MEAN WELL MDR-20 Series 20W Single Output Industrial DIN Rail Power Supply Owner’s Manual
- June 1, 2024
- MEAN WELL
Table of Contents
- MEAN WELL MDR-20 Series 20W Single Output Industrial DIN Rail Power
- Product Information
- Product Usage Instructions
- Features
- SPECIFICATION
- Mechanical Specification
- Block Diagram
- Application of DC OK Active Signal
- Derating Curve
- Output Derating VS Input Voltage
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
MEAN WELL MDR-20 Series 20W Single Output Industrial DIN Rail Power
Supply
Product Information
Specifications
- Product Name: 20W Single Output Industrial DIN Rail Power Supply
- Model: MDR-20 series
- GTIN CODE: [GTIN code]
- Features:
- Universal AC input/Full range
- Protections: Short circuit / Overload / Over voltage
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- Built-in DC OK active signal LED indicator for power on
- No load power consumption
Product Usage Instructions
Installation
- Ensure the power supply is suitable for the input voltage.
- Mount the power supply on a DIN rail TS-35/7.5 or 15.
- Connect the input and output terminals following the provided guidelines.
Operation
- Verify the DC OK active signal LED indicator is lit for power indication.
- Avoid overloading the power supply beyond its specified limits.
- Monitor for any abnormal behavior such as overheating.
FAQ
-
Q: What should I do if the DC OK signal LED indicator is not lighting up?
A: Check the input connections and ensure the input voltage is within the specified range. If issues persist, consult the user manual for troubleshooting steps. -
Q: Can this power supply be used in outdoor environments?
A: This power supply is designed for industrial use and can withstand varying environmental conditions; however, it is recommended to protect it from direct exposure to harsh elements.
Features
- Universal AC input/Full range
- Protections: Short circuit / Overload / Over voltage
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- Built in DC OK active signal
- LED indicator for power on
- No load power consumption<0.75W
- 100% full load burn-in test
- 3 years warranty
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
SPECIFICATION
MODEL | MDR-20-5 | MDR-20-12 | MDR-20-15 | MDR-20-24 |
---|
OUTPUT
| DC VOLTAGE| 5V| 12V| 15V| 24V
RATED CURRENT| 3A| 1.67A| 1.34A| 1A
CURRENT RANGE| 0 ~ 3A| 0 ~ 1.67A| 0 ~ 1.34A| 0 ~ 1A
RATED POWER| 15W| 20W| 20W| 24W
RIPPLE & NOISE (max.) **Note.2| 80mVp-p| 120mVp-p| 120mVp-p| 150mVp-p
VOLTAGE ADJ. RANGE| 4.75 ~ 5.5V| 10.8 ~ 13.2V| 13.5 ~ 16.5V| 21.6 ~
26.4V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME Note.5| 500ms, 30ms/230VAC 1000ms,
30ms/115VAC at full load
HOLD UP TIME (Typ.)**| 50ms/230VAC 20ms/115VAC at full load
INPUT
| VOLTAGE RANGE| 85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 76%| 80%| 81%| 84%
AC CURRENT (Typ.)| 0.55A/115VAC 0.35A/230VAC
INRUSH CURRENT (Typ.)| COLD START 20A/115VAC 40A/230VAC
LEAKAGE CURRENT| <1mA / 240VAC
PROTECTION
| ****
OVERLOAD
| 105 ~ 160% rated output power
Protection type : Constant current limiting, recovers automatically after
fault condition is removed
OVER VOLTAGE
| 5.75 ~ 6.75V| 13.8 ~ 16.2V| 17.25 ~ 20.25V| 27.6 ~ 32.4V
Protection type : Shut down o/p voltage, re-power on to recover
FUNCTION| DC OK ACTIVE SIGNAL (max.)| 3.75 ~ 6V / 50mA| 9 ~ 13.5V /
40mA| 11.5 ~ 16.5V / 40mA| 18 ~ 27V / 20mA
ENVIRONMENT
| WORKING TEMP.| -20 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,
Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY & EMC
(Note 4)
| SAFETY STANDARDS| UL508, TUV BS EN/EN62368-1, EAC TP TC 004, BSMI
CNS14336-1, AS/NZS 62368.1 , IS13252(Part1)/IEC60950-1 approved
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/
70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3
Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class B
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2, 3, 4, 5, 6, 8, 11, BS
EN/EN55035,BS EN/EN61000-6-1,BS EN/EN61204-3, light industry level, EAC TP TC
020
OTHERS
| MTBF| 2780.8K hrs min. Telcordia SR-332 (Bellcore) ; 236.9K hrs
min. MIL-HDBK-217F (25℃)
DIMENSION| 22.590100mm (WHD)
PACKING| 0.17Kg; 72pcs/13.2Kg/1.04CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC
input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx