Danfoss Large Commercial Compressor Instructions
- May 15, 2024
- Danfoss
Table of Contents
Danfoss Large Commercial Compressor
Product Information
Specifications :
- Recommended solder alloy: High silver cadmium free alloy
- Recommended silver content: 34% minimum
- Recommended silver rod options: 40%, 45%, 56%
Product Usage Instructions
Brazing Methods and Requirements:
As per industry standards, use high silver cadmium free solder alloy with
recommended silver content. Avoid self-flux alloys.
Benefits of Silver Content:
- Excellent fluidity
- Limited heating temperature
- Good resistance to corrosion
- Proper elongation for system vibration
- Good behavior under thermal variation
System Cleanliness:
Circuit Contamination Possible Causes:
- Brazing and welding oxides: Flow nitrogen through the system during brazing.
- Particles and burrs: Remove any generated by tube cutting and drilling.
- Moisture and air: Use clean, dehydrated refrigeration grade copper tubing. Avoid exposing opened compressors to air for more than 20 minutes.
Brazing Procedure:
Prior to un-brazing, remove refrigerant charge and vacuum the installation
to avoid refrigerant-oil dilution.
Frequently Asked Questions (FAQ):
-
Q: Can I use self-flux alloys for brazing?
A: No, it is not recommended as it may overheat connectors and result in joint embrittlement. -
Q: What is the recommended silver content for brazing alloys?
A: A minimum of 34% silver content is recommended, with options of 40%, 45%, and 56% silver rods.
Instructions
Brazing for large and medium compressor connectors
Introduction
The refrigeration and air conditioning industries depend on brazed copper tubes as a leak-proof carrier for pressurized refrigerant. The common approach to brazing copper to copper or copper to steel is to use filler metal (usually copper alloy). Torch brazing with oxygen/fuel gas (acetylene in most cases) is the standard practice in heating these connections. Large and medium scroll compressors connectors are made of steel copper coated, which benefit to prevent corrosion and facilitate adhesion during brazing operation.
Methods and requirements
- As per standards practice in the refrigeration industry, Danfoss Commercial Compressor recommends the use of high silver cadmium free solder alloy and flux (added or flux coated rods). The bests are 40%, 45%,and 56% silver rods. A minimum content of 34% Ag (Silver) is recommended by Danfoss.
- The significant silver content in these brazing alloys will help the brazing operation, providing an excellent fluidity and a limited heating temperature. It will also bring a good resistance to corrosion, a proper elongation compatible with system vibration, and good behavior under thermal variation improving the strength of connection and limiting fractures and refrigerant leaks. (Crucial with A2L and A3 refrigerants).
The use of self-flux alloys (as phosphorous alloys) is not recommended by Danfoss. This type of brazing requires a higher working temperature, that may overheat the connectors, damaging the thin layer of copper, resulting in phosphides creation and joint zone embrittlement.
System cleanliness :
Circuit contamination possible cause | Requirement |
---|---|
Brazing and welding oxides | During brazing, flow nitrogen through the system. |
Particles and burrs | Remove any particles and burrs generated by tube cutting |
and hole drilling.
Moisture and air|
- Use only clean and dehydrated refrigeration grade copper tubing.
- Opened compressor must not be exposed to air more than 20 minutes to avoid moisture captured by oil.
Brazing procedure
- Brazing operations must be performed by qualified personnel.
- Make sure that no electrical wiring is connected to the compressor.
- To prevent compressor shell and electrical box overheating, use a heat shield and/or a heat-absorbent compound.
- Clean up connections with degreasing agent. No trace of grease should remain into or around the fittings.
- Flow nitrogen through the compressor during the brazing operation.
- It is recommended to use double-tipped torch using acetylene to ensure a uniform heating of connection.
- For discharge connections brazing time should be less than 2 minutes to avoid NRVI damages if any.
- To enhance the resistance to rust, a varnish on the connection is recommended.
Before eventual un-brazing of the compressor or any system component, the refrigerant charge must be removed and the installation vacuumed to ensure that no refrigerant is remaining diluted into the oil (especially with A2L/A3 refrigerants).
Danfoss A/S
- Climate Solutions
- danfoss.com
- +45 7488 2222
Any information, including, but not limited to information on selection of
product, its application or use, product design, weight, dimensions, capacity
or any other technical data in product manuals, catalogues descriptions,
advertisements, etc. and whether made available in writing, orally,
electronically, on line or via download, shall be considered informative, and
is only binding if and to the extent, explicit reference is made in a
quotation or order confirmation. Danfoss cannot accept any responsibility for
possible errors in catalogues, brochures, videos and other material.
Danfoss reserves the right to alter its products without notice. This also
applies to products ordered but not delivered provided that such alterations
can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/5 or Danfoss group
companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/5. All
rights reserved.
© Danfoss | Climate Solutions | 2024.02