign a controller to more than one load using PnL. In this manner, using PnL is similar to using groups because you can control multiple loads at the same time. The important difference between using PnL and assigning groups is that groups offer more functionality, such as schedules and dark/light, whereas PnL can only assign controllers to loads.
Programming the LMCP Using PnL
1. There are three different methods you can use to enter PnL mode: · Press and hold the Config button on any remote DLM device for at least three seconds, until the red LED on the unit begins to blink. The location of this button will vary,depending on the device. On many devices (such as switches and occupancy sensors), you will need a small pointed tool to push the button. · Press and hold the Panel Config button on the LMPI board of the LMCP for at least three seconds, until the red LED on the unit begins to blink. · Use the LMCT-100-2. Select the LOAD CONFIG (PnL) menu, to enter PnL mode. No matter which method you use, once you enter PnL mode, the red LED on all DLM devices connected in the network will blink, and you can assign any DLM controller to a load on the panel.
2. When you first enter PnL mode, the Status LEDs for all loads except Load 1 will turn off. The Load 1 LED remains active, indicating it is the currently programmable load. At this point, the method of programming depends on whether you are using the LMCT-100-2. a. If you are not using the LMCT-100-2, press the Config button on the LMCP or any connected DLM device. Each time you press the Config button, the panel will cycle to the next load. The Status LED for a load turns ON when that load is selected (only one load LED will be on at a time). When you reach the highest number load, it will cycle back to load 1. You can also jump directly to a specific load by pressing the Override button for that load on the LMCP, LMRC, LMPL, or LMRC. Once you select the desired load, you can bind the specific controller to that load. For a switch, you do this by pressing the desired button on that switch to turn it on. For an occupancy sensor, you use the display and navigation buttons on the sensor to bind that load to the sensor. b. If you are using the LMCT-100-2 then you select the load on the LMCT. It starts by default on load 1. To choose another load, select NEXT, use the left and right arrow buttons to select the desired load, then point the LMCT at the IR sensor and press Select. The screen for that load’s settings opens. On this screen, you can bind a specific controller to that load. For a switch, you do this by pressing the desired button on that switch to turn it on. For an occupancy sensor, you point the LMCT-100-2 at the sensor and select BIND. For more details on programming PnL from the LMCT-100-2, see the LMCT-100-2 User Guide.
3. To exit PnL, hold the Config button for 3 seconds, until the LED stops blinking. Or if using the LMCT-100-2, select EXIT. If you have one or more DLM Room controllers connected to the LMCP, then as when you cycle through the loads by pressing the Config button, once the last relay is reached on the LMCP, the sequence advances to the Room Controller with the highest serial number and cycles through the loads on that controller in order.
A primary difference in operation of the LMCP compared to a DLM Room Controller is that by default, while in load configuration mode, the panel relays do not turn on and off in sequence as the Config button is pressed. Only the LED associated with the relay turns on On a DLM Room Controller, the load itself will turn on and off.
NOTE: It is possible to change the LMCP so that the relays turn on and off in PnL, just like a room controller. This is done by setting Dip switch #7 on the LMPI board to the ON position.
16

PROGRAMMING USING THE LMCT-100

NOTE: In addition to programming the LMCP, the LMCT-100-2 is used for programming many different DLM devices, including switches, occupancy sensors, and other devices. This user guide only describes the screens specific to network setup, panel programming, and assigning of groups. Use of the LMCT-100-2 to bind switches and sensors to individual loads (even when those loads exist in a panel) is detailed in the LMCT-100-2 User Guide.
IMPORTANT: In order to use the LMCT-100-2 with LMCPx-10V, you must have version 6.22 or later firmware installed in the LMCT-100-2. For details on updating firmware, see the LMCT-100-2 User Guide.

LMCT-100-2 Basics
The LMCT-100-2 provides an easy to read display and a simple user interface that makes it easy to navigate through programmable features It both send information to and receives information from the LMCP and other DLM devices.
It is important to understand that all information is stored in the LMCP or accessory devices, and not the LMCT-100-2. Therefore, if you change any values on the LMCT-100-2, you must select the Send option in order to save your changes. If you press the Home button, Back button, or select Done without first sending the data to the LMCP, that data is not saved.
User Interface Navigation
You navigate from one field to another using (up) or (down) arrow keys. The active field flashes between yellow text on black
background and black text on yellow background. Navigation “wraps” around, so if the active field is the top field and you need to get to
the field at the bottom of the screen, pressing will bring you to the bottom in a single key press.
NOTE: The up and down arrow keys are always used to move between fields. So even when fields are placed on the same horizontal line, which is often found with the Action options at the bottom of the screen, you still use the Up/Down arrows to move left/right between fields.
Once a menu field is active, press the Select button to open that menu.
Value fields are used to adjust parameter settings. They are shown within “less than/greater than” symbols: . Change the value
using and arrow keys. In general the key increments and the key decrements a value. Selections wrap-around if you continue to press the key beyond maximum or minimum values. Move between value fields using or arrow keys.
The button takes you to the main menu.
The (Back) button can be thought of as an undo function. It takes you back one screen. Changes that were in process prior to pressing the key are lost.
At the bottom of any screen that includes programmable fields, you will see Send and Done (and sometimes additional choices). As mentioned previously, you must press Send to save your data to the LMCP before pressing Done, if you want to save the values you set on that screen.
On some screens, one of the options at the bottom of the screen will take you to a secondary, related screen. For example, at the bottom of the Program Schedules screen is an Active Days option, where you choose which days the schedule will be active. In the case, the Schedule Active On screen has only a Done option at the bottom–you must return to the Program Schedules screen before you can send the schedule information to the LMCP.

Configuring the Network Settings The Network Settings screen allows you to customize settings related to communication over a BACnet network.

Display

Description

Press

BAT =
Sensor Configuration Load Config (PnL) Load Settings Daylighting Config Button Configuration
More

Scroll Down or Up to Highlight More, then press Select.
Hint: Navigation “wraps” around, so if you scroll “up”, you can reach More with a single button press.

or

then Select

BAT =
Adjust Light Level Global Network Utilities Panel Setup Group Setup
More

Scroll to Global Network. Press Select.

then Select

Point to the desired Panel IR Sensor and
press `Select’

Point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select.

Select

17

Display
Panel Network Network Settings Network Status

Description

Press

The Panel Network screen opens, with Network Settings selected. Press Select

Select

LM Panel

0603981210

Name: 603981210

Device ID:

0981210

AutoSet MSTPMAC:

Auto MSTP MAC:

051

Baud Rate:

<38400>

Max Master:

<127>

DONE SEND

[603981210

]

Move to any chacter with left/right keys. Change the character with the up/down keys.

