QUEST 746 480V Dehumidifier Climate Installation Guide
- September 25, 2024
- Quest
Table of Contents
746 480V Dehumidifier Climate
“`html
Specifications:
- CFM: 1750 @ 0.0 WG
- Power: 4300 Watts
- Supply Voltage: 480 VAC
- Current Draw: 6.5A
- Rated Current Draw: 7.5A
- Operating Temperature: 56°F to 95°F
- Water Removal (Pints/Day): Not specified
- Efficiency (Pints/KWH): Not specified
- Air Filter (MERV-13): Qty 2, Size: 18 x 20 x 2
Product Usage Instructions:
1. Intended Application for Quest 746:
The Quest 746 Dehumidifier is designed to operate in
temperatures between 56°F and 95°F. Ensure that the area where the
dehumidifier will be used is free of water intrusion or excessive
outside air infiltration. Address any water intrusion or air
infiltration issues before installation.
2. Installation:
Follow these steps for proper installation of the Quest 746
Dehumidifier:
-
Ensure the power supply matches the unit’s voltage
requirements. -
Connect the unit to a suitable electrical source using the
specified electrical knockout size. -
Make sure to provide proper drainage by connecting the drain to
a threaded NPT outlet. -
Install the unit in a location that allows for proper air
circulation and access for maintenance.
FAQ:
1. What should I do if the dehumidifier does not start?
If the dehumidifier does not start, check the power supply and
ensure it is connected properly. If the issue persists, contact
customer support for assistance.
2. How often should I clean or replace the air filters?
It is recommended to clean or replace the air filters every 3 to
6 months depending on usage and environmental conditions. Clean
filters ensure optimal performance of the dehumidifier.
3. Can the Quest 746 Dehumidifier be used in a basement?
Yes, the Quest 746 Dehumidifier can be used in a basement as
long as the operating temperature and humidity levels fall within
the specified range. Ensure proper installation and drainage to
prevent water damage.
“`
QUEST
746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
For complete product information, scan here:
Quieter Operation Patented M-CoRR Technology Industry-Leading Efficiency
Superior MERV-13 Air Filtration Integrated Lift and Hang Points Auto-Restart
After Power Outages
QUESTCLIMATE.COM / 877-420-1330
Serial Number Install Date Sold By
CALIFORNIA
TITLE 24 COMPLIANT
Patents: thermastor.com/patents
TS-2005 05/24 REV E
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
TABLE OF CONTENTS
Safety Precautions……………………………………………………2 1. Intended
Application…………………………………………….3 2. Registrations ………………………………………………………..3 3.
Specifications……………………………………………………….3 4. Installation ……………………………………………………………4
4.1 Location………………………………………………………….4 4.2 Electrical Requirements
……………………………….4 4.3 Condensate Water Removal ………………………….5 4.4 Hanging Diagram
………………………………………….5 5. Control Options…………………………………………………….6 5.1 Humidity
Control…………………………………………….6 5.2 24VAC Wiring ………………………………………………..6
5.2A Deh 3000R……………………………………………7 5.2B Honeywell Remote Humidistat ……………..7
5.2C Daisy Chain ……………………………………………. .7 Maintenance …………………………………………………….8 6.1
Standard Air Filter ……………………………………..8 7. Service…….. …………………………………………………………..8
7.1 Warranty………………………………………………………….8 7.2 Technical Description
…………………………………….8 8. Ducting Guidelines ……………………………………………… .9 9. Display
…………………………………………………………………10 9.1 User Interface………………………………………………. 10 9.2
Settings Change Example……………………………. 11 9.3 Viewing Active Alarms/Alarm Logs
……………. 12 9.4 Viewing Unit Run Hours ……………………………… 13
Service Parts List …………………………………………………… 14 Optional Parts List …………………………………………………. 14 Wiring Diagram……………………………………………………….. 16 Warranty……… …………………………………………………………. 18
4201 Lien Rd. Madison, WI 53704 | 1-877-420-1330 Thermastor.com | QuestClimate.com
1
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
SAFETY PRECAUTIONS
Read the installation, operation and maintenance instructions carefully before
installing and operating this device. Proper adherence to these instructions
is essential to obtain maximum benefit from your Quest dehumidifier.
READ AND SAVE THESE INSTRUCTIONS
» The device is designed to be installed INDOORS IN A SPACE THAT IS PROTECTED
FROM RAIN AND FLOODING.
