Versa LAMP-ZW2 Z-Wave Dimmer Plug Module Instruction Manual
- June 1, 2024
- versa
Table of Contents
Z-Wave Dimmer Plug(800S)
• LAMP-ZW2 •
Specification
Input: 125VAC 60Hz
Frequency: 908.42 MHz
Dimmable CFL/LED
Loading: 200W Incandescent 100W
Indoor use in dry location
Features:
- Z-Wave on / off + dimmer control.
- Grounded 3-wire power connection for safety.
- Remember and restore on/off status after power failure.
- Built-in Z-Wave Plus signal repeater to extend network range
- S2 security and 800 Z-Wave chip for reliable wireless communication.
- Work with all certificated Z-Wave controllers.
- Support Long Range.
Min brightness level setting( Refer to Parameter 11)
- Press the button 5 times quickly, the LED indicator flashes slowly to enter the setting “Min brightness” mode. The lamp will adjusts to the min brightness automatically.
- Hold the button to adjust the brightness of the bulb, select the appropriate brightness to set the min brightness.
- Press the button 5 times quickly to confirm it (the min brightness setting is completed).
The LED indicator will flashes 3 times.
Max brightness level setting( Refer to Parameter 12)
- Press the button 10 times quickly, the LED indicator flashes slowly to enter the setting “Max brightness” mode. The lamp will adjusts to the max brightness automatically.
- Hold the button to adjust the brightness of the bulb, select the appropriate brightness to set the max brightness.
- Press the button 10 times quickly to confirm it (the max brightness setting is completed).
The LED indicator will flashes 3 times.
Remark: If the setting is not confirmed at Step 3, the setting mode will be exited after 10S.
Z-WAVE INTEROPERABILITY
devices from other manufacturers and/or other applications. All non-battery
operated nodes This product can be included and operated in any Z-Wave network
with other Z-Wave certified within the network will act as repeaters
regardless of vendor to increase the reliability of the network. This Device
supports Lifeline (association group 1) supporting 1 node for lifeline
communication. Group 1 must be assigned the Node ID of the primary controller
where unsolicited notifications will be sent.
The Z-Wave controller should set this association automatically after
inclusion.
Lifeline association only supports the “Device Reset Locally” function.
Adding Device To Z-Wave Network for QR CODE
Scan here for SmartStar inclusion
Note: DSK Code can be found on the packaging box.
Do not remove or damage them.
Z-Wave Network Configuration
Adding Device To Z-Wave Network
- Follow the instructions for your Z-Wave certified controller to add a device to the Z-Wave network.
- Once the controller is ready to add your device, press the Manual/ Program button on the smart plug 3 times quickly. The blue LED will flash quickly.
Now, you have completed control to turn your device ON / OFF according to
groups, schedules and interactive automation programmed by your controller. If
your Z-Wave certified controller features remote access, you can control your
device from your mobile devices.
Again: If you have issues with pairing / including, please move the device as
close as possible to the hub and try again–you can move to your final location
when completed.
Note:
- If the manual button doesn’t light up after pressing 3 times, please reset the device: press the button twice quickly then hold a 3rd press for 10 seconds.
- The flashing purple light means the device is already paired and also in exclusion mode.
If adding fails, please do a z-wave exclusion on your z-wave controller and re-add it.
To Remove The Device
- Follow the instructions for your Z-Wave certified controller to remove a device from the Z-Wave network.
- Once the controller is ready to remove your device, press the manual / program button on the smart plug 3 times quickly.
To Return The Device To Factory Defaults
Manual: Press the button twice quickly then hold a 3rd press for 10 seconds.
Host reset: Remove it from hub, the device will be restore to factory default.
Add QR Code For LR
-
The device is compatible with smartstart.
SmartStart enabled products can be added into a Z-Wave network by scanning the Z-Wave QR Code found on the top of the outlet or the back of the box with a controller providing SmartStart inclusion. No furthe action is required and the SmartStart product will be added automaticaly within 10 minutes of being switched on and in the network vicinity. -
Note: Z – Wave Long Range device can only support be included via SmartStart. Extract the DSK from end device and paste it into the DSK Value in PC Controller, make sure the Long Range’ option is ticked.