DONE ERASE COPY PASTE

The top line of the screen shows the serial number of the panel. The Name defaults to the serial number, but can be changed. Highlight the value and press Select to open a new screen, as shown below.
The Device ID must be a unique number within the BACnet network. By default, it is set to the last six digits of the serial number, but like Name can be changed by highlighting the value and pressing Select.
The MS/TP MAC address is another ID used to identify a device. If you select a value of “Yes” for AutoSet MSTP MAC, the LMCP will select a value itself, displayed as the Auto MSTP MAC. If you change the auto set value to “No” and scroll down, the parameter changes to Manual MSTP MAC and you can change the value.
The default Baud Rate is 38400, but can be changed. The Max Master is the highest number the LMCP will try when polling for a master.
Highlight SEND and press Select.
Once again, point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select. You return to the Panel Network screen.
Highlight DONE and press Select, or press to return to the Panel Setup screen.
For a detailed explanation of these parameters, see “Connecting Multiple LMCP Panels in a Network” on page 33.
If you press Select with the Name or Device ID field highlighted, this screen opens. You can change the name using numerals or letters, and change the ID with numerals only.
Select ERASE to clear all characters before entering new data.
When finished editing, select DONE to return to the Panel Network screen.

or

to move to each parameter

or

to change the value of the parameter

then choose SEND and press Select

or

to move to each character

or

to change the value of the character

then choose DONE and press Select

Viewing the Network Status

The Network Status shows the communication “health” of the network and the number of devices currently found on the network.

Display

Description

Press

Panel Network
Network Settings Network Status

From the Panel Network screen, scroll down to Network Status. Press Select

Select

18

Display

Network Status

LM

0603981210

Net Status:

Unhealthy

Net Device Count:

<0>

DONE

Description

Press

The Network Status will display as “Unhealthy” if it can’t find the BACnet network, or if devices on network drop off and then reappear while the LMCP is polling the network (indicating connection problems). If devices show up consistently, or if they disappear and do not show up again (which would indicate the device was disabled or disconnected), the status will display as “Healthy”.
The Net Device Count displays the number of devices on the BACnet network.
Select DONE to return to the Panel Network screen. Highlight DONE and press Select, or press
to return to the Panel Setup screen

Select DONE

Accessing Panel Setup
As mentioned previously, this user guide describes the screens specific to Panel Setup. The following screens show how to navigate into this screen. To avoid repeating the same steps for every function described in the following pages, all sections after this one assume you have already navigated to the Panel Setup screen on the second main menu screen.

Display

Description

Press

BAT =
Adjust Light Level Global Network Utilities Panel Setup Group Setup
More

Scroll Down or Up to Highlight Panel Select, then press Select.

or

then Select

Point to the desired Panel IR Sensor and
press `Select’

Point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select.

Select

Panel Setup
Location Settings Date and Time Panel Programming Panel Status

This screen is the starting point for all following instructions.

Setting the Panel Location

Setting the panel location provides sunrise/sunset information to the panel, for use when you set a schedule according to an astronomical clock.

NOTE: The LMCT-100-2 has a limited number of locations to choose from. For a much more extensive list, use the LMCS software to access this feature.

Display

Description

Press

Panel Setup
Location Settings Date and Time Panel Programming Panel Status

When you first enter the Panel Setup screen, Location Settings is already highlighted. Press Select.

Select

19

Display
Point to the desired Panel IR Sensor and
press `Select’

Description

Press

Point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select.

Select

Location Setup

State:

Rhode Island

City:

Newport

Latitude:

41N

Longitude:

71W

Hours Behind GMT 5

DONE SEND

Select the desired State, and City. The Latitude/ Longitude/Behind/Ahead Hours are fixed values. Then highlight SEND and press Select.
Once again, point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select. You return to the Location Setup screen.
Highlight DONE and press Select, or press to return to the Panel Setup screen

or

to move to each parameter

or

to change the value of the parameter

then choose SEND and press Select

Setting the Date and Time

The date and time are used for schedules, including both manually set events and sunrise/sunset determination (in conjunction with the location settings).

Display

Description

Press

Panel Setup
Location Settings Date and Time Panel Programming Panel Status

From Panel Setup, scroll to Date and Time. Press Select.

then Select

Point to the desired Panel IR Sensor and
press `Select’

Point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select.

Select

Date and Time Set

Ye a r : Month: Date: Hour (24 Hour): Minute:

<2014> <14> <16> <37>

SEND DSTSTD DONE

DST Configuration

Follows DST: Method:

< Ye s >

BEGINS ENDS DONE

DST Automatic Rules

Begins:

<2nd>

DONE

Scroll to each field and set the value. An illegal date (for example, February 30) cannot be entered. After selecting all values, scroll to DSTSTD and press Select.
NOTE: There is no clock in the LMCT-100-2, so the time values will not change if you remain on this screen longer than a minute.
This screen determines if the panel will follow Daylight Savings Time. If you set Follows DST to “Yes”, you can choose a value of “Auto” or “Manual” for Method. Select BEGINS.
NOTE: If you set Follows DST to “No”, the Method field disappears. Highlight DONE and press Select, or press to return to the Date and Time Set screen
Depending on whether you choose a value of Auto or Manual, the screen changes. For Auto, you select the week, the day of the week, and the month. For Manual, you select a specific date (for example, March 20th). Select DONE to return to the DST Configuration window. Repeat the process for the end of DST by pressing ENDS. Then select DONE to return to the Date and Time Set screen.

or

to move to each parameter

or

to change the value of the parameter

then choose DSTSTD and press Select

or

to move to each parameter

or

to change the value of the parameter

then choose BEGINS and press Select

or

to move to each parameter

or

to change the value of the parameter

then choose DONE and press Select

20

Display

Date and Time Set

Ye a r : Month: Date: Hour (24 Hour): Minute:

<2014> <14> <16> <37>

SEND DSTSTD DONE

Description

Press

Highlight SEND and press Select.

or

Once again, point the LMCT-100-2 at the infrared

sensor on the LMRD board and press Select. You

or

return to the Date and Time Set screen.

Highlight DONE and press Select, or press to return to the Panel Setup screen

to move to each parameter
to change the value of the parameter
then choose SEND and press Select

Panel Programming

Panel Programming functions include:

· Schedules ­ Allows you to specify an event and assign it to a group

· Holidays ­ Allows you to specify a specific date as a holiday. Used in conjunction with schedules.

Display

Description

Press

Panel Setup
Location Settings Date and Time Panel Programming Panel Status

From Panel Setup, scroll to Panel Programming. Press Select.

then Select

Panel Programming 603981210
Schedules Holidays

The Panel Programming screen is displayed

To avoid repeating the same steps for every function described in the following pages, the Panel Programming Sections assume you have already navigated to the Panel Programming screen.

Schedules

On this set of screens, you assign and event to a group, and set one action for that event. For each event, you specify the time the event occurs. You also specify whether the event will occur on a per day basis. Additionally, you specify whether the event will occur on any day designated as a holiday.

Display

Description

Press

Panel Programming 603981210
Schedules Holidays

From the Panel Programming screen, highlight Schedules and press Select

Select

Point to the desired Panel IR Sensor and
press `Select’

Point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select to open the Program Schedule screen.

Select

Program Schedule

Event Number:

<1>

Ty p e :

Time:

<07>:<00>

Group: ACTIVE DAYS

<1>

DONE DELETE SEND

Select the Event Number in which to store the schedule information. The Type determines the action for the event. For details on the actions, see the Schedules on page 7. Set the Time for the event to occur and assign the event to a Group. Then, highlight ACTIVE DAYS and press Select.

21

or

to move to each parameter

or

to change the value of the parameter

then choose ACTIVE DAYS and press Select

Display

Schedule Active On

Mon: Wed: Fri: Sun:

Tue: Thu: Sat: Holiday:

DONE

Program Schedule

Event Number:

<1>

Ty p e :

Time:

<07>:<00>

Group:

<1>

ACTIVE DAYS

DONE DELETE SEND

Description

Press

For each day of the week, select whether the event will be active (Yes or No). Additionally, select whether the event will be active on holidays. (You determine which days are holidays in the Holidays screen.)
Highlight DONE and press Select to return to the Program Schedule screen.
Highlight SEND and press Select.
Once again, point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select. You return to the Program Schedule screen, where you can program the next event
When finished, highlight DONE and press Select to return to the Panel Programming screen.

or

to move to each parameter

or

to change the value of the parameter

then choose DONE and press Select

then Select

Holidays

On this screen, you determine which days are designated as holidays.

Display

Description

Press

Panel Programming 603981210
Schedules Holidays

From the Panel Programming screen, highlight Holidays and press Select

then Select

Point to the desired Panel IR Sensor and
press `Select’

Point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select to open the Holiday Setup screen.

Select

Holiday Setup

Holiday: Ye a r : Month: Date: Duration:
DONE

DELETE

<1> <2014> <4> <1 day> SEND

For the Holiday parameter, select the memory location to store the information. Then select the date for the holiday and Duration.
Highlight SEND and press Select.
Once again, point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select. You return to the Holiday Setup screen, where you can program the next event
When finished, highlight DONE and press Select to return to the Panel Programming screen.

or

to move to each parameter

or

to change the value of the parameter

then choose SEND and press Select

Panel Status

This screen displays the date and time,based on the panel settings, sunrise/sunset times based on date and location settings, whether the current date is a holiday, and the current settings of the dip switches. Additionally, it will display an error message for certain problems.

Display

Description

Press

Panel Setup
Location Settings Date and Time Panel Programming Panel Status

From Panel Setup, scroll to Status. Press Select .

then Select

22

Display

Description

Press

Point to the desired Panel IR Sensor and
press `Select’

Point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select.
One of the following screens will display, depending on the Status option you selected.

Select

Panel Status Nov 10, 2014 Mon

15:19 STD Non-Holiday

Sunrise:

06:14

Sunset:

16:47

Con LEDs:

00000000

Dip Switch:

00000000

DONE

Most fields on this screen are self explanatory. A value of “STD” indicates standard time and a value of “DST” indicates daylight savings time
The Con LEDs field indicates errors, and will show “1” in individual digits when the Config LED is lit solid and not blinking. From left to right, the error categories are as follows:
· 1st and 2nd digits ­ not used
· 3rd digit ­ RTCLOCK
· 4th digit ­ SEEPROM
· 5th digit ­ Bootload
· 6th digit ­ Power
· 7th digit ­ DLM Local Network
· 8th digit ­ Relay
Press Select to return to the Status screen.
For the Dip Switch field, a value of 1 indicates that particular dip switch is set to ON. For details on what each dip switch controls, see “Dip Switches” on page 7.

Select DONE

Accessing Group Setup Options

Group Setup provides access to the following functions:

· Assign Loads to groups · Set Occupancy Sensor behavior for groups · Assign Dark/Light Events to groups

Display

Description

Press

BAT = Adjust Light Level Global Network Utilities Panel Setup Group Setup
More
WARNING: LMBC or Panel must
be connected To a c c e s s
Group Setup
Press `Select’ to proceed

Navigate to the Group Setup option on the second main menu screen and press Select.

then Select

A warning appears, explaining that a bridge or panel is needed for this functionality. Press Select, then point the LMCT-100-2 at any IR enabled device and press Select again..

Select

Group Setup ­ Panel
Group Loads Group Occ Sensors Group Dark/Light
DONE

This screen provides access to the three Group setup options. Navigate to the desired option and press Select.

Select

23

Group Loads

On this set of screens, you assign loads to groups and customize the behavior of those groups.

Display

Description

Press

Group Setup ­ Panel

Group Loads Group Occ Sensors Group Dark/Light
DONE

Group Setup

Group: Ty p e :

<1+> <Custom+>

DONE DELETE SEND

From Group Setup,highlight Group Loads and press Select.
Choose the Group number. Press Select to open the Group x Loads screen.

Select or

or

Group 1 Loads

To assign various loads to the group, scroll through

Load:

each Load number and select whether that load

< 1 > is a Member of that group. When complete, select

or

Member:

< Ye s > DONE to return to the Group Setup screen.

DONE SMARTWIRE

You also select have the option of using the Smartwire function instead of manually scrolling through the loads. To do this, select SMARTWIRE.

to choose the Group number then press Select
to move to each parameter to change the value of the parameter then choose DONE and press Select
OR Select SMARTWIRE

Point to any IR enabled device and
press Select to begin Smartwiring
loads within the Panel

Point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select

Select

Add or Remove loads by using the
push button next to each relay. When finished, point to the IR device and select either
DONE CANCEL

Group Setup

Group: Ty p e :

<1+> <Custom+>

DONE DELETE SEND

Group 1 Custom Parms

Blink:

<5 min>

Time Delay NH:

Time Delay AH: <120 min>

NH > AH:

AH > NH:

NEXT DONE

Once you enter Smartwire mode, you can use the Load buttons on the panel to assign the loads to the group. See “Load Binding to Groups 1­8 (Smartwire)” on page 16 for details. Note that using this method, you can program groups higher than #8 (up to group #99) with Smartwire. Once finished, select DONE to return to the Group Setup screen.
Select the Type field. Choose one of the predefined macros or select “Custom+” to define the group behavior parameters.
If choosing “Custom+”, press Select to open the Group x Custom Parms screen.
For details on the Macros, see “Macros” on page 12. If choosing a Macro, proceed to the last step in this section.
The Group x Custom Parms screen contains the first five of the seven programmable parameters. For definitions of these fields see “Groups, Scenes, Schedules, and Macros” on page 9.
Select NEXT to access the remaining two parameters.