» Install the unit with space to access the back or side panels for
maintenance and service. DO NOT INSTALL UNIT WITH THE SERVICE PANELS
INACCESSIBLE.
» Avoid directing the discharge air at people, or over the water in pool
areas.
» If used near a pool, spa or water: be certain there is NO chance the unit
could fall into the water, be splashed, and that it is plugged into an outlet
that is a GROUND FAULT INTERRUPT protected circuit.
» DO NOT use the device as a bench or table. » DO NOT place the device
directly on structural members. Provide
vibration isolation in order to minimize operational vibration and/or noise.
» A drain pan MUST be placed under the unit if installed above a living area
or above an area where water leakage could cause damage.
» Never operate a unit with a damaged power cord. If the power cord is damaged
it must be replaced by the manufacturer, its service agent, or similarly
qualified person in order to avoid a hazard.
» Make all electrical connections in accordance with the current edition of
the NEC ANSI/NFPA 70 and any national and local codes or ordinances that may
apply.
» Maintain a minimum 1 ft (.3 m) clearance to avoid obstructing the air return
and supply.
» This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance.
» Not intended for use at altitudes over 6500 ft (2000M).
2
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
1. INTENDED APPLICATION FOR QUEST 746
The Quest 746 Dehumidifier is designed to operate in temperatures between 56 F
and 95 F. In order to efficiently control humidity levels, the area in which
the dehumidifier is to be operated must be free of water intrusion or
excessive fresh (outside) air infiltration. Before installing the Quest 746
Dehumidifier, water intrusion and air infiltration problems should be
addressed or noted in calculations.
2. REGISTRATIONS
The Quest 746 Dehumidifier units conform to unified standards: UL 60335-2-40,
CSA 22.2 # 60335-240:2012 Ed. 1+4. Patent: thermastor.com/patents
3. SPECIFICATIONS @ 80°F / 60% RH
UNIT
CFM: POWER:
SUPPLY VOLTAGE:
CURRENT DRAW: RATED CURRENT DRAW:
(104 F | 36%) MCA MOP
RECOMMENDED BREAKER SIZE: ENERGY FACTOR (L/KWH): OPERATING TEMP:
WATER REMOVAL (PINTS/DAY): EFFICIENCY (PINTS/KWH): AIR FILTER (MERV-13): (QTY
2)
POWER CORD:
QUEST 746 4037610 1750 @ 0.0″ WG
4300 Watts 480 VAC
3 Phase – 60 Hz 6.5A
7.5A
10A 15A 10A 3.45 56 F Min 95 F Max 746 7.3
Size: 18″ x 20″ x 2″
No cord; hardwire only
ELECTRICAL KNOCKOUT SIZE:
3/4″ (1.094″ opening)
DRAIN CONNECTION:
REFRIGERANT TYPE:
REFRIGERANT AMOUNT: DIMENSIONS: WIDTH: HEIGHT: LENGTH: WEIGHT:
3/4″ Threaded NPT
R410A 6 lb 4 oz
Unit 28.9″ 34.1″ 44.8″ 340 lb
Shipping 36″ 40″ 48″ 420 lb
This unit requires external control, not provided. Specifications are subject to change without notice.
- MCA = Minimum Circuit Ampacity
This number provides a qualified electrician with the information needed to determine the minimum wire size used in the circuit that feeds a single dehumidifier. - MOP = Maximum Overcurrent Protection
This number provides a qualified electrician with the value of the maximum size circuit breaker that may be used to protect the circuit that feeds a dehumidifier.
3
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
4. INSTALLATION
4.1 LOCATION
The Quest 746 Dehumidifier can be installed in a variety of locations to meet
the owner’s needs as listed below. In all cases keep the following cautions in
mind:
» It is designed to be installed INDOORS IN A SPACE THAT IS PROTECTED FROM
RAIN AND FLOODING.
» Install the unit with space to access side panel for maintenance and
service. DO NOT INSTALL UNIT WITH ACCESS PANEL INACCESSIBLE.
» Avoid discharging the air directly at people, or over the water in pool
areas.
» Be certain there is NO chance the unit could fall into water.
» DO NOT use the Quest 746 Dehumidifier as a bench or table.
» DO NOT place the Quest 746 Dehumidifier directly on structural members.
Provide vibration isolation in order to minimize operational vibration and/or
noise.
