Senseca PBS83M BAROsense Barometric Transmitter User Manual
- June 2, 2024
- senseca
Table of Contents
- Senseca PBS83M BAROsense Barometric Transmitter
- Specifications
- Technical Specifications
- Frequently Asked Questions (FAQ)
- Introduction
- Technical specifications
- Installation
- Configuration and measurement
- ASCII proprietary protocol
- Modbus-RTU protocol
- Maintenance
- Safety instructions
- Accessories ordering codes
- WARRANTY
- TECHNICAL INFORMATION
- DISPOSAL INFORMATION
- ABOUT COMPANY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Senseca PBS83M BAROsense Barometric Transmitter
Specifications
- Barometric pressure Sensor: Piezoresistive
- Measuring range: 300-1100 hPa (Configurable for the analog output: default 600-1100 hPa)
- Accuracy: See detailed specifications below
- Long-term stability: See detailed specifications below
Technical Specifications
Barometric Pressure Sensor
- Measuring Range: 300-1100 hPa (Configurable for analog output: default 600-1100 hPa)
- Resolution: See table below
- Accuracy: Detailed accuracy information provided below
- Long-term Stability: Detailed stability information provided below
Capacitive Sensor
- Measuring Range: 0-100%
- Resolution: 0.1%
- Accuracy: Detailed accuracy information provided below
- Temperature Drift: Detailed temperature drift information provided below
- Response Time: T63 < 4 s (air speed = 2 m/s, without filter)
- Long-term Stability: Detailed stability information provided below
Dew Point, Absolute Humidity, and Wet Bulb Temperature
- Output: RS485 with Modbus-RTU or ASCII proprietary protocol
- Analog Output: Optional, selectable in current (0/4-20 mA) or voltage (0-1 V, 0-5 V, or 0-10 V depending on the model)
- Power Supply:
- PBS83M0: 7-30 Vdc
- PBS83MW and PBS83MX: 8-30 Vdc
- PBS83MY: 15-30 Vdc
Installation
To install the BAROsense PBS83M series barometric transmitter, follow the
steps below:
- Choose a suitable location for mounting the transmitter.
- Ensure proper power supply within the specified voltage range.
- Connect the necessary cables for communication (RS485) and optional analog output if required.
- If using an optional LCD display, connect it as per the provided instructions.
- If using a T/RH probe, ensure it is connected correctly for combined temperature and relative humidity measurements.
- If using the optional static port with a support bracket, install it to minimize dynamic pressure effects due to wind.
Frequently Asked Questions (FAQ)
-
What is the default analog output configuration for the BAROsense PBS83M series?
The default analog output configuration is 4-20 mA for most models. However, it can be user-configurable to different ranges such as 0-20 mA or specific voltage ranges depending on the model. -
Can I connect multiple BAROsense PBS83M transmitters to create a sensor network?
Yes, the digital RS485 output allows for connecting multiple transmitters over long distances to create a sensor network for comprehensive environmental monitoring.
Introduction
- BAROsense is a barometric transmitter equipped with a precision piezo-resistive pressure sensor with integrated temperature sensor. The pressure and temperature measurements are digitally processed to obtain a pressure output value compensated over the whole transmitter temperature operating range.
- The sensor is factory calibrated in multiple points and has excellent time stability and re-peatability.
- The pressure can be expressed in different user-selectable units of measurement.
- The instrument has a digital RS485 output with MODBUS-RTU or proprietary proto-col. As option, it can be supplied with an additional analog output, which can be selected by the user in current or voltage via an internal jumper. The current output is user configurable 0…20 mA or 4…20 mA (default), while the voltage output must be defined when ordering (0…1 V, 0…5 V or 0…10 V).
- The transmitter digital output enables the transmission of the measurements over long distances and connects the transmitter to sensors networks.
- Optional LCD display.
- Optional input for combined temperature and relative humidity probe. With the external probe connected, the instrument calculates the dew point, the absolute humidity and the wet bulb temperature.
- Available as an accessories a static port with support bracket to minimize the effect of dynamic pressure due to the wind in open field measurements.
- The table below highlights the features included in the various models of the series.
| Output| T/RH
probe
|
LCD
---|---|---|---
Model| Digital RS485| Analog
PBS83M00 …|
Ö
|
—
| —|
…= 0 no
…= L yes
PBS83M0C …| Ö
PBS83MW0 …|
Ö
| Configurable 4…20 mA (default),
0…20 mA or 0…1 V
| —
PBS83MWC …| Ö
PBS83MX0 …|
Ö
| Configurable 4…20 mA (default),
0…20 mA or 0…5 V
| —
PBS83MXC …| Ö
PBS83MY0 …|
Ö
| Configurable 4…20 mA (default),
0…20 mA or 0…10 V
| —
PBS83MYC …| Ö
Technical specifications
Barometric pressure
Sensor| Piezoresistive
Measuring range| 300…1100 hPa
Configurable for the analog output: default 600…1100 hPa
Resolution| See table below
Accuracy| ± 0.5 hPa (700…1100 hPa) @ 20 °C
±1 hPa (500…1100 hPa) / ±1.5 hPa (300…500 hPa) @ T=(0…60 °C)
Long-term stability| < ±1 hPa/year
Relative humidity ( optional – external T/RH probe is required )
Sensor| Capacitive
Measuring range| 0…100%
Resolution| 0.1%
Accuracy| ± 2.5% (0..85%) / ± 3.5% (85…100%) @ T=23 °C
Temperature drift| 0.05%/K (0…60 °C)
Sensor operating temp.| -40…+105 °C (R.H. max=[100-2*(T-80)] @ T=80…105 °C)
Response time| T63 < 4 s (air speed = 2 m/s, without filter)
Long-term stability| < 1%/year (@ 23 °C and 30…70%)
Temperature ( optional – external T/RH probe is required )
Sensor| PTAT integrated in humidity module
Measuring range| -40…+105 °C
Resolution| 0.1 °C
Accuracy| ± 0.2 °C in the range 0…+60 °C
± (0.2 – 0.05 * T) °C in the range T=-40…0 °C
± [0.2 + 0.032 * (T-60)] °C in the range T=+60…+105 °C
Long-term stability| 0.05 °C/year
Calculated quantities ( optional – external T/RH probe is required )
Dew point, absolute humidity and wet bulb temperature
General specifications
Output| RS485 with Modbus-RTU or ASCII proprietary protocol
Optional analog output, selectable in current (0/4…20 mA) or volt- age (0…1 V, 0…5 V or 0…10 V, depending on the model)
Current output load resistance: RL < (Vdc-7)/0,022) Voltage output load resistance: RL > 10 kW
Power supply| PBS83M0… : 7…30 Vdc
PBS83MW… and PBS83MX… : 8…30 Vdc
PBS83MY… : 15…30 Vdc
Consumption| 4 mA @ 24 Vdc (+ output current if current output is used)
Connection| Internal screw terminal header / PG7 cable gland for power supply
and output. Optional M12 connector for the T/RH external probe.
Operating conditions| -40…+60 °C (-20…+60 °C con LCD) / 0…100%RH
Compatible media| Air and dry gases
---|---
Materials| Transmitter: Polycarbonate, pressure input in nickel-plated brass
Static port (optional): ASA
Support bracket (optional): Aluminium alloy
Housing dimensions| 120 x 80 x 55
Weight| 250 g approx.
570 g approx. the static port with support bracket
Protection degree| IP65
Units of measurement available and corresponding resolution
- With the MODBUS-RTU protocol, two different input registers are available for the pressure measurement, with different resolution: IR 0 (32-bit) and IR 2 (16-bit).
- With the ASCII proprietary protocol, the resolution is unique.
| Resolution
---|---
Unit of measurement| ASCII proprietary protocol Modbus protocol IR 0 (32-bit)| Display
Modbus protocol IR 2 (16- bit)
Pa| 1 Pa| 10 Pa
hPa| 0.01 hPa| 0.1 hPa
kPa| 0.001 kPa| 0.01 kPa
mbar| 0.01 mbar| 0.1 mbar
bar| 0.00001 bar| 0.0001 bar
atm| 0.00001 atm| 0.0001 atm
psi| 0.0001 psi| 0.001 psi
mmHg| 0.01 mmHg| 0.1 mmHg
inHg| 0.001 inHg| 0.01 inHg
mmH2O| 0.1 mmH2O| 1 mmH2O
inH2O| 0.01 inH2O| 0.1 inH2O
kg/cm2| 0.00001 kg/cm2| 0.0001 kg/cm2
Torr| 0.01 Torr| 0.1 Torr
Installation
- The transmitter is wall mounted using the two holes on the back (open the cover to access the holes and the terminal header for electrical connections).
- It is advisable to mount the transmitter so that the pressure input is facing down-wards, in order to reduce the accumulation of dust and dirt on the input.
- For outdoor installation, the use of the optional static pressure port is recommended, in order to minimize the measurement error caused by the wind flow on the pressure input (the measurement deviation due to wind is less than 0.3 hPa @ 20 m/s if the static port is used). The static port includes a support bracket suitable for fixing to a Ø30…50 mm mast.
Electrical connections
- The transmitter has an internal screw terminal header for connecting the power supply and the outputs, and optionally an M12 connector for connecting the external temper-ature and relative humidity probe.
Terminal N°| Function
---|---
1| RS485 D-
2| GND
3| RS485 D+
4| Power supply positive (+Vdc)
5| GND
6| GND
7| Analog output (OUT) - The analog output, if present, can be in current or voltage, configurable via the jump-er to the right of the terminal header.
- To the left of the terminal header there is a built-in line termination that can be con-nected or removed through a short jumper. To connect the termination, place the short jumper between the “RT” and “CLOSE” indications. To remove the termination, place the short jumper between the “RT” and “OPEN” indications.
Configuration and measurement
- The configuration of the instrument and the reading of the measurements can be done via the RS485 serial output, both with the proprietary protocol and with the MODBUS-RTU protocol.
- In the first 10 seconds after the instrument power on, it is always active the proprie-tary protocol. After 10 seconds from power on, the operating protocol is activated, which by default is the MODBUS-RTU protocol.
- It is possible to keep the proprietary protocol active even after 10 seconds from power on by sending, before the 10 seconds expire, the command @ of the proprietary protocol. The proprietary protocol can be set as operating protocol by means of the DP0 command.
- By default, the instrument has MODBUS address 1 and communication parameters 19200, 8E1. Different parameters can be set using the proprietary protocol or the MODBUS-RTU protocol.
- The commands of the proprietary protocol and the registers of the MODBUS-RTU pro-tocol are described in detail in the following chapters.
Analog output:
- The output is current or voltage depending on the configuration of the IOUT / VOUT jumper on the board. By default, the current output is 4…20 mA and the voltage out-put is 0…1, 0…5 V or 0…10 V depending on the model.
- The analog output is preset to correspond to the pressure range 600…1100 hPa.
- Using the proprietary protocol or the MODBUS-RTU protocol it is possible:
- to associate the analog output to a different pressure range, within the full measuring range;
- to associate the analog output to the temperature or relative humidity measured by the optional external probe or to the calculated humidity quantities;
- to add/remove an offset to the output minimum value (e.g., change from 0…10 V to 2…10 V or from 4…20 mA to 0…20 mA);
- to reverse the direction of the output, so that the output decreases as the meas-urement increases.
- In the event of a measurement error, the output goes to a value 10% higher than the full scale (e.g., 11 V if the output is 0…10 V or 22 mA if the output is current).
Status of the transmitter:
The transmitter version with LCD option has two front LEDs: the green LED
indicates the presence of the external power supply (blinks once per second),
the red LED indi-cates the presence of any measurement errors (normally off,
it blinks twice per sec-ond if in error).
ASCII proprietary protocol
- To use the ASCII proprietary protocol, it is necessary to connect the instrument to the PC via a RS485/USB or RS485/RS232 converter and use a standard serial communica-tion program. In the serial communication program, set the COM port number to which the instrument is connected and the communication parameters as follows:
- If the MODBUS-RTU protocol is set as the operating protocol in the instrument (default), set the Baud Rate 57600 and the parameters 8N2 in the serial commu-nication program, then power cycle the instrument and send the command @ within 10 seconds from the instrument power on.
- If the proprietary protocol is already set as the operating protocol in the instru-ment, it is possible to operate with Baud Rate 57600 and parameters 8N2 by sending the command @ within 10 seconds from the instrument power on, or you can let the 10 seconds pass without sending the command @ and operate with the communication parameters set in the instrument (default 19200, 8E1).
- To change the instrument configuration, the serial command CAL USER ON must be sent first (the instrument replies with USER CAL MODE ON). The command CAL USER ON is automatically disabled after a few minutes of inactivity. If the settings should be only read, the command CAL USER ON is not required.
Below is the list of the serial commands.
Instrument information:
Command | Reply | Description |
---|---|---|
G0 | Model | Instrument model |
G1 | & Revision | Instrument hardware revision |
G2 | SN=nnnnnnnn | Instrument serial number |
G3 | Firm.Ver.=x.y | Instrument firmware revision |
G4 | Firm.Date=yyyy/mm/dd | Date of firmware revision |
GC | Fact.Calib.Date= yyyy/mm/dd | Date of factory calibration |
Protocol:
Command | Reply | Description |
---|---|---|
@ | & | Keeps the proprietary protocol operational even after 10 seconds from |
instrument power on. It must be sent within 10 seconds from instrument power
on.
DPn| &|| Sets the operating protocol:
§ Proprietary if n=0
§ MODBUS-RTU if n=1
Default : MODBUS-RTU (n=1)
GP| & n|| Reads the operating protocol set in the instrument.
SM| &|| Activates the MODBUS-RTU protocol immediately.
CMAn| &|| Sets the MODBUS-RTU address (1…247) to n.
Default : 1
RMA| & n|| Reads the MODBUS-RTU address.
Warning: after sending the DP1 command, the instrument remains with the proprietary pro-tocol. Send the command SM to activate the MODBUS-RTU protocol immediately, or power cy-cle the instrument.
RS485 communication parameters:
Command | Reply | Description |
---|---|---|
CMBn | & | Sets the Baud Rate: |
§ 1200 if n=0 ▪ 19200 if n=4
§ 2400 if n=1 ▪ 38400 if n=5
§ 4800 if n=2 ▪ 57600 if n=6
§ 9600 if n=3 ▪ 115200 if n=7
Default : 19200 (n=4)
RMB| & n|| Reads Baud Rate setting
CMPn| &|| Sets parity and stop bits:
§ 8N1 if n=0 [No parity, 1 stop bit]
§ 8N2 if n=1 [No parity, 2 stop bits]
§ 8E1 if n=2 [Even parity, 1 stop bit]
§ 8E2 if n=3 [Even parity, 2 stop bits]
§ 8O1 if n=4 [Odd parity, 1 stop bit]
§ 8O2 if n=5 [Odd parity, 2 stop bits] The number of data bits is fixed to 8.
Default : 8E1 (n=2)
RMP| & n|| Reads the setting of parity and stop bits.
CMWn| &|| Sets waiting time after transmission with MODBUS-RTU protocol:
§ Immediate reception if n=0 (violates protocol)
§ Waiting 3.5 characters if n=1 (respects protocol)
Default : Immediate reception (n=0)
RMW| & n|| Reads the setting of waiting time after transmission with MODBUS- RTU protocol.
Measurements reading:
Command | Reply | Description |
---|---|---|
S0 | & | Disables the sending of the measurements enabled with S1. |
S1 | & | Enables the sending of the measurements at regular inter- vals. To set |
the sending interval, use the command MT.
S2| & Measurements| Prints the measurements in the following sequence:
§ Pressure
§ Environmental temperature ( optional T/RH probe )
§ Relative humidity ( optional T/RH probe )
§ Dew Point ( calculated from T/RH )
§ Absolute humidity ( calculated from T/RH )
§ Wet bulb temperature ( calculated from T/RH )
§ Power supply voltage
§ Internal temperature
§ Error status ( value to be converted into binary ): Bit 0 = 1 Þ Pressure measurement error
Bit 1 = 1 Þ Internal temperature measurement error Bit 2 = 1 Þ Environ. temperature measurement error Bit 3 = 1 Þ Relative humidity measurement error
The measurements are expressed in the set meas. units.
MTn| &|| Sets the measurement interval to n seconds (1…30 s).
Default : 1
NT| & n|| Reads the measurements sending interval.
Units of measurement:
Command | Reply | Description |
---|---|---|
CUn | & | Sets the pressure unit of measurement of index n: |
§ Torr if n=0
§ Pa if n=1
§ hPa if n=2
§ kPa if n=3
§ mbar if n=4
§ psi if n=5
§ kg/cm2 if n=6
§ mmH2O if n=7
§ mmHg if n=8
§ inH2O if n=9
§ inHg if n=10
§ atm if n=11
§ bar if n=12
Default : 2 Þ hPa
RU| & n|| Reads the pressure unit of measurement.
TTn| &|| Sets the temperature unit of measurement of index n:
§ °C if n=0
§ °F if n=1
Default : 0 Þ °C
HT| & n|| Reads the temperature unit of measurement.
Quantities displayed on LCD:
Command | Reply | Description |
---|---|---|
DLx1;…;x6 | & | Enabling/disabling of the quantities to be displayed. |
x1;…;x6 is a sequence of 0 (disable) and 1 (enable) sep- arated by semi- colons, where each “x” indicates a quan- tity in the order: P, Tamb, RH, DP, AH, Twet
Example: 1;0;1;0;0;0 enables pressure and RH.
RL| & n|| Reads the enabled/disabled quantities on LCD.
Pressure measurement offset:
Command | Reply | Description |
---|---|---|
COn | & | Adds the offset n to the measured pressure value. For the value n to |
be entered..
The offset must be within the ±10 hPa range or equiva- lent range in the set unit of measurement, if different from hPa.
Default : 0
RO| & n|| Reads the pressure measurement offset.
Restoring the factory configuration:
Command | Reply | Description |
---|---|---|
DFLT | & | Restores the factory configuration. |
Analog output:
Command | Reply | Description |
---|
Current output
CATn| &|| Associates the current analog output with:
§ Pressure if n=0
§ Environmental temperature (T/RH probe) if n=1
§ Relative humidity (T/RH probe) if n=2
§ Dew Point (calculated) if n=3
§ Absolute humidity (calculated) if n=4
§ Wet bulb temperature (calculated) if n=5
Default : Pressure (n=0)
RAT| & n|| Reads the physical quantity associated with the current analog
output.
CAOn| &|| Enable/disable the offset of the current analog output:
§ Offset disabled if n=0 (0…20 mA)
§ Offset enabled if n=1 (4…20 mA)
Default : Offset enabled (n=1)
RAO| & n|| Reads the setting of the offset for the current analog output.
CASOn| &|| Sets the direct or reversed correspondence between cur- rent analog
output and associated physical quantity:
§ If n=0: Min. mA Þ Min. quantity Max. mA Þ Max. quantity
§ If n=1: Min. mA Þ Max. quantity Max. mA Þ Min. quantity
Default : Direct correspondence (n=0)
RASO| & n|| Reads the type of correspondence (direct or reversed) between
current analog output and associated physical quantity.
CALn| &|| Sets n as the minimum value of the quantity associated with the
current analog output.
For the value n to be entered.
Default : 60000 (=600.00 hPa). See Note 2.
RAL| & n|| Reads the minimum value of the quantity associated with the current
analog output.
CAHn| &|| Sets n as the maximum value of the quantity associated with the
current analog output.
For the value n to be entered.
Default : 110000 (=1100.00 hPa). See Note 2.
RAH| & n|| Reads the maximum value of the quantity associated with the current
analog output.
RAF| & 0
Minimum value Maximum value
| Simultaneously provides the information obtainable with the RAL e RAH
commands.
Voltage output
CVTn| &|| Associates the voltage analog output with:
§ Pressure if n=0
§ Environmental temperature (T/RH probe) if n=1
§ Relative humidity (T/RH probe) if n=2
§ Dew Point (calculated) if n=3
§ Absolute humidity (calculated) if n=4
§ Wet bulb temperature (calculated) if n=5
Default : Pressure (n=0)
RVT| & n|| Reads the physical quantity associated with the voltage analog
output.
CVOn| &|| Enable/disable the offset of the voltage analog output:
§ Offset disabled if n=0 (0…1/0…5/0…10 V)
§ Offset enabled if n=1 (0,2…1/1…5/2…10 V)
Default : Offset disabled (n=0)
RVO| & n|| Reads the setting of the offset for the voltage analog output.
CVSOn| &|| Sets the direct or reversed correspondence between voltage analog
output and associated physical quantity:
§ If n=0: Min. mA Þ Min. quantity Max. mA Þ Max. quantity
§ If n=1: Min. mA Þ Max. quantity Max. mA Þ Min. quantity
Default : Direct correspondence (n=0)
RVSO| & n|| Reads the type of correspondence (direct or reversed) between
voltage analog output and associated physical quantity.
CVLn| &|| Sets n as the minimum value of the quantity associated with the
current voltage output.
For the value n to be entered, see Note 1.
Default : 60000 (=600.00 hPa). See Note 2.
RVL| & n|| Reads the minimum value of the quantity associated with the voltage
analog output (see Note 1 ).
CVHn| &|| Sets n as the maximum value of the quantity associated with the
voltage analog output.
For the value n to be entered, see Note 1.
Default : 110000 (=1100.00 hPa). See Note 2.
RVH| & n|| Reads the maximum value of the quantity associated with the voltage
analog output (see Note 1 ).
RVF| & 0
Minimum value Maximum value
| Simultaneously provides the information obtainable with the RVL e RVH commands.
Note 1: The value is an integer, expressed in the set unit of measurement
and must take into account the resolution corresponding to the set unit of
measurement.
For example, if the set unit of measurement is hPa, the value is in hundredths
of hPa (60000 equals 600.00 hPa. The number is automatically converted if the
unit of measurement is changed (which must therefore be set first).
Note 2 : The defaults changes automatically if the quantity associated
with the output changes. The defaults are -400 (=-40.0 °C) / 600 (=60.0 °C)
for temp. measurements, 0/1000 (=100.0%) for RH.
Relative humidity calibration:
- In the models with T/RH probe, a 2-point user RH calibration can be performed with the CRH1 and CRH2 commands.
- User calibration must be enabled by sending the CAL USER ON command, and the cal-ibration type in use must be set to “user” (CC1 command).
Command| Reply| Description
---|---|---
CCn| &|| Sets the type of RH calibration to be used:
§ Factory calibration if n=0 ( default )
§ User calibration if n=1
GC| & n|| Reads the type of RH calibration in use.
CRH1nnn| &|| Calibrates the lower RH point to the value nnn in tenths of
%RH (e.g., 33.0% Þ nnn=330).
CRH2nnn| &|| Calibrates the higher RH point to the value nnn in tenths of %RH
(e.g., 75.0% Þ nnn=750).
CRHD| &|| Reset of user RH calibration.
Modbus-RTU protocol
- By default, the instrument has MODBUS address 1 and communication parameters 19200, 8E1. The address and the communication parameters can be changed by using the appropriate serial commands of the proprietary protocol or, alternatively, directly with MODBUS commands by changing the value of the Coils and Holding Registers de-scribed later.
- The MODBUS-RTU protocol, if set as the operating protocol (default), is active after 10 seconds from the instrument power on.
- In order to change the instrument configuration using the MODBUS-RTU protocol, the value 1 must be written first in the Coil with address 1.
- Below is the list of registers.
Input Registers:
Address | Description | Format |
---|---|---|
0 | Pressure in the set unit of measurement | 32-bit Integer |
( Note 3 )
2| Pressure in the set unit of measurement| 16-bit Integer
3| Power supply voltage in Volt [x10]| 16-bit Integer
4| Internal temperature in the set unit of measurement [x10]| 16-bit Integer
5| Error register:
Bit 0 = 1 Þ Pressure measurement error
Bit 1 = 1 Þ Internal temperature measurement error Bit 2 = 1 Þ Environ. temperature measurement error Bit 3 = 1 Þ Relative humidity measurement error
| 16-bit Integer
11| Environmental temperature (T/RH probe) in the set unit of measurement
[x10]| 16-bit Integer
12| Relative humidity (T/RH probe) in % [x10]| 16-bit Integer
13| Dew Point (calculated from T/RH) in the set unit of meas- urement [x10]|
16-bit Integer
14| Absolute humidity (calculated from T/RH) in g/m3 [x10]| 16-bit Integer
15| Wet bulb temperature (calculated from T/RH) in the set unit of measurement
[x10]| 16-bit Integer
Coils:
Address | Description | Format |
---|---|---|
0 | Set 1 to restore the factory configuration. Bit zeroing is au- tomatic. |
Bit
1| Enable configuration change:
0=no (default), 1=yes.
The changes to Coils and Holding Registers will be accept- ed only if this register is set to 1.
| Bit
2| Sets waiting time after transmission with MODBUS-RTU pro- tocol:
0=immediate reception (default); 1=waiting 3.5 characters.
| Bit
3| Enable/disable the offset of the current analog output: 0=offset disabled
(0…20 mA)
1=offset enabled (default, 4…20 mA)
| Bit
---|---|---
4| Sets the direct or reversed correspondence between current analog output
and associated physical quantity:
0=direct (default): Min. mA Þ Min. quantity
Max. mA Þ Max. quantity
1=reversed: Min. mA Þ Max. quantity
Max. mA Þ Min. quantity
| Bit
6| Enable/disable the offset of the voltage analog output: 0=offset disabled
(default, 0…1/0…5/0…10 V) 1=offset enabled (0,2…1/1…5/2…10 V)| Bit
7| Sets the direct or reversed correspondence between voltage analog output
and associated physical quantity:
0=direct (default): Min. mA Þ Min. quantity
Max. mA Þ Max. quantity
1=reversed: Min. mA Þ Max. quantity
Max. mA Þ Min. quantity
| Bit
Holding Registers:
Address | Description | Format |
---|---|---|
0 | RS485 Baud Rate: |
0=1200 4=19200 (default)
1=2400 5=38400
2=4800 6=57600
3=9600 7=115200
| 16-bit Integer
1| RS485 parity and stop bits:
0=8N1 3=8E2
1=8N2 4=8O1
2=8E1 (default) 5=8O2
[N=no parity, E=even parity, O=odd parity]| 16-bit Integer
2| Instrument address for the MODBUS-RTU protocol (1…247, default=1).| 16-bit
Integer
3| Pressure unit of measurement:
0 Þ Torr, 1 Þ Pa, 2 Þ hPa, 3 Þ kPa, 4 Þ mbar,
5 Þ psi, 6 Þ kg/cm2, 7 Þ mmH2O, 8 Þ mmHg,
9 Þ mmH2O, 10 Þ inHg, 11 Þ atm, 12 Þ bar
Default : 2 Þ hPa
| 16-bit Integer
4| Offset added to the measured pressure value. For the value, see Note 4.
The offset must be within the ±10 hPa range or equivalent range in the set unit of measurement, if different from hPa.
Default : 0.
| 16-bit Integer
5| Temperature unit of measurement:
0 Þ °C, 1 Þ °F
Default : 0 Þ °C
| 16-bit Integer
6| Measurement interval in seconds (1…30, default=1).| 16-bit Integer
8| Minimum value of the quantity associated with the current analog output.
For the value, see Note 4.
Default : 60000 (=600.00 hPa). See Note 5.
| 32-bit Integer
( Note 3 )
---|---|---
10| Maximum value of the quantity associated with the current analog output.
For the value, see Note 4.
Default : 110000 (=1100.00 hPa). See Note 5.
| 32-bit Integer
( Note 3 )
13| Minimum value of the quantity associated with the voltage analog output.
For the value, see Note 4.
Default : 60000 (=600.00 hPa). See Note 5.
| 32-bit Integer
( Note 3 )
15| Maximum value of the quantity associated with the voltage analog output.
For the value, see Note 4.
Default : 110000 (=1100.00 hPa). See Note 5.
| 32-bit Integer
( Note 3 )
17| Setting of the type of RH calibration to be used: 0=user calibration;
1=factory calibration (default).
| 16-bit Integer
18| Enabling/disabling of the quantities to be displayed. Set the bit
corresponding to the quantity to 1 if you wish to include the quantity in the
viewing cycle:
Bit 0: P
Bit 1: Tamb
Bit 2: UR
Bit 3: Tdew
Bit 4: UA
Bit 5: Twet
| 16-bit Integer
Note 3: The value is a 32-bit integer; two consecutive registers starting
from the one indicated must be accessed to read it. The register with lower
address contains the least significant bits.
Note 4: The value is an integer, expressed in the set unit of measurement
and must take into account the resolution corresponding to the set unit of
measurement. For example, if the set unit of measurement is hPa, the value
indicates hundredths of hPa (60000 equals 600.00 hPa. The number is
automatically converted if the unit of measurement is changed (which must
therefore be set first).
Note 5: The defaults changes automatically if the quantity associated
with the output changes. The defaults are -400 (=-40.0 °C) / 600 (=60.0 °C)
for temp. measurements, 0/1000 (=100.0%) for RH.
Maintenance
- it is recommended to perform a calibration check of the instrument annually at ac-credited laboratories.
- Do not use aggressive cleaning agents or incompatible with the materials indicated in the technical specifications. For cleaning, use a soft dry cloth or slightly dampened with clean water.
Safety instructions
- The instrument proper operation and operating safety can be ensured only in the cli-matic conditions specified in this manual and if all standard safety measures as well as the specific measures described in this manual are followed.
- Do not use the instruments in places where there are:
- Corrosive or flammable gases.
- Direct vibrations or shocks to the instrument.
- High-intensity electromagnetic fields, static electricity.
User obligations
The instrument operator shall follow the directives and regulations below that
refer to the treatment of dangerous materials:
- EU directives on workplace safety.
- National law regulations on workplace safety.
- Accident prevention regulations.
Accessories ordering codes
The models with input for T/RH probe are supplied with HP3517ITC1.2 probe, HD9007A-1 protection from solar radiations (for the probe) and HD9007T26.2 fitting (for fixing the probe to the solar protection).
- FIXB001 Static port with support bracket and silicone tube.
- SWD10F 100…240 Vac / 12 Vdc – 1A power supply. Includes adapter cable with jack connector on the power supply side and free wires on the instrument side.
Spare parts
- HP3517ITC1.2 Spare temperature and relative humidity combined probe. 4-pole M12 connector. Stem dimensions: Ø14 x 135 mm. Material: PBT. Ca-ble length: 2 m.
- HD9007A-1… Spare 12-ring protection from solar radiations. Supplied with mounting bracket. For the HP3517ITC1.2 probe.
- HD9007T26.2 Spare fitting for Ø 14 mm probes for the protection from solar radia-tions HD9007A-1.
WARRANTY
- The manufacturer is required to respond to the “factory warranty” only in those cases provided by Legislative Decree 6 September 2005 – n. 206. Each instrument is sold after rigorous inspections; if any manufacturing defect is found, it is necessary to contact the distributor where the instrument was purchased from. During the warranty period (24 months from the date of invoice) any manufacturing defects found will be repaired free of charge. Misuse, wear, neglect, lack or inefficient maintenance as well as theft and damage during transport are excluded. Warranty does not apply if changes, tampering or unauthorized repairs are made on the product. Solutions, probes, electrodes and microphones are not guaranteed as the improper use, even for a few minutes, may cause irreparable damages.
- The manufacturer repairs the products that show defects of construction in accordance with the terms and conditions of warranty included in the manual of the product. For any dispute, the competent court is the Court of Padua. The Italian law and the “Convention on Contracts for the International Sales of Goods” apply.
TECHNICAL INFORMATION
- The quality level of our instruments is the result of the continuous product development. This may lead to differences between the information reported in the manual and the instrument you have purchased.
- We reserve the right to change technical specifications and dimensions to fit the product requirements without prior notice.
DISPOSAL INFORMATION
- Electrical and electronic equipment marked with specific symbol in compliance with 2012/19/EU Directive must be disposed of separately from household waste. European users can hand them over to the dealer or to the manufacturer when purchasing a new electrical and electronic equipment, or to a WEEE collection point designated by local authorities. Illegal disposal is punished by law.
- Disposing of electrical and electronic equipment separately from normal waste helps to preserve natural resources and allows materials to be recycled in an environmentally friendly way without risks to human health.