ESP UDTAKIT Disabled Persons Toilet Alarm Kit Instruction Manual
- June 1, 2024
- ESP
Table of Contents
ESP UDTAKIT Disabled Persons Toilet Alarm Kit
Product Information
Specifications
- Model Options: UDTAKIT White, UDTAKITSS Stainless Steel, UDTAKITG Grey
- Components: Power/Light/Buzzer Module, Reset Module, Pull Cord Module
- Battery Type: A23 Alkaline Battery 12V
FAQ
- Q: What should I do if the alarm keeps sounding?
- A: Check the battery level and replace it if necessary. Ensure proper installation of all components.
- Q: Can the system be self-installed?
- A: No, installation should be done by a qualified electrician to ensure compliance and safety.
Information
Assistance Alarm
Overview
- Pull cord Module
- 1st pull handle to be 100mm from floor.
- 2nd pull handle to be mounted 800/1000mm from floor.
- Reset Module
- Module to be mounted maximum 1200mm from the floor
- Input Power, Light and Buzzer Module
- Activates when the Pull Cord is triggered.
- Also provides system power input
System designed to comply with care standards BS8300 Installation to be carried out by a qualified electrician.
Wiring Configuration
Kit Wiring Configuration
Maximum Wiring Configuration
Operation Guide
For backup battery modules please test/replace the battery a minimum of every
12 months & after any duration the system has been powered directly from the
battery.
An audible tone will sound if the battery is missing or low.
Battery Conditions:
- Battery level normal
- (12v-9.6v) Alarm activation for approximately 10 minutes
- Battery level low
- (9.6v-6v) Alarm activation for approximately 4 minutes
- Battery level 6v or below
- Replace battery
- Battery Type: A23 Alkaline Battery 12V
Contact
Elite Security Products
- Unit 7, Target Park, Shawbank Road, Lakeside, Redditch B98 8YN
- Tel: +44 (0) 1527 51 51 50
- Fax: +44 (0) 1527 51 51 43
- www.espuk.com