» A drain pan MUST be placed under the unit if installed above an area where
water leakage could cause damage.
» Do not obstruct the air intake and exhaust. Maintain a 1 ft clearance around
the air intake and exhaust.
» Permanently removing the fixed feet (4038225 and 4038226) from the base pan
will invalidate the ETL/UL certification. Please contact Quest for more
information.
4.2 ELECTRICAL REQUIREMENTS
High Voltage Connections
The Quest 746 Dehumidifier must be wired directly to the electrical service.
The current draw under normal operating conditions is listed in section 3.
Information required for proper electrical service installation and
overcurrent protection may be found on the Dehumidifier nameplate. The unit
power switch is a disconnect switch. Route power and ground wires through the
electrical knockout hole. Electrical input power wiring must comply with all
national, state, and local electrical codes. Make electrical connections
according to the wiring diagram provided in this manual and inside the access
panel of the Dehumidifier. A ground fault interrupter protected circuit is
recommended.
Low Voltage Connections
Install the external control in a central area of the structure where it will
sense the relative humidity accurately. Avoid installing the sensor near HVAC
supply registers, near exterior doors, or near pool or spa. The installer must
supply the wiring between the Dehumidifier and the control panel. Be sure to
safely route the control wiring to prevent damage during installaion. Be
careful not to cross the wires when connecting the Dehumidifier and the
Control.
The controls of the Dehumidifier are powered by a low voltage circuit (24VAC)
and must NEVER contact or be connected to a high voltage circuit. The control
terminals are labeled to prevent confusion. For more information on controls,
see section 5.
WARNING! Electrical Shock Hazard: Electrical power must be present for
some tests. These tests should performed by a qualified service person.
4
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
4.3 CONDENSATE WATER REMOVAL
Condensate drains by gravity via the drain port. Use 3/4″ male NPT PVC pipe. An optional condensate pump kit may be installed if a lift is required to dispose of the condensate. Optional parts list for information on the kit.
FOLLOW DIAGRAM:
Level unit within 2°
CAP
3/4″ drain port
4.4 HANGING DIAGRAM
4″ 6.75″
2″
3/8″ threaded rod
28.95 27.25
Treated Air
3/8″ Jam Nuts
Intake Air
5.56″
PARTS NEEDED: 4 pieces 3/8″ threaded rod (not included) 4 – 3/8″ threaded jam nuts (not included
WARNING! Hanging installation must meet all state and local codes.
WARNING! Installation should be done by a qualified agency in accor-
dance with these instructions. The qualified service agency installing this
high
efficiency refrigeration system is responsible for the installation.
5
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
WARNING! Check the supporting structure to be used to verify that it has
sufficient load carrying capacity to support the weight of the unit. Suspend
the unit only from the threaded nut retainers. Do NOT suspend from the
cabinet.
CAUTION! Recommended maximum hanger rod is 6 ft (1.8 m).
5. CONTROL OPTIONS
The Quest 746 Dehumidifier is controlled by an external remote humidistat
through a 24V terminal block. External control NOT provided.
5.1 HUMIDITY CONTROL
A 24VAC signal is sent by the remote humidistat signals the fan or fan and
compressor to actuate.
Quest Control Options:
» Cloud Control » DEH 3000R » Honeywell Humidistat » Any 24V signal to
dehumidify
CAUTION! Low Voltage Hazard. Can cause equipment damage. Disconnect
power before beginning installation.
5.2 24VAC WIRING
The terminal block, low voltage circuit breaker, and power switch are located
on the intake side of the unit. Turn the power switch to the off position
while wiring the unit.
FLOAT: {External normally closed dry contact float switch.} No voltage may be
applied to the float switch.
FLOAT: Applying voltage may damage the control and void the warranty. {If no
float is used in the system, leave the jumper connected to the terminal
block.}
DEHU: Dehumidificaton (compressor and fan operation).
R:
24VAC output
FAN: Fan operation only.
C:
24VAC neutral (common)
Note: » External devices can be powered between 24V/COM (10VA max). » 24V circuit is protected by circuit breaker
FLOAT
FLOAT DHUM
(COMPRESSOR AND FAN)
R
FAN
C
6
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
5.2 24 VAC
QUEST CLOUD CONTROL WIRING DIAGRAM
(BLUE) (YELLOW) (RED)
FLOAT
FLOAT DHUM
(COMPRESSOR AND FAN)
R
FAN
C
5.2A QUEST
QUEST DEH 3000R CONTROL WIRING DIAGRAM
24VAC
FLOAT
FLOAT DHUM
(COMPRESSOR AND FAN)
R
FAN
C
COMP FAN
5.2B HONEYWELL
HONEYWELL REMOTE HUMIDISTAT WIRING DIAGRAM
Black Red
FLOAT
FLOAT DHUM
(COMPRESSOR AND FAN)
R
FAN
C
24V IN COM 24V OUT
5.2C DAISY CHAIN
QUEST DEH 3000R CONTROLER
QUEST 6 SERIES UNIT#3
FLOAT FLOAT DHUM
(COMPRESSOR AND FAN)
R
FAN
C
QUEST 6 SERIES UNIT#2
FLOAT FLOAT DHUM
(COMPRESSOR AND FAN)
R
FAN
C
QUEST 6 SERIES UNIT#1
FLOAT FLOAT DHUM
(COMPRESSOR AND FAN)
R
FAN
C
24VAC
COMP FAN
*NOTE DO NOT WIRE IN “FAN” TERMINAL WITH THIS APPLICATION
7
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
6. MAINTENANCE
WARNING! Do not operate the unit without the filter or with a less effective
filter. Filter non-compliance invalidates the product warranty.
6.1 STANDARD AIR FILTER
The Quest 746 Dehumidifier ships with two standard MERV 13 efficient pleated
fabric filters. This filter should be checked every six months. Operating the
unit with a dirty filter will reduce dehumidifier capacity and efficiency.
To access the air filter, the filter should be readily visible and can be
removed by pulling it straight out of the Quest 746 Dehumidifier.
For agriculture, we recommend changing the filter with every grow cycle.
7. SERVICE
WARNING! Servicing the Quest 746 with its high pressure refrigerant
system and high voltage circuitry presents a health hazard which could result
in death, serious bodily injury, and/or property damage. Only qualified
service personnel should service this unit.
7.1 WARRANTY
A warranty certificate has been enclosed with this unit; read it before any
repair is initiated. If a warranty repair is required, call the factory first
at 1-877-420-1330 for warranty claim
authorization and technical assistance.
7.2 TECHNICAL DESCRIPTION (NON STANDARD PATENTED)
The Quest 746 Dehumidifier uses a refrigeration system to remove moisture from
incoming air, and add heat to the air that is discharged.
Hot, high-pressure refrigerant gas is routed from the compressor to the
condenser coil. The refrigerant is cooled and condensed by giving up its heat
to the air that is about to be discharged from the unit. The refrigerant
liquid then passes through a filter/drier and expansion drier which causes the
refrigerant pressure and temperature to drop. It next enters the evaporator
coil where the cool refrigerant absorbs heat from the incoming air and
evaporates.
The compressor evacuates the cool refrigerant vapor from the evaporator and
compresses it to a high pressure and temperature to repeat the process.
8
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
8. DUCTING GUIDANCE
CAUTION! Quest 746 is intended for use in statics under .5″WG.
» Ducting the intake and exhaust requires rectangular ducting, dimensions
shown below. Custom Therma-Stor duct accessory kits below are recommended.
» Grills or diffusers on the duct ends must not excessively restrict airflow.
» Effective dehumidification may require ducting to be branched to isolated or
stagnant flow areas. Be sure to use appropriate size duct branches to maintain
proper feed throughout the ducting system.
» System control should be placed remotely from the dehumidifier in a central
location.
» Intake and exhaust ducting should have a minimum of 4 feet from the unit
before any turns and maximum of 25′ for total run.
CAUTION! Do not connect with a static pressure greater than +.5″wg.
Contact technical support for additional details.
· Optional duct kits are available from the factory: Exhaust Kit 4039868 and
Intake Kit 4038642. See figures below for plenum dimensions. Alternatively,
licensed contractors can fabricate duct plenums and reference figures below
for safe fastener mounting points.
QUEST 6 SERIES 746 INTAKE DUCT
LOCATION
QUEST 6 SERIES 746 SUPPLY DUCT
LOCATION
9
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
9. DISPLAY
9.1 USER INTERFACE
The main status screen is shown:
Alarm Prg/Bullseye
Escape
Up Enter Down
Left side buttons (top to bottom): » Alarm press at any time to check active
alarms. » Prg/Bullseye press at any time to access settings and menus. »
Escape press at any time to move to the previous menu.