Select DONE

or

to move to each parameter

or

to change the value of the parameter

then choose LOADS and press Select

or

to move to each parameter

or

to change the value of the parameter

then choose NEXTand press Select

24

Display

Group 1 Custom Parms Sensor Behavior

AH: NH:

<Auto On/Off> <Auto On/Off>

PRIOR DONE

Group Setup

Group: Ty p e :

<1+> <Custom+>

DONE DELETE SEND

Description

Press

or

After setting the last two parameters, select DONE

or

to return to the Group Setup screen.

Highlight SEND and press Select.

or

Once again, point the LMCT-100-2 at the infrared

sensor on the LMRD board and press Select. You

return to the Group Setup screen, where you can

or

program the next group.

When finished, highlight DONE and press Select to return to the Group Setup Options screen.

to move to each parameter to change the value of the parameter then choose DONE and press Select
to move to each parameter to change the value of the parameter then choose LOADS and press Select

Group Occupancy Sensors

On this set of screens, you assign individual events that determine whether loads assigned to a group will turn on or off, based on input from an occupancy sensor.

NOTE: If using multiple occupancy sensors, when programming with the LMCT-100-2, you should only assign ONE sensor input to a group. Assigning more than one sensor to a group will lead to inconsistent response (but you can assign different sensors to different groups). If you need to assign multiple sensors to a group, use the LMCS software to program the actions. The LMCS software has additional capabilities for programming input from multiple sensors.

Display

Description

Press

Group Setup ­ Panel
Group Loads Group Occ Sensors Group Dark/Light
DONE

From Group Setup,highlight Group Occ Sensors and press Select.

Select

Point to the desired Panel IR Sensor and
press `Select’

Point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select to open the OccSensor Event screen.

Select

OccSensor Event

Event Number:

<1>

NEXT DONE DELETE SEND

Select the Event number in which to store the occupancy sensor event. Then highlight NEXT and press Select.

or

to change the value of the parameter

then choose NEXT and press Select

25

Display

Occ Sensor Event 1

OccSensor:

<1>

Event Type:

Occupied:

Vacant:

Group:

<1>

ACTIVE DAYS DONE

Occ Sensor Active On

Mon: Wed: Fri: Sun:

Tue: Thu: Sat: Holiday:

DONE

OccSensor Event

Event Number:

<1>

NEXT DONE DELETE SEND

Description

Press

Select the number of the OccSensor assigned to the event. Sensor numbers are automatically assigned based on serial number with the highest number set to 1, next highest set to 2, etc.
Set the Event Type to either “Group” or “Scene”.
Set the Occupied (sensor detects occupancy) and Vacant (sensor detects vacancy). Depending on whether you chose “Group” or “Scene”, the possible values will change. For a scene, it will be either “Scene On” or “Scene Off”. For a group, see “Occupancy Sensor Events for Groups” on page 11 for a description of the values for these parameters.
NOTE: Whether the load responds to the sensor message is determined by the two sensor related parameters that are part of the group. So, for example, if Sensor NH is set to Manual On/Auto Off, the load will respond to the Off Action but not the On Action during Normal Hours.
The last parameter will change to be either Group or Scene, depending on the value you chose for Event Type. Select the group or scene that the event is assigned to. Then, highlight ACTIVE DAYS and press Select
For each day of the week, select whether response to sensor input will be active (Yes or No). Additionally, select whether the event will be active on holidays. (You determine which days are holidays in the Holidays screen.)
Highlight DONE and press Select to return to the Occ Sensor Event x screen. Then select DONE again to return to the OccSensor Event screen.
Highlight SEND and press Select.
Once again, point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select. You return to the Group Setup screen, where you can program the next group.
When finished, highlight DONE and press Select to return to the OccSensor Event screen.

or

to move to each parameter

or

to change the value of the parameter

then choose ACTIVE DAYS and press Select

or

to move to each parameter

or

to change the value of the parameter

then choose DONE and press Select

to choose

or

SEND and

press Select

Group Dark/Light

On this set of screens, you assign individual dark/light events.

Display

Description

Panel Programming 603981210
Schedules Holidays Dark/Light Groups Occupancy Sensors

From the Panel Programming screen, highlight Dark/Light and press Select.

Press then Select

Point to the desired Panel IR Sensor and
press `Select’

Point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select to open the Dark/ Light Events screen.

Select

26

Display

Dark/Light Events

Event:

<1>

NEXT DONE DELETE SEND

Dark/Light Event 1

Controller:

Ty p e :

Dark:

Light:

<20min>

Group:

<9>

ACTIVE DAYS DONE

Description

Press

Select the Event number in which to store the dark/light event. Then highlight NEXT and press Select to open the Dark/Light Event x screen.
This screen changes depending on the value of the Control parameter. By default, this is set to “Astro”. In this case, the dark and light events are determined by sunrise and sunset, which is dependent on the values you set on the Location Setup screen.
Set the Type to either “Group” or “Scene”.
Set the Dark and Light parameters. Depending on whether you chose “Group” or “Scene”, the possible values will change. For a scene, it will be either “Scene On” or “Scene Off”. For a group, see “Dark/Light Events” on page 12 for a description of the values for these parameters.
The next parameter can be set to “More Light” or “Less Light”. This parameter, in conjunction with the following Time parameter, determines when the event will bet triggered in relation to the actual sunrise and sunset time. More/Less light refers to the amount of “daytime”/”nighttime”. The time parameter can be selected in two minutes increments, and is equally divided between before and after the actual sunrise/sunset time. The More Light parameter acts as if the time between sunrise and sunset was longer (more daytime), and Less Light acts as if there were less time between sunrise and sunset (less daytime). So if you select Less Light with a time value of 20 minutes, the Dark event will trigger 10 minutes before sunset and the Light event will trigger 10 minutes after sunrise. See the chart on page 13 for more details of this example.
The last parameter will change to either Group or Scene, depending on the value you chose for Event Type. Select the group or scene that the event is assigned to.
Then, highlight ACTIVE DAYS and press Select. (Skip ahead to the D/L Active Event ON screen.

or

to change the value of the parameter

then choose NEXT and press Select

or

to move to each parameter

or

to change the value of the parameter

then choose ACTIVE DAYS and press Select

27

Display

Dark/Light Event 1

Control:

<Photocel 1>

Ty p e :

Dark:

Light:

Setpoint:

<50fc>

Delay:

<2min>

MORE

DONE

Dark/Light Event 1

Group:

<1>

ACTIVE DAYS DONE

D/L Event Active On

Mon: Wed: Fri: Sun:

Tue: Thu: Sat: Holiday:

DONE

Dark/Light Events

Event:

