Nailor D0100 Extension of Factory Sleeves Fire and Combination Damper Instruction Manual

May 15, 2024
Nailor

Nailor D0100 Extension of Factory Sleeves Fire and Combination Damper

Nailor D0100 Extension of Factory Sleeves Fire and Combination
Damper

Product Description

Figure 1: Factory sleeve extends all the way through the rated barrier.
Product Description

Figure 2: Factory sleeve ends in the plane of the rated barrier.
Product Description

APPLICATION

Factory installed sleeves may sometimes need to be extended in the field when there is insufficient length of ductwork connection relative to the depth of the fire rated wall/barrier/partition. This supplement installation instruction provides details for attachment of the sleeve extension. Consult Authority Having Jurisdiction (AHJ) for approval.

Figure 1: When the factory sleeve extends all the way through the rated fire barrier.
Figure 2: When the factory sleeve ends in the plane of the rated fire barrier.

NOTES:

  1. Sleeve extension must be same material and gauge as factory sleeve.
  2. The inside dimensions of the sleeve extension must be the same dimensions as the outside dimensions of the factory sleeve.
  3. Sleeve extension must overlap the factory sleeve a minimum of 1″ (25).
  4. All four sides of the sleeve extension must be attached to the factory sleeve. Attachments must be spaced a maximum of 6″ (152) on center and a maximum of 2″ (51) from corners. A minimum of 2 attachments per side (8 per damper) are required. Attach the sleeve extension using 1/2″ (13) long tack or spot welds, #10 sheet metal screws, 1/4″ (6.35) dia. bolts and nuts or 3/16″ (5) steel pop rivets.
  5. Products with a smoke leakage rating require that the joint between the two sleeves be sealed with a continuous 1/8″ (3) bead of Dow Corning 732, G.E. RTV108, Boss 310 or 315RTV silicone sealant.
  6. Sleeve extensions can be made to either end of the factory sleeve. However, the sleeve cannot extend beyond the fire partition more than 6″ (152) on either side or 16″ (406) on one side if equipped with an actuator or integral access door.
  7. The joint created by the factory sleeve and sleeve extension cannot be in the plane of the fire rated barrier.

Refer to the Following Installation Instructions:

Curtain Type Fire Dampers (D)0100, 0300 & (D)0500 FDINST
Curtain Type Fire Dampers 0200 & 0500 Thin line FDTINST
Multi-Blade Fire Dampers (D)1200 & D1250 MBFDINST
Combination Fire/Smoke Dampers 1220 1220 INST
Combination Fire/Smoke Dampers 1270 1270 INST

Refer to the UL Classification Marking on the Product

Customers Support

Houston, Texas
Tel: 281-590-1172
Fax: 281-590-3086

Las Vegas , Nevada
Tel: 702-648-5400
Fax: 702-638-0400

Toronto, Canada
Tel: 416-744-3300
Fax: 416-744-3360

Calgary, Canada
Tel: 403-279-8619
Fax: 403-279-5035

” Complete Air Control and Distribution Solutions.”
www.nailor.com

Logo

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Nailor User Manuals

Related Manuals