Right side buttons (top to bottom): Up » On a menu selection screen – moves
cursor up. » On an editable value increases the value. Press and hold to
change the value faster. » If cursor is in upper left corner of a screen
moves to previous screen. Enter » On a menu selection screen enters the
highlighted menu. » On an editable value saves the current value and moves
to the next editable item on the screen. Down » On a menu selection screen
moves cursor down. » On an editable value decreases the value. Press and
hold to change the value faster. » If cursor is in upper left corner of screen
moves to next screen.
10
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
9.2 SETTINGS CHANGE EXAMPLE: CHANGING DATE DISPLAY FORMAT
1. From any screen, press the Prg/Bullseye key. This will prompt for a
password. 2. Press Enter four times to access the menu. Then, press Up/Down
keys until Settings is highlighted. 3. Press Enter to enter Settings menu.
Then, press Up/Down until Date/Time is highlighted. 4. Press Enter to select
Date/Time. Then, press Enter again to move the cursor to the Format field.
11
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
1. Press the Up/Down keys to cycle through the options. Once MM/DD/YY is displayed, press Enter. This will save the new value, and will move the cursor down to the date field.
2. Press Escape three times to get back to the main status screen.
9.3 VIEWING ACTIVE ALARMS/ALARM LOGS
1. From any screen, press the Alarm key. If there are active alarms, this will display a screen like this.
Alarm Code
Description of Fault
Current Alarm Total Number of Number Active Alarms Time/Date Alarm was Triggered
Operating Mode updates in real-time
2. Press Up/Down to cycle through all active alarms. The alarms are arranged
in order of their alarm code (lowest to highest). One screen beyond last
active alarm, the following screen will be displayed.
» Note that if a fault condition is still present, resetting an alarm will
have no effect. Active alarms will automatically be removed from the list when
the fault condition is resolved.
12
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
3. Press Enter to access the Alarm Log. This allows you to cycle through the
50 most recent alarms, whether they are active or if they’ve been resolved.
These are arranged from newest to oldest. The Alarm Log screen is similar to
the Active Alarm screen, except for a few differences:
» The Alarm Log screen does not display the current operating mode
» The Alarm Log screen shows both when the alarm was first triggered (Event:
Start) and when the fault condition was resolved (Event: Stop).
9.4 VIEWING UNIT RUN HOURS
1. From any screen, press Escape several times to return to the main status
screen. Press Up/Down until the clock icon is displayed in the lower-right of
the screen.
2. Press Enter to display the operating hours for the entire unit (compressor
or fan), for the blower, and for the compressor.
13
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
SERVICE PARTS LIST
Item Part No
Description
1
4029507 CONTROL, HIGH PRESSURE
2 4042474 CONTACTOR, 3-POLE (QTY 2)
3 4042114
TRANSFORMER
4 4036559 CIRCUIT BREAKER
5
4039667
THERMISTOR W/CLAMP (QTY 2) (NOT SHOWN)
6 4042979 CPRSR
7 4037702 FILTER, DRIER
8 4037703-04 COIL, EVAP
9
4037699
THERMISTOR BULB (QTY 2) (NOT SHOWN)
10 4039605-02 COIL, MICRO (QTY 4)
11 4039661 EEV
12 4042479 FAN,MOTORIZED IMPELLER
13 4038135
HANDLE, POCKET (QTY 4)
1 4 4038136
BEZEL, HANDLE (QTY 4)
Item Part No
Description
15 4042586 WIRE HARNESS (NOT SHOWN)
16 4038079 LUG, GROUND
17 4038219
FOOT, RUBBER, 1.25″ DIA (QTY 4)
18 4038225-01 BRACKET, FOOT, RIGHT
19 4038226-01 BRACKET, FOOT, LEFT
20 4042475 BLOCK, WIRING
21 4042596 PLC
22 4038233 FILTER – 18 X 20 X 2 (QTY 2)
23 4039862 PRESSURE TRANSDUCER
24 4042477
CPRSR WIRE HARNESS (NOT SHOWN)
25 4041558 PLC DISPLAY
26 4041559
DISPLAY CABLE ASSEMBLY (NOT SHOWN)
27 4039875 PCB
28 4034716-08 THERMISTOR PROBE
OPTIONAL PARTS LIST
Part No
Qty
Description
4028531
1
4022220
1
4038642
1
DEH 3000R Control, Remote Kit, Pump Kit, Intake Duct
Part No
Qty
4039868
1
4038644
1
Description
Kit, Exhaust Duct Drain Trap Kit
14
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
15
QUESTCLIMATE.COM
QUEST 746
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
WIRING DIAGRAM OF THE QUEST 746 DEHUMIDIFIER
4042587 REV B
16
QUESTCLIMATE.COM
QUEST 746
DO NOT DISCARD
LIMITED WARRANTY
IMPORTANT WARRANTY INFORMATION
WARRANTOR: Therma-Stor LLC 4201 Lien Rd Madison, WI 53704 Telephone:
1-800-533-7533
WHO IS COVERED: This warranty extends only to the original end-user of the
Quest 746 dehumidifier, and may not be assigned or transferred.
FIRST YEAR WARRANTY: Therma-Stor LLC warrants that, for one (1) year the Quest
746 dehumidifier will operate free from any defects in materials and
workmanship, or Therma-Stor LLC will, at its option, repair or replace the
defective part(s), free of any charge.
SECOND THROUGH FIFTH YEAR WARRANTY: Therma-Stor LLC further warrants that for
a period of five (5) years, the condenser, evaporator, and compressor of the
Quest 746 dehumidifier will operate free of any defects in material or
workmanship, or Therma-Stor LLC, at its option, will repair or replace the
defective part(s), provided that all labor and transportation charges for the
part(s) shall be borne by the end-user.
END-USER RESPONSIBILITIES: Warranty service must be performed by a Servicer
authorized by Therma-Stor LLC. If the end-user is unable to locate or obtain
warranty service from an authorized Servicer, he should call Therma-Stor LLC
at the above number and ask for the Therma-Stor LLC Service Department, which
will then arrange for covered warranty service. Warranty service will be
performed during normal working hours.
The End-user must present proof of purchase (lease) upon request, by use of
the warranty card or other reasonable and reliable means. The end-user is
responsible for normal care. This warranty does not cover any defect,
malfunction, etc. resulting from misuse, abuse, lack of normal care,
corrosion, freezing, tampering, modification, unauthorized or improper repair
or installation, accident, acts of nature or any other cause beyond Therma-
Stor LLC’s reasonable control.
LIMITATIONS AND EXCLUSIONS: If any Quest 746 Dehumidifier part is repaired or
replaced, the new part shall be warranted for only the remainder of the
original warranty period applicable thereto (but all warranty periods will be
extended by the period of time, if any, that the Quest 746 Dehumidifier is out
of service while awaiting covered warranty service).
UPON THE EXPIRATION OF THE WRITTEN WARRANTY APPLICABLE TO THE QUEST 746
DEHUMIDIFIER OR ANY PART THEREOF, ALL OTHER WARRANTIES IMPLIED BY LAW,
INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, SHALL ALSO
EXPIRE. ALL WARRANTIES MADE BY THERMA-STOR LLC ARE SET FORTH HEREIN, AND NO
CLAIM MAY BE MADE AGAINST THERMA-STOR LLC BASED ON ANY ORAL WARRANTY. IN NO
EVENT SHALL THERMA-STOR LLC, IN CONNECTION WITH THE SALE, INSTALLATION, USE,
REPAIR OR REPLACEMENT OF ANY Quest Dual DEHUMIDIFIER OR PART THEREOF BE LIABLE
UNDER ANY LEGAL THEORY FOR ANY SPECIAL, INDIRECT OR CONSEQUENTIAL DAMAGES
INCLUDING WITHOUT LIMITATION WATER DAMAGE (THE END-USER SHOULD TAKE
PRECAUTIONS AGAINST SAME), LOST PROFITS, DELAY, OR LOSS OF USE OR DAMAGE TO
ANY REAL OR PERSONAL PROPERTY.
Some states do not allow limitations on how long an implied warranty lasts,
and some do not allow the exclusion or limitation of incidental or
consequential damages, so one or both of these limitation may not apply to
you.
LEGAL RIGHTS: This warranty gives you specific legal rights, and you may also
have other rights which vary from state to state.
SERIAL NUMBER
PART NUMBER
PLACE LABEL HERE
QUESTCLIMATE.COM
REGISTER YOUR NEW DEHUMIDIFIER using the serial number and part number at
thermastor.com/ registration or scan code above