<1>

NEXT DONE DELETE SEND

Description

Press

If you change the Controller parameter to “Photocel 1”, dark light events are instead triggered by photocell sensor input. Although multiple LMIN-104s or LMIO-301s may be connected to the network, only a single one can be programmed using the LMCT. Select the number of the LMIN-104/LMIO-301 you wish to assign. The LMIN-104 or LMIO-301 with the highest serial number will have the lowest ID, and so on.
Set the Type to either “Group” or “Scene”.
Once you select a value and scroll down to the next parameter, the screen changes. Two new parameters are displayed below Dark and Light.
The Setpoint is the amount of foot candles that will determine when the Dark and Light events are triggered. (When the light becomes brighter than the Setpoint, it triggers the Light event, and when it becomes darker, it triggers the Dark event.)
The Delay parameter sets the amount of time after the Setpoint is reached that the event is actually triggered. This helps prevent unwanted event triggering, for example, when the light temporarily gets darker because of a cloud passing over the sun.
Select MORE to display the final parameter.
The parameter on this screen will change to either Group or Scene, depending on the value you chose for Event Type. Select the group or scene that the event is assigned to.
Then, highlight ACTIVE DAYS and press Select.
For each day of the week, select whether the dark/ light event will be active (Yes or No). Additionally, select whether the event will be active on holidays. (You determine which days are holidays in the Holidays screen.)
Highlight DONE and press Select to return to the Dark/Light Event x screen. Then select DONE again to return to the Dark/Light Events screen.
Highlight SEND and press Select.
Once again, point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select. You return to the Dark/Light Events screen, where you can program the next event
When finished, highlight DONE and press Select to return to the Panel Programming screen.

or

to move to each parameter

or

to change the value of the parameter

then choose ACTIVE DAYS and press Select

or

to move to each parameter

or

to change the value of the parameter

then choose DONE and press Select

or

to move to each parameter

or

to change the value of the parameter

then choose DONE and press Select

to choose

or

SEND and

press Select

Utilities

The LMCT-100-2 contain a number of different Utilities. This section covers the Status utilities provide status information on loads and groups, photosensors, and sensors connected to the panel.

An additional screen containing status information specific to panels is also available from the Panel Setup screen. See “Panel Status” on page 22.

Display

Description

Press

BAT =
Adjust Light Level Global Network Utilities Panel Setup Group Setup
More

Navigate to the Utilities option on the second main menu screen and press Select.
28

then Select

Display
Utilities Menu SmartWire Identify Devices Force System into PnG Room Mode Load Shed Status
Done
Status ­ Panel
Load Status Group Status Light Level Occupancy Sensors
Done

Description

Press

Navigate to the Status option and press Select.

then Select

Press Select to choose the Load Status option.

Select

Load Status This set of screens displays details about each load in the panel, as well as any loads in connected room controllers.

Display

Description

Press

Load 1 Status

Load On:

Select More

01 1111111111 10

11 1101101001 20

21 11101 . . . . . 30

31 . . . . . . . . . . 40

41 . . . . . . . . . . 50

51 . . . . . . . . . . 60

The “1” indicates a priority of 8.

The first screen indicates the on/off status of each load. A value of “1” indicates it is ON. A value of “0” indicates it is OFF. A value of “.” indicates no load exists for that number.
The loads within the panel display first followed by loads from connected room controllers. In the example to the left, loads 1­24 are within the panel and load 25 is from an LMRC-101.
For additional details about the load, highlight that load and press Select to open the Load x Online screen. (If you try and select a number for which there is no load, nothing happens.)
To return to the Status screen, scroll down past the bottom row (51­60). A second screen displays showing loads 21­64. Highlight DONE and press Select.

or

to select the

or

desired load

then press Select

Load 1 Online

1 2 3 4 5 6 … . ..

7 8 9 10 11 12 .1. . .. 13 14 15 16

… .

PROPERTIES

DONE

Load 2 Properties 1

Output Level:

100%

Load Type:

NonDim

Grace Timer:

None

Mode:

Normal Hours

Blink:

5 min

NEXT

DONE

This screen displays the BACnet priority of the load DLM devices will typically have a priority of 8. Highlight PROPERTIES and press Select.
This screen indicates the current output of the load, whether the load is a dimming or non-dimming load. Mode indicates whether the load is currently in Normal Hours or After Hours. Grace Timer indicates whether the load is currently counting down between Normal Hours and After Hours, during the Blink period. For details on the definitions of each parameter value on this and the next two screens, see the Load Settings section of the LMCT-100-2 User Guide. Highlight NEXT and press Select to see more properties or select DONE to return to the Panel Setup screen.

Select Select

29

Display

Load 2 Properties 2

TDelay NH: TDelay AH: NH­>AH: AH­>NH:

None 120 min Tur n Off Do Nothing

NEXT PRIOR DONE

Load 2 Properties 3

Sensor Behavior

AH:

Man On/Auto Off

NH:

Auto On/Off

PRIOR

DONE

Description

Press

This screen displays parameters related to the transitions between Normal Hours and After Hours.
Highlight NEXT and press Select to see more properties or select DONE to return to the Panel Setup screen.

Select

This screen displays the sensor behavior for this load.
Highlight DONE and press Select to return to the Status screen.

Select DONE

Group Status

This set of screens displays the loads that are assigned to the group, along with their current on/off state. Additionally, you can view the settings for the group. Finally, in cases where the setting of an individual load are different from the group settings, you can view the differences. This can be extremely helpful when trying to diagnose a situation in which a load is not responding as expected. Keep in mind that individual loads can be programmed with different values from the group but still be a member of the group.

Display

Description

Press

Status ­ Panel

Load Status Group Status Light Level Occupancy Sensors

Done

Group Status

Group:

<1>

NEXT

DONE

From the Status Menu, highlight the Group Status option and press Select.
Select the Group number that you want to display, highlight NEXT, and press Select.

then Select

or

to change the value of the parameter

then choose NEXT and press Select

Point to the desired Panel IR Sensor and
press `Select’

Point the LMCT-100-2 at the infrared sensor on the LMRD board and press Select.
One of the following screens will display, depending on the Status option you selected.

Select

30

Display

Group

1 Status Mixed

Load 5

Parms Not Same

01 11 .0 1. . . . . 10

11 11. . . . . . .1 20

21 . . 101 . . . . . 30

31 . . . . . . . . . . 40

41 . . . . . . . . . . 50

51 . . . . . . . . . . 60

Actual Load 5
Blink: TDelay NH: TDelay AH: NH­>AH: AH­>NH:

Parms1
5 min None 120 min Tur n Off Tur n On

MORE GROUP PARMS DONE

Actual Load 5

Parms2

Sensor Behavior

AH:

Man On/Auto Off

NH:

Auto On/Off

MORE GROUP PARMS DONE

Group Load 5
Blink: TDelay NH: TDelay AH: NH­>AH: AH­>NH:

Parms1
10 min None
120 min Tur n Off Tur n On

MORE LOAD PARMS DONE

Group Load 5

Parms2

Sensor Behavior

AH:

Man On/Auto Off

NH:

Auto On/Off

MORE LOAD PARMS DONE

Description

Press

This screen indicates which loads are assigned to the group, along with the on/off status of each load. A value of “1” indicates it is ON. A value of “0” indicates it is OFF. A value of “.” indicates the load is not assigned to the group.

