MEAN WELL SDR-75 Series 75W Single Output Industrial DIN RAIL with Power Supply Owner’s Manual

June 1, 2024
MEAN WELL

75W Single Output Industrial DIN RAIL with Power Supply
SDR-75 series
MEAN WELL SDR-75 Series 75W Single Output Industrial DIN RAIL
with Power Supply

Features :

  • High efficiency 90% and low power dissipation
  • -150% peak load capability
  • Protections: Short circuit / Overload / Over voltage / Over temperature
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • UL 508 (industrial control equipment) approved
  • BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
  • 100% full load burn-in test
  • 3 years warranty

https://www.meanwell.com/Upload/PDF/SDR%20DIN%20rail.pdf

GTIN CODE

MW Search: https://www.meanwell.com/serviceGTIN.aspx

SPECIFICATION

MEAN WELL SDR-75 Series 75W Single Output Industrial DIN RAIL with Power
Supply - Symbol

MODEL SDR-75-12 SDR-75-24 SDR-75-48
**OUTPUT** DC VOLTAGE 12V 24V
RATED CURRENT 6.3A 3.2A 1.6A
CURRENT RANGE 0 ~ 6.3A 0 ~ 3.2A 0 ~ 1.6A
RATED POWER 75.6W 76.8W 76.8W
PEAK CURRENT 9.375A 4.69A 2.34A
PEAK POWER Note.6 112.5W (3 sec.)
RIPPLE & NOISE (max.) Note.2 100mVp-p 100mVp-p 120mVp-p
VOLTAGE ADJ. RANGE 12 ~ 14V 24 ~ 28V 48 ~ 55V
VOLTAGE TOLERANCE Note.3 ±1.0% ±1.0% ±1.0%
LINE REGULATION ±0.5% ±0.5% ±0.5%
LOAD REGULATION ±1.0% ±1.0% ±1.0%
SETUP, RISE TIME 1500ms, 60ms/230VAC 3000ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.) 80ms/230VAC 20ms/115VAC at full load
 INPUT VOLTAGE RANGE Note.7 88 ~ 264VAC  124 ~ 370VDC  [DC input operation

possible by connecting AC/L(+),AC/N(-)]
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 88.5%| 89%| 90%
AC CURRENT (Typ.)| 1.4A/115VAC 0.85A/230VAC
INRUSH CURRENT (Typ.)| 30A/115VAC 50A/230VAC
LEAKAGE CURRENT| <1mA / 240VAC
 PROTECTION| OVERLOAD| Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage, re-powr on to recover
150 ~ 170% rated power, constant current limiting with auto-recovery within 3 seconds, and then shut down o/p voltage after 3 seconds, re-powr on to recover
OVER VOLTAGE| 14 ~ 17V| 29 ~ 33V| 56 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| 100℃±10℃ (RTH2) detect on main of power transistor
Protection type : Shut down o/p voltage, re-powr on to recover after temperature goes down
 ENVIRONMENT| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 60℃)
VIBRATION| Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
 SAFETY & EMC (Note 4)| SAFETY STANDARDS| UL508, TUV BS EN/EN62368-1, AS/NZS 62368.1, EAC TP TC 004 approved, design refer to GL ;(meet BS EN/EN60204-1)
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC  O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32). BS EN/EN61204-3 Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2),
BS EN/EN61204-3, heavy industry level, EAC TP TC 020, SEMI F47 approved
 OTHERS| MTBF| 2670.8K hrs min.  Telcordia SR-332 (Bellcore) ; 479.8K hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 32125.2102mm (WHD)
PACKING| 0.51Kg; 28pcs/15.3Kg/1.22CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds max., please refer to peak loading curves.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.
8. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Mechanical Specification

MEAN WELL SDR-75 Series 75W Single Output Industrial DIN RAIL with Power
Supply - Mechanical Specification

Block Diagram

MEAN WELL SDR-75 Series 75W Single Output Industrial DIN RAIL with Power
Supply - Block Diagram

Peak Loading

MEAN WELL SDR-75 Series 75W Single Output Industrial DIN RAIL with Power
Supply - Peak Loading

Derating Curve

MEAN WELL SDR-75 Series 75W Single Output Industrial DIN RAIL with Power
Supply - Derating Curve

Output derating VS input voltage

File Name:SDR-75-SPEC 2024-02-23
Downloaded from Arrow.com.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals