TRANE TECHNOLOGIES BAYHTRR Electric Heaters Installation Guide
- September 18, 2024
- Trane Technologies
Table of Contents
TRANE TECHNOLOGIES BAYHTRR Electric Heaters
Product Information
Specifications
- Product: Electric Heaters – Split System Air Handlers
- Capacity: 5-25 Tons
- Compatible with models: TWE051, TWE060, TWE072, TWE076, TWE090, TWE101, TWE120, TWE126, TWE150, TWE156, TWE180, TWE201, TWE240, TWE251, TWE300
Product Usage Instructions
Safety Guidelines
Only qualified personnel should install and service the equipment. Improper
installation or servicing can be hazardous. Ensure all precautions mentioned
in the manual and on equipment tags are followed.
Installation
- Before installation, carefully read the manual provided.
- Ensure proper field wiring and grounding following NEC and local electrical codes.
- Use only R-454 B-rated service equipment for refrigerant handling.
Operation
Before operating the unit, check for proper installation and connections.
Follow all safety precautions to avoid any hazards.
Maintenance
Regular maintenance is essential for optimal performance. Refer to the
manual for maintenance schedules and procedures.
FAQ
-
Q: Who should install and service the equipment?
A: Only qualified personnel should handle installation and servicing to prevent hazards. -
Q: What refrigerant does the equipment use?
A: The equipment described in the manual uses R-454B refrigerant, which is flammable (A2L). Use ONLY R454B rated service equipment and components.
SAFETY WARNING
Only qualified personnel should install and service the equipment. The
installation, starting up, and servicing of heating, ventilating, and air-
conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an
unqualified person could result in death or serious injury. When working on
the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal
safety and the proper operation of this machine depend upon the strict
observance of these precautions.
The three types of advisories are defined as follows:
- WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
- CAUTION Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
- NOTICE Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the
earth’s naturally occurring stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified chemicals that may affect
the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon
(CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs).
Not all refrigerants containing these compounds have the same potential impact
to the environment. Trane advocates the responsible handling of all
refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the
environment, our customers, and the air conditioning industry. All technicians
who handle refrigerants must be certified according to local rules. For the
USA, the Federal Clean Air Act (Section 608) sets forth the requirements for
handling, reclaiming, recovering and recycling of certain refrigerants and the
equipment that is used in these service procedures. In addition, some states
or municipalities may have additional requirements that must also be adhered
to for responsible management of refrigerants. Know the applicable laws and
follow them.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field
wiring MUST be performed by qualified personnel. Improperly installed and
grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these
hazards, you MUST follow requirements for field wiring installation and
grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death
or serious injury. Technicians, in order to protect themselves from potential
electrical, mechanical, and chemical hazards, MUST follow precautions in this
manual and on the tags, stickers, and labels, as well as the instructions
below:
- Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
- When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
- If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
WARNING Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
- All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
- Non-Trane personnel should always follow local regulations.
WARNING R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result
in equipment failure, and possibly fire, which could result in death, serious
injury, or equipment damage.
The equipment described in this manual uses R-454B refrigerant which is
flammable (A2L). Use ONLY R-454B rated service equipment and components. For
specific handling concerns with R-454B, contact your local representative.
Copyright
This document and the information in it are the property of Trane, and may not
be used or reproduced in whole or in part without written permission. Trane
reserves the right to revise this publication at any time, and to make changes
to its content without obligation to notify any person of such revision or
change.
Trademarks
All trademarks referenced in this document are the trademarks of their
respective owners.
Revision History
- Updated model numbers on the front cover.
- Updates to the Heater compatibility table in the Pre-Installation section.
Pre-Installation
Inspection
Remove the contents of the kit from the shipping package and check carefully
for shipping damage. If any damage is found, report it immediately, and file a
claim against the transportation company. Any missing parts should be
immediately reported to your supplier and replaced with authorized parts only.
General
These instructions are for the installation of electric heaters into the split
system heat pump and cooling unit air handlers. Unit-to-heater match up is
described in the table that follows.
These air handlers and heaters are designed so that all Class I (high voltage)
wiring between the heater and unit is accomplished by the method of hard
wiring. Class II wiring (low voltage) is accomplished by push-on type wire
connectors.
Find the heater model number on the heater nameplate. Check the heater
compatibility table that follows to ensure the heater selected is approved for
use with the air handler in which it is to be installed, and that the power
supply is compatible with this heater.
Table 1. Heater compatibility
Unit Model | Voltage | Phase | Heaters |
---|---|---|---|
TWE060*1 | 208-230 | 1 | BAYHTRP106, BAYHTRS112, BAYHTRT117, BAYHTRS123 |
TWE060*3 | 208-230 | 3 | BAYHTRP305, BAYHTRS310, BAYHTRS315, BAYHTRP325 |
TWE060*W | 575 | 3 | BAYHTRPW05, BAYHTRSW10, BAYHTRSW15, BAYHTRPW25 |
TWE0901, TWE1201 | 208-230 | 1 | BAYHTRP106, BAYHTRS112, BAYHTRT117*, |
BAYHTRS123, BAYHTRP129
TWE0723, TWE0903, TWE1203| 208-230| 3| BAYHTRP305, BAYHTRS310,
BAYHTRS315, BAYHTRP325
TWE0903, TWE1203| 208-230| 3| BAYHTRP335
TWE101D| 380-151/50Hz| 3| BAYHTRP435
TWE051D, TWE0604, TWE072D, TWE0724, TWE076D, TWE0904, TWE101D,
TWE1204| 380-415/50Hz
460V/60Hz
| 3| BAYHTRP405, BAYHTRS410, BAYHTRS415, BAYHTRP425
TWE0904, TWE1204| 460V/60Hz| 3| BAYHTRP435
TWE072W, TWE090W, TWE120W| 575| 3| BAYHTRPW05, BAYHTRSW10, BAYHTRSW15,
BAYHTRPW25
TWE090W, TWE120W| 575| 3| BAYHTRPW35
TWE1503, TWE1803, TWE2403, TWE3003| 208-230| 3| BAYHTRT310, BAYHTRR320,
BAYHTRR330, BAYHTRR350
TWE126D, TWE1504, TWE156D, TWE1804, TWE201D, TWE2404, TWE251D, TWE3004|
380-415/50Hz
460V/60Hz
| 3| BAYHTRT410, BAYHTRR420, BAYHTRR430, BAYHTRR450
TWE150W, TWE180W, TWE240W, TWE300W| 575| 3| BAYHTRTW10, BAYHTRRW20,
BAYHTRRW30, BAYHTRRW50
Voltages indicated are for Air Handlers.
For heater rated voltages, see heater nameplates.
Parts List
Qty | Description |
---|---|
1 | Heater (with enclosure) |
2 | Cable clamps |
2 | Screws (for cable clamp) |
2 | Adapter harnesses |
2 | Bullet wire ties |
4 | Regular wire ties |
1 | Plastic bushing |
11 or 20 | Screws (depending on heater kit) |
1 | Gasket |
Installation
WARNING Rotating Components!
Failure to disconnect power before servicing could result in rotating
components cutting and slashing technician which could result in death or
serious injury.
Disconnect all electric power, including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the power can not be
inadvertently energized.
Note: All phases of this installation must comply with national, state, and local codes.
-
Remove duct flange from around air discharge on top of the air handler. Retain screws and flange for
(optional) installation on top of the heater. See Figure 1, p. 6 and Figure 2, p. 6. -
Remove the control wire knockout (Knockout #1) from top of air handler and insert plastic bushing supplied with heater. This knockout will also be used if single point power entry is utilized.
Important: For ventilation purposes, Heaters 112, 117, 123, 129, 325, and 335 require that an additional knockout (knockout #2) be removed (see Figure 1, p. 6). When using BAYHTR325 with a TWE0603 (5 ton) air handler, the heater baffle must be removed (see Figure 3, p. 7). -
Remove air handler access panel and control box cover.
Note: Apply gasket to heater see heater gasket installation sheet. -
Place heater on air handler and secure in place with the screws provided.
Low Voltage Wires (24 Volts)
The heater kit includes two adapter harnesses for the low voltage wiring. If
heater control box is equipped with a low voltage terminal block, use the
adapter harness in the kit that has PPM13 and quick connect terminations. If
the low voltage terminal block is not present and the control box is equipped
with Symbio 700 controller, use the adapter harness with PPM13 and PPF14
attached. Refer to the schematics for the appropriate connection points.
- If the heater control box is equipped with a low-voltage terminal block, there will be 1 brown wire and 1 black wire for a single-stage heat control connection. For two-stage heat, there will be 1 brown wire, 1 black wire, and 1 orange wire.
- Route the 2 or 3 low voltage wires down through the plastic bushing in the knockout #1 to the low voltage terminal block see Figure 4, p. 8 and Figure 5, p. 9. Wire according to heater wiring diagram.
- Wire ties and cable clamps supplied should be used to secure the wires from the heater to the air handler control box in a location that will not allow them to interfere with any moving parts.
High Voltage Wires
NOTICE Use Copper Conductors Only!
Failure to use copper conductors could result in equipment damage as the
equipment was not designed or qualified to accept other types of conductors.
-
For single point power entry, route 2 or 3 red wires, down through the plastic bushing in knockout #1 and into the air handler control box.
-
For single phase there will be 2 red wires, and for 3 phase there will be 3 red wires.
-
The 2 or 3 red wires should be hard wired to the bottom contacts of the air handler contactor per the wiring diagram for the standard air handlers. For the 2-speed VFD and SZVAV the wires connect to the fuse block.
Important: When the dual point power entry option is used, the high voltage wires, for single point power entry, should remain capped, coiled up and clamped inside the heater control box. -
When using dual point power entry, knockouts on the control end of both the air handler and the heater are to be used. See Figure 4, p. 8 and Figure 5, p. 9 for location of each.
-
Replace air handler control box cover.
-
Replace air handler access panel.
-
Replace control box panel on accessory heater.
-
Check blower rotation. If incorrect, change positions of any two power leads at fan contactor (F) or fuse block. After electrical hookup has been completed, duct work can be assembled. The duct flanges removed from the air handler, can be secured in place on top of the heater and the duct work can be attached or the flange can be discarded and the duct can be fashioned to fit up to the heater.
Notes:
- For power supply to heater only see the heater nameplate to determine “MCA” and over current protection device values.
- For single point power entry option (heater and blower motor) see the “heater installed” nameplate on the air handler for “MCA” and over current protection device values.
- When electric heater accessory is used single-point power entry or dual-point power entry is field optional. Single point power entry option is through electric heater only.
Notes:
- For power supply to heater only see the heater nameplate to determine “MCA” and over current protection device values.
- For single point power entry option (heater and blower motor) see the “heater installed” nameplate on the air handler for “MCA” and over current protection device values.
- When electric heater accessory is used single point power entry or dual point power entry is field optional. Single point power entry option is through electric heater only.
Wiring Diagrams
Table 2. Wiring diagram matrix
Voltage | Diagram Number | Description |
---|---|---|
208-240V | 436758590001 | DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT |
12.98/17.28KW 208-240V/1PH
436757600001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 37.42/49.84KW
208-240V/3PH
436757610001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 3.7/5KW or
7.48/9.96KW 208-240V/3PH
436757620001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 11.25/14.96KW
208-240V/3PH
436757630001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 18.71/24.92KW
208-240V/3PH
436757640001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 26.20/34.88KW
208-240V/3PH
436757690001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 14.96/19.92KW
208-240V/3PH
436757700001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 7.50/10.0KW
208-240V/3PH
436757710001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 4.33/5.76KW
208-240V/1PH
436757730001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 8.65/11.52KW
208-240V/1PH
436757740001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 17.30/23.04KW
208-240V/1PH
436757750001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 21.65/28.80KW
208-240V/1PH
436757760001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 22.50/29.92KW
208-240V/3PH
460/575V| 436766640001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT
5.00/9.96KW 460/575V/3PH
436766650001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 14.96KW
460/575V/3PH
436766660001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 24.92KW
460/575V/3PH
436766670001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 34.88KW
460/575V/3PH
436766680001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 10.0/19.92KW
460/575V/3PH
436766690001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 49.84KW
460/575V/3PH
436766700001| DIAGRAM; SCHEMATIC/CONNECTION, ELECTRIC HEAT 29.92KW
460/575V/3PH
Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.