On the top line, the Status will display “Off” if all

assigned loads are off, “100%” if all loads are on

and there is no dimming, and “Mixed” if some loads

or

are on and others are off. If all loads in the group

dim and are set to the same dimming amount, it

will display that amount.

or

Move the cursor to highlight a specific load. If you scroll down below the line for 51­60, you will see loads 61­64.

The load number will display in the second line. The Parms parameter will say either “Same” if the load parameters match the group parameters, or “Not Same” if there is a difference. To view the difference, press Select to open the Actual Load x Parms 1 screen

The screen displays the values of the first five

parameters assigned to the individual load.

To view the sensor parameters, highlight MORE

or

and press Select.

To compare the values on this screen with the values for the group, highlight GROUP PARMS and press Select.

The screen displays the values of the sensor

parameters assigned to the individual load.

To return to the original 5 parameters, highlight

or

MORE and press Select.

To compare the values on this screen with the values for the group, highlight GROUP PARMS and press Select.

The screen displays the values of the first five parameters assigned to the group.

In this example, if you compare the Blink

parameter to the one on the Actual Load screen,

you will see the group value is 10 minutes, while

or

the individual load is 5 minutes.

To view the sensor parameters, highlight MORE and press Select.

To compare the values on this screen with the values for the individual load, highlight LOAD PARMS and press Select.

The screen displays the values of the sensor parameters assigned to the individual load.

To return to the original 5 parameters, highlight

MORE and press Select.

or

To compare the values on this screen with the

values for the group, highlight GROUP PARMS

and press Select.

Once you finish comparing the values, highlight DONE and press Select to return to the Status screen

to select the desired load then press Select
to choose the option then press Select
to choose the option then press Select
to choose the option then press Select
to choose the option then press Select

31

Light Level This screen displays the current light level, in foot candles, registered by an LMIO-301 with an attached photosensor.

Display

Description

Press

Status ­ Panel

Load Status Group Status Light Level Occupancy Sensors

From the Status Menu, highlight the Light Level option and press Select.

Done

301 MAC:

1 of 2 Level 0373303229

Light Level:

1 fc

NEXT PRIOR DONE

The top line of the display shows the number of LMIO-301s connected to the network. The display shows the light level of a single device. The second line shows the serial number (MAC address) of the currently displayed device.
Highlight NEXT and press Select to view the light level of another photosensor. Or select DONE to return to the Status screen.

Occupancy Sensor Status

This screen display current values of occupancy sensors attached to the network.

Display

Description

Press

then Select
Select NEXT OR
Select DONE

Status ­ Panel
Load Status Group Status Light Level Occupancy Sensors
Done

OccSen MAC:

1 of 4 Stat 0209715204

Status: State: Load Tracking:

Online Occupied
Ye s

NEXT PRIOR DONE

From the Status Menu, highlight the Occupancy Sensors option and press Select.
The top line of the display shows the number of occupancy sensors connected to the network. The display shows the values for a single occupancy sensor. The second line shows the serial number (MAC address) of the currently displayed device.
Status indicates whether the sensor is currently found on the network. (When a sensor is connected, it is stored in memory until the panel is reset. So, if the sensor is disconnected and the panel has not been reset, the status will display “Offline”.)
State indicates whether the sensor currently is set as occupied or unoccupied.
If Load Tracking is “Yes”, loads bound to the sensor will respond, based on the programming settings for the sensor and group. If it is set to “no, then the loads will not respond to the sensor. This is used in situations where the panel is connected to a BAS or other BACnet device and you want to use the sensor to monitor occupancy/vacancy for purposes other than turning loads on or off.
Highlight NEXT and press select to view the values of additional photosensors. Or select DONE to return to the Status screen.

then Select
Select NEXT OR
Select DONE

32

CONNECTING MULTIPLE LMCP PANELS IN A NETWORK

The LMCP can connect to other LMCP panels via BACnet, using the MS/TP connections. Connecting panels to each other via BACnet allows them to share common group numbers for schedules or switches. This provides the ability to program a common behavior for an entire building or section of a building, via LMCS-100 software
One or more LMCPs can also be connected to other devices in a Building Automation System (BAS) using BACnet. This provides for connection to a Segment Manager or other supervisory system. The BACnet settings can be configured using the LMCT-100-2 controller or LMCS-100 software.
BACnet Settings
The following parameter settings and concepts are important to understand when configuring the LMCP for BACnet communication:
· Device ID ­ The device ID is a unique number, between 0 and 4194302, that identifies a device in a BACnet network. Every device in the network must have a different number. By default, the LMCP uses the last 6 digits of the serial number (plus a leading 0 to complete the seven digit number). This number can be changed if needed, for example, when required by an integrator, as part of a BAS. Once set, the LMCP will remember the ID number even if other parameters are reset to their default values.
· Device Name ­ This is a label for the panel, useful when working with LMCS in a situation where multiple panels are used, to help more easily distinguish between the panels. Any numerals or letters can be used in naming the panel. By default, the name is the same as the serial number. The name can be programmed using either LMCS, the LMCT-100-2, or a BAS application.
· MS/TP MAC Address ­ The MS/TP MAC address is an additional identifier, used by the devices on the network to communicate with each other. It is a number between 0 and 127. It is important to understand the difference between the device ID and the MS/ TP MAC Address. The Device ID is, in essence, a number that identifies “who” the devices is, while the MS/TP MAC address identifies its “location”. In a BACnet network, all the devices pass a token to each other to determine which device has control of communication over the network. The MS/TP MAC address is used to “locate” other devices. When a device receives the token, it will take control of the communication and send messages to other devices as needed. It then passes the token to the device with the next highest MS/TP MAC address. In order to do this, it sends an “Are you there?” message on the MAC address one higher than its own. If it receives a response, it passes the token. If it does not receive a response, it tries again on the next highest number, continuing in this manner until it receives a response. This “Are you there?” message is referred to as a Poll For Master.
NOTE: In order to send and respond to this Poll For Master message, a device must be designated as a master device. Other devices (slave devices) on the network will not respond, and cannot take control of the communication.
While the Device ID is fixed and should not change, the MS/TP MAC address can change as devices come on or drop off the network. By default, the LMCP will automatically assign an MS/TP MAC address. When the LMCP is powered up, it will check the network for other devices to determine if its current MAC address is being used by another device. If, not it will keep the same address, but if it is, and will assign an unused number between 32 and 127.
You can manually assign an MS/TP MAC address instead of having the LMCP automatically assign the number. This can be useful, especially in larger networks where response time is important. Since the Poll For Master message checks the next highest address number and then increments that number until it finds a device, having devices with gaps between numbers can increase latency. If you have 10 devices, numbered 0­9, you will have optimal performance since no time is wasted sending the Poll For Master message to an unused number.
· Max Master ­ The Max Master parameter is another parameter that will cut down on latency. The value you set for this parameter is the highest number the LMCP will check when sending a Poll For Master message, before returning to 0. So, in the previous example, where there are 10 devices numbered 0­9, if you set the Max Master to 9, it will never check addresses 10­127. NOTE: If using the LMCP with a global controller such as a router, BAS or Segment Manager, the global controller will always default to a MAC address of 0.
NOTE: You should be aware that devices connected over the DLM Local Network also have MAC addresses for communication purposes, but that MAC address is entirely separate from the MS/TP MAC address.
Further details on Device IDs and MAC addresses can be found in WattStopper’s Technical Bulletin #180 at http://www.wattstopper.com/ resources/download- center/tech-bulletins-whitepapers.aspx.
Examples of Using the LMCP in a BACnet Network
The following three examples demonstrate applications for connecting the LMCP to a BACnet network:
Two or more LMCP panels connected to each other without a Segment Manager or BAS
This is the simplest configuration. Remember that when a relay is assigned to a group, if more than one panel uses the same group number, those relays in the different panels will respond to any events or controllers that affect that group. While this can provide an easy way of controlling relays in multiple locations, if that is not what you want, make sure to use different group numbers in different panels.
When connecting the panels via the MS/TP jack, keep in mind that the general rules for BACnet MS/TP apply. This includes termination quality, polarity of the dataline, maximum network physical length, usage of repeaters/isolators, usage of proper dataline (LM-MSTP and LM-MSTP-DB only), etc.
One or more LMCP panels connected to an LMJA-8125-AX or LMJA-8300-AX Network Controller
Best practice rules for connecting panels to a Segment Manager can be found in technical bulletin #189. Wiring information, including termination quality and polarity are discussed in technical bulletin #179.2. These technical bulletins can be found at http://www.wattstopper.com/resources/download-center/tech- bulletins-whitepapers.aspx.
The critical issue to keep in mind when using a Segment Manager is that you should normally use only the LMCP or the Segment Manager to control scheduled events, since these events are associated with groups. The group related control messages sent from the
33

