SDR-75 series
Features :
- High efficiency 90% and low power dissipation
- -150% peak load capability
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508 (industrial control equipment) approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- 100% full load burn-in test
- 3 years warranty
https://www.meanwell.com/Upload/PDF/SDR%20DIN%20rail.pdf
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
SPECIFICATION
MODEL | SDR-75-12 | SDR-75-24 | SDR-75-48 |
---|---|---|---|
**OUTPUT** | DC VOLTAGE | 12V | 24V |
RATED CURRENT | 6.3A | 3.2A | 1.6A |
CURRENT RANGE | 0 ~ 6.3A | 0 ~ 3.2A | 0 ~ 1.6A |
RATED POWER | 75.6W | 76.8W | 76.8W |
PEAK CURRENT | 9.375A | 4.69A | 2.34A |
PEAK POWER Note.6 | 112.5W (3 sec.) | ||
RIPPLE & NOISE (max.) Note.2 | 100mVp-p | 100mVp-p | 120mVp-p |
VOLTAGE ADJ. RANGE | 12 ~ 14V | 24 ~ 28V | 48 ~ 55V |
VOLTAGE TOLERANCE Note.3 | ±1.0% | ±1.0% | ±1.0% |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% |
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% |
SETUP, RISE TIME | 1500ms, 60ms/230VAC 3000ms, 60ms/115VAC at full load | ||
HOLD UP TIME (Typ.) | 80ms/230VAC 20ms/115VAC at full load | ||
INPUT | VOLTAGE RANGE Note.7 | 88 ~ 264VAC 124 ~ 370VDC [DC input operation |
possible by connecting AC/L(+),AC/N(-)]
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 88.5%| 89%| 90%
AC CURRENT (Typ.)| 1.4A/115VAC 0.85A/230VAC
INRUSH CURRENT (Typ.)| 30A/115VAC 50A/230VAC
LEAKAGE CURRENT| <1mA / 240VAC
PROTECTION| OVERLOAD| Normally works within 110 ~ 150% rated output power for
more than 3 seconds and then shut down o/p voltage, re-powr on to recover
150 ~ 170% rated power, constant current limiting with auto-recovery within 3
seconds, and then shut down o/p voltage after 3 seconds, re-powr on to recover
OVER VOLTAGE| 14 ~ 17V| 29 ~ 33V| 56 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| 100℃±10℃ (RTH2) detect on main of power transistor
Protection type : Shut down o/p voltage, re-powr on to recover after
temperature goes down
ENVIRONMENT| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 60℃)
VIBRATION| Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z
axes; Mounting: Compliance to IEC60068-2-6
SAFETY & EMC (Note 4)| SAFETY STANDARDS| UL508, TUV BS EN/EN62368-1, AS/NZS
62368.1, EAC TP TC 004 approved, design refer to GL ;(meet BS EN/EN60204-1)
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70%
RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32). BS EN/EN61204-3 Class B,
BS EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS
EN/EN61000-6-2 (BS EN/EN50082-2),
BS EN/EN61204-3, heavy industry level, EAC TP TC 020, SEMI F47 approved
OTHERS| MTBF| 2670.8K hrs min. Telcordia SR-332 (Bellcore) ; 479.8K hrs min.
MIL-HDBK-217F (25℃)
DIMENSION| 32125.2102mm (WHD)
PACKING| 0.51Kg; 28pcs/15.3Kg/1.22CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC input,
rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted
pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load
regulation.
4.The power supply is considered a component which will be installed into a
final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. (as available on
https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left
and right side are recommended when loaded permanently with full power. In
case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds max., please refer to peak loading curves.
7. Derating may be needed under low input voltage. Please check the derating
curve for more details.
8. The ambient temperature derating of 3.5℃/1000m with fanless models and of
5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer:For detailed information, please refer to
https://www.meanwell.com/serviceDisclaimer.aspx
Mechanical Specification
Block Diagram
Peak Loading
Derating Curve
Output derating VS input voltage
File Name:SDR-75-SPEC 2024-02-23
Downloaded from Arrow.com.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>