Association Group
Group 1 supports 1 node ID,Group 2 Supports maximum of 5 node ID’s
Association Group 1: Z-Wave Plus Lifeline
Association Group 2: Send Basic Set ON / Off
Warranty
Our Products warrant this product to be free from manufacturing defects for a
period of one year from the original date of consumer purchase. This warranty
is limited to the repair or replacement of this product only and does not
extend to consequential or incidental damage to other products that may be
used with this product. This warranty is in lieu of all other warranties,
expressed or implied. Some states do not allow limitations on how long an
implied warranty lasts or permit the exclusion or limitation of incidental or
consequential damage, so the above limitations may not apply to you. This
warranty gives you specific rights, and you may also have other rights which
vary from state to state.
Parameter Settings
LED Indicator
This parameter can access you to choose the LED indicator to be on when the
plug(light) is on/off, or LED indicator remains on/off all times.
(LED flashes 3 times when the configuration parameter changed.)
— Parameter =2, size =1byte, Default =0
Value=0 (default) LED is On when switch (light) is Off.
Value=1 — LED is On when switch (light) is On.
Value=2 — LED is always Off.
Value=3 — LED is always On.
Auto Turn-Off Timer
This parameter can access you to set a timer to make the switch turn off
automatically after the switch turns on.The numberentered as value corresponds
to number of minutes. Operation: Set up on the hub.
(LED flashes 3 times when the configuration parameter changed.)
— Parameter =4, Size=4,Value: 0– 65535(minutes);
Value=0(default) disable
Auto Turn-On Timer
This parameter can access you to set a timer to make the switch turn on
automatically after the switch turned on.The numberentered as value
corresponds to number of minutes.
Operation: Set up on the hub.
(LED flashes 3 times when the configuration parameter changed.)
— Parameter =6, Size=4,Value: 0– 65535(minutes);
Value=0(default) disable turn on the outlet
Night Light Set
This parameter can access you to set a specific brightness for the light when
you want to make it as a night light.
(LED flashes 3 times when the configuration parameter changed.)
— Parameter =7, Size=1, Default = 2
Value=1 — 10% brightness
Value=2 — 20% brightness
Value=10 — 100% brightness
Restores state after power failure
This parameter can access you to set the switch to be on/off after power
failure.
Operation: quickly press 8 times to change this parameter.
(LED flashes 3 times when the configuration parameter changed.)
Parameter=8,Size=1,Value=2(default)
Value=0 — The switch is off regardless of the state prior to power failure.
Value=1 — The switch is on regardless of the state prior to power failure.
/
Value=2(default) memory state before power failure
This switch will be return to state prior to the power failure after power is
restored.
Dimmer speed (ON/OFF Control)
This parameter can access you to set the time from maximum brightness to
minimum brightness or minimum brightness to maximum brightness (Only when turn
ON / OFF the light )
Operation: Set up on the hub.
(LED flashes 3 times when the configuration parameter changed.)
Value=0 — instant on/off
Parameter=9,Size=1, Default = 2
Value=1— from 0x63 to 0x00 or from 0x00 to 0x63 need 1s
Value=2 — from 0x63 to 0x00 or from 0x00 to 0x63 need 2s
Value=10 — from 0x63 to 0x00 or from 0x00 to 0x63 need 10s
/
Dimmer speed (Dimmer Control)
This parameter can access you to set the time from maximum brightness to
minimum brightness
or minimum brightness to maximum brightness.
(Only when hold it to change the brightness or control from HUB).
Operation: Set up on the hub.
(LED flashes 3 times when the configuration parameter changed.)
Parameter=10,Size=1, Default = 4
Value=1 — from 0x63 to 0x00 or from 0x00 to 0x63 need 1s
Value=2 — from 0x63 to 0x00 or from 0x00 to 0x63 need 2s
Value=10 — from 0x63 to 0x00 or from 0x00 to 0x63 need 10s
/
Multilevel minimum value can be set
Operation: quickly press 5 times to change this parameter.
(LED flashes 3 times when the configuration parameter changed.)
—Parameter=11,Size=1,Default = 10
Value=0 — disable
Value=1
/
Value=99
Multilevel maximum value can be set
Operation: quickly press 10 times to change this parameter.
(LED flashes 3 times when the configuration parameter changed.)