Segment Manager (see Appendix A) have the same priority as LMCP native schedules. Therefore, the group will always respond to the most recently received event, and Segment Manager schedules and LMCP schedules can conflict with each other.
Utilizing LMCS-100 allows for programming intricate coordinated behaviors, where either the LMCP or Segment Manager schedules can take precedence under certain circumstances, but this requires detailed understanding of the BACnet priority array and of LMCS configuration, and is not normally recommended.
Additionally, similar to the way in which a load can be programmed individually and still be part of a group, and so that the group setting is applied when the group information is sent to the LMCP, you can send a message from the Segment Manager that will change a setting for a device that is part of a group, and the group setting will not revert to the group value until the group information is sent again to the LMCP by the LMCT-100-2 or LMCS-100.
One or more LMCP panels connected directly to the front end systems configured by an integrator/BAS technician When connected to a BAS application, the LMCP can provide a variety of status messages. The LMCP (and other devices connected via the DLM Local Network) can also respond to a variety of command messages. “Appendix A” on page 35 lists the objects used for communication with the LMCP.
BACnet Connectivity Scenarios

Addressing shown using optimized Device IDs and Mac addresses. Default IDs and Auto MAC addressing can be used as desired, but sequential addresses can optimize performance if needed.

Optional connection to LMCS-100 software.
Must match UDP port# of any routers

ID: 86001 MAC: 01

LMCP Panels

ID: 86002 MAC: 02

ID: 86003 MAC: 03

Network Number = 1000

NB-Router
ID: 1000 MAC: 00

Optional connection to Segment Manager Connect via MS/TP or IP
LMSM

Each of these are valid Segment Networks

ID: 86004 MAC: 04

ID: 86005 MAC: 01

LMCP Panels
ID: 86006 MAC: 06

ID: 86007 MAC: 07

ID: 86008 MAC: 08

Network Number = 1001 (if a router were added)
The Device ID’s of this BACnet Segment Network are unique so that it could be combined with the top network if desired. Combining Segment Networks is done using NB-ROUTERs that must then assign a network number to each Segment Network.

34

APPENDIX

BACnet Objects
NOTE: While there are 96 object instances available for many of the objects listed below, keep in mind that the LMCP panel supports only 48 devices per network (A & B), and the panel itself is one of the devices in each network. Therefore, there is never a case where you would use all 48 instances of an object in a single network.

Object Instance BO1­BO64
AO1­AO64 AV1­AV96
AV401­496
AV501­596
AV101­AV196 AV201­AV296 AV301­AV396 AI1­AI96 AI4001­AI4096 AI5001­AI5096 AV4101­AV4196 AV4201­AV4296 AV4301­AV4396 AV4401­AV4496 AV4501­AV4596 AV4601­AV4696 AV5101­AV5196 AV5201­AV5296 AV5301­AV5396 AV601­AV664

Object Alias

Object Function

Device/Group Specific Control Objects

Loads 1­64, state

Relay state, internally linked to the Analog Output objects by the trip point parameter. Relay is ON above trip point and OFF below trip point. Default trip point is 50% for LMRC-100 Series room controllers and 1% for LMRC-200 and -300 Series room controllers.

Loads 1­64, level

Dimming level, internally linked to the Binary Output objects by the trip point parameter. Range = 0 to 100%.

Wattage

Calculated based on the input voltage and measured current for room controller 1 to 96. This only provides a valid reading if LMCS is used to configure the “Baseline Wattage” values of all the panel’s relays. The panel has no Current Transformers so this reading is also subject to those loads operating correctly. If no full duty baseline power values are configured, this value is calculated as AV501 * AV401 when any one relay is active.
AV2-96 will only exist if any LMRCs or LMPLs or LMFCs are present on the CAT5 networks A or B.

Input Voltage

Per room controller, written by the user, default is 0.
AV402­496 will only exist if any LMRCs or LMPLs or LMFCs are present on the CAT5 networks A or B.

Electrical current

Read total current flowing through the room controller in amps, for room controller 1 to 96.
AV502­596 will only exist if any LMRCs or LMPLs or LMFCs are present on the CAT5 networks A or B.

Occupancy sensor 1­96, time delay

For occupancy sensor 1 to 96, 0 to 30 minutes.

Occupancy sensor 1­96, PIR sensitivity Per PIR (passive infrared) sensor, 0 to 100% in percent, 10% resolution.

Occupancy sensor 1­96, ultrasonic sensitivity

Per ultrasonic sensor, 0 to 100% in percent, 10% resolution.

Exterior photocell

Daylight level as read by LMIO-301 photocell input module 1 to 96.

Daylight sensor 1­96, light level

Interior footcandle level as read by LMLS-400 daylight sensor 1 to 96.

Daylight sensor 1­96, light level

Interior footcandle level as read by LMLS-500 daylight sensor 1 to 96.

Daylight sensor 1­96, ramp up rate

For LMLS-400 daylight sensor 1 to 96, ramp up rate. Default is 20% per second, writable in the range of 1% to 100 % per second.

Daylight sensor 1­96, day setpoint

For LMLS-400 daylight sensor 1 to 96, day setpoint. Default is 50 footcandles, writable in the range of 1 to 255 footcandles.

Daylight sensor 1­96, night setpoint

For LMLS-400 daylight sensor 1 to 96, night setpoint. Default is 10 footcandles, writable in the range of 2 to 255 footcandles.

Daylight sensor 1­96, off time delay

For LMLS-400 daylight sensor 1 to 96, off time delay. Default is 10 minutes, writable in the range of 3 to 30 minutes.

Daylight sensor 1­96, on setpoint

For LMLS-400 daylight sensor 1 to 96, on setpoint. Default is 7.5 footcandles, writable in the range of 1 to 3000 footcandles.

Daylight sensor 1­96, off setpoint

For LMLS-400 daylight sensor 1 to 96, off setpoint. Default is 11.25 foot- candles, writable in the range of 1.5 to 6000 footcandles.

Daylight sensor 1­96, zone 1 setpoint For LMLS-500 daylight sensor 1 to 96, target setpoint for zone 1. Writable in the range of 1 to 200 footcandles.

Daylight sensor 1­96, zone 2 setpoint For LMLS-500 daylight sensor 1 to 96, target setpoint for zone 2. Writable in the range of 1 to 200 footcandles.

Daylight sensor 1­96, zone 3 setpoint For LMLS-500 daylight sensor 1 to 96, target setpoint for zone 2. Writable in the range of 1 to 200 footcandles.

Loads 1­64, demand response cap level

Maximum dimming level for load during a demand response (shed) event. 100 = disabled.

35

Object Instance

Object Alias

Object Function

BI101­BI9608

Button state

Read button state for 1 to 8 buttons per switch for 1 to 96 switches.

BI1­BI96

Detection state

Occupancy sensor detection state. Active = occupied.

BV101­196

Switch lock status

Read switch status (locked or unlocked). Active = locked.

BV201-299

Group Normal Hours/After Hours

Normal Hours/After Hours selection for a group. Active = after hours.

MV4001­MV4096 Daylight sensor 1­96, operating mode For LMLS-400 daylight sensor 1­96, operation mode: 1 = ON/OFF, 2 = bi-level, 3 = tri-level, 4 = dimming.

MV4101­MV4196 Daylight sensor 1­96, setpoint multiplier For LMLS-400, off setpoint multiplier: 1=1.25x, 2=1.50x, 3=1.75x, 4=2x.

Room Level Control Objects

BV1

Schedule state

Normal hours/after hours selection. Active = after hours.
NOTE: This changes the status for the entire panel, and therefore can conflict with BV201-299, if not used carefully.

BV2

Switch lock control

Lock or unlock enabled switches. Active = lock.
NOTE: This changes the switch lock status for every switch connected to the panel, and therefore can conflict with BV101-196, if not used carefully.

BV3

Room occupancy status

Read occupancy status (occupied or unoccupied). Active = occupied.
NOTE: This is the logical OR of the states of ALL sensors connected to the panel regardless of their local control scheme. In other words, if any sensor has a status of occupied, this value will read occupied.

BV4

Force all loads ON

Active = all loads ON at priority 1. Inactive = relinquish at 1 and ON at priority 8.
NOTE: This will force all loads connected to the panel ON.

BV5

Force all loads OFF

Active = all loads OFF at priority 2. Inactive = relinquish. NOTE: This will force all loads connected to the panel OFF.

MV1

Scene control

Write scene selection. Range = 1 to 16.

MV2

Demand response (shed) control

Activate room level DR mode: 1 = no shed, 2 = shed mode, permit switch override, 3 = shed mode, prohibit switch override.
NOTE: This will affect all loads connected to the panel.

AV901

MS/TP MAC address

Default is 255 for automatic, writable in the range of 0 to 127.

AV902

MS/TP network speed

Baud rate: 9600, 19200, 38400, 57600, 78600, 115200.

AV903

Input room size

Allows user to write area in square feet from 0 to 65,534, default is 0.

AV904

Room lighting watts

Read total lighting wattage for room.
Total of baseline watts for active relays, or if no baseline wattage for the relays are used, then this is calculated as AV401 * AV501 + any usage from LMRC/LMFC connected via CAT5 to the panel.
NOTE: This does not include used from LMPLs. Use AV906 for plug load controllers.

AV905

Room watts/sq.ft.

Read total room lighting W/ft2.
If the input room size for the entire application area is used and the baseline watts method or AV401 * AV501 method is used, then this object will calculate the aggregate watts per square foot of the whole panel’s application area.
Use of this object is not recommended for use in applications where panels cover mixed areas.

AV906

Room plug load watts

Read total plug load wattage for LMPLs connected to the panel.

36

WARRANTY INFORMATION

INFORMATIONS RELATIVES À LA GARANTIE

INFORMACIÓN DE LA GARANTÍA

Wattstopper warranties its products to be free of defects in materials and workmanship for a period of five (5) years. There are no obligations or liabilities on the part of Wattstopper for consequential damages arising out of, or in connection with, the use or performance of this product or other indirect damages with respect to loss of property, revenue or profit, or cost of removal, installation or reinstallation.

Wattstopper garantit que ses produits sont exempts de défauts de matériaux et de fabrication pour une période de cinq (5) ans. Wattstopper ne peut être tenu responsable de tout dommage consécutif causé par ou lié à l’utilisation ou à la performance de ce produit ou tout autre dommage indirect lié à la perte de propriété, de revenus, ou de profits, ou aux coûts d’enlèvement, d’installation ou de réinstallation.

Wattstopper garantiza que sus productos están libres de defectos en materiales y mano de obra por un período de cinco (5) años. No existen obligaciones ni responsabilidades por parte de Wattstopper por daños consecuentes que se deriven o estén relacionados con el uso o el rendimiento de este producto u otros daños indirectos con respecto a la pérdida de propiedad, renta o ganancias, o al costo de extracción, instalación o reinstalación.

No. 24811 ­ 07/23 rev. 5
© Copyright 2023 Legrand All Rights Reserved. © Copyright 2023 Tous droits réservés Legrand. © Copyright 2023 Legrand Todos los derechos reservados.

800.879.8585 www.legrand.us/wattstopper

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals