OPTONICA NDR-75-12 Power Supply
Features
- Universal AC input / Full range
- Protections: Short circuit / Overload / Over voltage/ Over temperature
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508 (industrial control equipment) approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- 100% full load burn-in test
- 3 years warranty
Applications
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
Description
NDR-75 is one economical slim 75W Din rail power supply series, adapted to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 32mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 90 VAC to 264 VAC and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. NDR-75 is designed with a metal housing that enhances the unit’s power dissipation. With working efficiency up to 89%, the entire series can operate at the ambient temperature between -20°C and 70°C under air convection. It is equipped with a constant current mode for overload protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV BS EN/EN62368-1, etc.) make NDR-75 a very competitive power supply solution for industrial applications.
Model Encoding
MODEL | NDR-75-12 | NDR-75-24 | NDR-75-48 |
---|
OUTPUT
| DC VOLTAGE| 12V| 24V| 48V
RATED CURRENT| 6.3A| 3.2A| 1.6A
CURRENT RANGE| 0 ~ 6.3A| 0 ~ 3.2A| 0 ~ 1.6A
RATED POWER| 75.6W| 76.8W| 76.8W
RIPPLE & NOISE (max.) **Note.2| 80mVp-p| 120mVp-p| 150mVp-p
VOLTAGE ADJ. RANGE| 12 ~ 14V| 24 ~ 28V| 48 ~ 55V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 1200ms, 60ms/230VAC 2000ms, 60ms/115VAC at full
load
HOLD UP TIME (Typ.)**| 60ms/230VAC 12ms/115VAC at full load
INPUT
| VOLTAGE RANGE Note.6| 90 ~ 264VAC 127 ~ 370VDC [DC input
operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 85.5%| 88%| 89%
AC CURRENT (Typ.)| 1.45A/115VAC 0.9A/230VAC
INRUSH CURRENT (Typ.)| 20A/115VAC 35A/230VAC
LEAKAGE CURRENT| <1mA / 240VAC
PROTECTION
| OVERLOAD| 105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after
fault condition is removed
OVER VOLTAGE| 14 ~ 17V| 29 ~ 33V| 56 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Protection type : Shut down o/p voltage, re-power on
to recover
ENVIRONMENT
| WORKING TEMP.| -20 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,
Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY & EMC
(Note 4)
| SAFETY STANDARDS| UL508, TUV BS EN/EN62368-1, EAC TP TC 004
approved;(meet BS EN/EN60204-1)
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/
70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3
Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS
EN/EN55024, BS EN/EN61000-6-2 (BS EN/EN50082-2),
BS EN/EN61204-3, heavy industry level, EAC TP TC 020
OTHERS
| MTBF| 2757.3K hrs min. Telcordia SR-332 (Bellcore) ; 486.2K hrs
min. MIL-HDBK-217F (25℃)
DIMENSION| 32125.2102mm (WHD)
PACKING| 0.51Kg; 28pcs/15.3Kg/1.22CUFT
NOTE
- All parameters NOT specially mentioned are measured at 230VAC input, rated load, and 25°C of ambient temperature.
- Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
- Tolerance: includes set up tolerance, line regulation, and load regulation.
- The power supply is considered a component that will be installed into the final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
- Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
- Derating may be needed under low input voltage. Please check the derating curve for more details.
- The ambient temperature derating of 3.5°C/1000m with fanless models and of 5°C/1000m with fan models for operating altitudes higher than 2000m(6500ft).
Block Diagram
Derating Curve
Static Characteristics
Mechanical Specification
Installation Instruction
This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual.
IMPORTER: Prima Group 2004 LTD, Bulgaria, 1784 Sofia, Mladost 1, bl. 144, Ground Floor; Phone: +359 2 988 45 72;
Specifications
- Model: NDR-75-12, NDR-75-24, NDR-75-48
- Output: 12V, 24V, 48V
- Rated Current: 6.3A, 3.2A, 1.6A
- Rated Power: 75.6W
- Ripple & Noise (max.): 80mVp-p
- Efficiency (Typ.): 85.5%, 88%, 89%
- Dimensions: 32125.2102mm (WHD)
- Weight: 0.51Kg
FAQ
Q: What is the input voltage range for the product?
A: The input voltage range is 90 ~ 264VAC or 127 ~ 370VDC.
Q: What are the compliance standards for EMC Immunity?
A: The product complies with BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55024, BS
EN/EN61000-6-2 (BS EN/EN50082-2), BS EN/EN61204-3, heavy industry level, EAC
TP TC 020.