—Parameter=12,Size=1,Default = 99
Value=0 — disable
Value=1
/
Value=99
FCC / IC
This device complies with part 15 of the FCC and Industry Canada license-
exempt RSS standard(s). Operation s subjected to the following two conditions:
(1) This device may not cause harmful interference, (2) Ths device must accept
any interference received, including interference that may cause undesred
operation.
FCC NOTE: The manufacturer is not responsible for any radio or TV
interference caused by unauthorized modifications to this equipment. Such
modifications could void the user’s authority to operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if
not installed and used in accordance with the instructions may cause harmful
interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment
does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio / TV technican for help.
Important note: To comply with the FCC RF exposure compliance
requirements, no change to the antenna or the device is permtted. Any change
to the antenna or the device could result n the device exceeding the RF
exposure requirements and void user’s authority to operate the device.
This equipment complies with FCC radiation exposure limits set forth for an
uncontrolled environment. This equipment should be installed and operated with
minimum distance 20cm between the radiator & your body.
CAUTION – PLEASE READ!
This device is intended for installation in accordance with the National
Electric Code and local regulations in the United States, or the Canadian
Electrical Code and local regulations in Canada If you are unsure or
uncomfortable about performing this installation
consult a qualified electrician.
WARNING
RISK OF FIRE / RISK OF ELECTRICALSHOCK / RSK OF BURNS TO REDUCE THERISK OF
ELECTRICSHOCK, THIS PRODUCT HAS A GROUNDING TYPE PLUG THAT HAS A THIRD
(GROUNDING) PN. THS PLUG WLL ONLY FIT INTO A GROUNDING TYPE POWER OUTLET. IF
THE PLUG DOES NOT FITNTO THE OUTLET, CONTACT A QUALFIED ELECTRCIANTO INSTALL
THE PROPER OUTLETDO NOT CHANGE THE PLUG IN ANY WAY. CONTROLLING APPLIANCES:
CAUTON:
TO REDUCETHE RSK OF OVERHEATING ANDPOSSIBLE DAMAGE TO OTHER EQUIPMENT
- DO NOT EXCEED RATINGS
- DO NOT USE TO CONTROL ANY DEVICE
WHERE UNINTENDED OPERATION COULD
CAUSE UNSAFE CONDITIONS (HEAT LAMP, SUN LAMP, ETC.)
MEDICAL EQUIPMENT
Please DO NOT use this switch to control Medical or Life Support equipment.
Z-Wave devices should never be used to control the On / Off status of Medical
and / or Life Support equipment.
CONTROLLING APPLIANCES
Please exercise EXTREME CAUTION when using Z-Wave devices to control
appliances.
Reason being is because the appliance you want to control may be in a separate
room and if unintentional behavor occurs (such as adevice turning on or off –
either intentonally via schedules, or unintentionally via network error) this
event may lead to a hazardous conditon.
For these reasons, please note the following suggestions:
- Do not include Z-Wave devices in Groups or Scenes if they control appliances.
- Do not use Z-Wave devices to control electric heaters or any other appliances which may present a hazardous condition due to unattended, unintentional, or automatic power control.
Generic Device Class:
0x11-GENERIC_TYPE_SWITCH_MULTILEVEL
Specific Device Class:
0x00-SPECIFIC_TYPE_NOT_USED
Command Classes:
0x5E-COMMAND_CLASS_ZWAVEPLUS_INFO_V2,
0x26-COMMAND_CLASS_SWITCH_MULTILEVEL_V4,
0x70-COMMAND_CLASS_CONFIGURATION_V4,
0x85-COMMAND_CLASS_ASSOCIATION_V2,
0x8E-COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3,
0x59-COMMAND_CLASS_ASSOCIATION_GRP_INFO_V3,
0x55-COMMAND_CLASS_TRANSPORT_SERVICE_V2,
0x87-COMMAND_CLASS_INDICATOR
0x86-COMMAND_CLASS_VERSION_V3,
0x72-COMMAND_CLASS_MANUFACTURER_SPECIFIC_V2,
0x5A-COMMAND_CLASS_DEVICE_RESET_LOCALLY,
0x73-COMMAND_CLASS_POWERLEVEL,
0x9F-COMMAND_CLASS_SECURITY_2,
0x6C-COMMAND_CLASS_SUPERVISION,
0x7A-COMMAND_CLASS_FIRMWARE_UPDATE_MD_V5
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>