Nailor (D)0110GOW Out of Wall Curtain Fire Damper for Grilles and Registers Instruction Manual

May 15, 2024
Nailor

Nailor (D)0110GOW Out of Wall Curtain Fire Damper for Grilles and

Registers

Specifications

  • Model: (D)0110GOW 1 1/2 HR. LABEL
  • Material: Steel or Aluminum
  • Construction: Vertical steel stud or masonry, horizontal concrete fire partition
  • Insulation: Intumescent thermal insulation
  • Mounting: Vertical or Horizontal

Product Usage Instructions

Installation Steps

  1. Refer to the UL Classification Marking on the Product for guidelines.
  2. Prepare the construction type and duct connection as per the manual.
  3. Ensure proper insulation and use appropriate fasteners based on the construction material.
  4. Attach the steel or aluminum grille/diffuser securely.
  5. Follow the specific instructions for vertical or horizontal mounting.

Notes for Installation

  • Installation must comply with NFPA Standard NFPA 90A latest edition.
  • Use a factory-furnished sleeve of at least 16-gauge coated steel for the damper sleeve.
  • Frame and finish the opening to accommodate damper sleeve thickness and insulation.

Important Points

  • The damper is provided in full size for installation.
  • Expansion clearance and opening preparation are crucial for proper installation.
  • The maximum distance of the damper outside of the barrier should not exceed 1 inch (25mm).

FAQ

Q: What type of construction is suitable for the (D)0110GOW fire damper?

  • A: The fire damper is suitable for vertical steel studs, masonry, horizontal concrete fire partitions, and wood stud constructions.

Q: What kind of insulation is recommended for the damper?

  • A: Intumescent thermal insulation is recommended for use with the damper.

Q: How should I attach the grille/diffuser to the damper?

  • A: The grille/diffuser should be securely attached using appropriate fasteners as per the manual instructions.

INSTALLATION INSTRUCTIONS

QUALIFICATIONS:

  • Meets all the requirements of UL 555 and CAN/ULC-S112.
  • Meets the requirements for NFPA 80, 90A, and 101 as well as IBC and NBC (Canada) building codes.
  • California State Fire Marshal Listing No. 3225-0935:0113/0100.
  • Vertical or Horizontal installation.

ITEMS:

  • A. Typical 2-hour rated vertical steel stud or masonry construction or horizontal concrete fire partition.
  • B. Duct connection (see Note 2).
  • C. Intumescent thermal insulation.
  • D. Fasteners (see note 4):
    • a. In metal stud/drywall walls and partitions and cavity shaft wall partitions, use #10 sheet metal screws.
    • b. In masonry wall or floor/ceiling construction, use #10 self-tapping concrete anchors.
    • c. In Wood Stud, use minimum #10 steel screws.
  • E. Steel or Aluminum Grille/Diffuser.
  • F. Typical 2-Hour Rated
  • Vertical Wood Stud Construction

F: Wood Stud Detail

APPLICATION

  • (D)0110GOW are “out of wall” or floor integral sleeve curtain type fire dampers, specifically designed for supply or return ducts that terminate at a grille or register.
  • The (D)0110GOW design provides sufficient damper offset to accommodate most commercial grille/register designs while ensuring an approved installation in any fire partition or wall no matter how narrow.
  • This model is particularly suited for use in common steel stud drywall partition designs, as narrow as 3 1/2″ (89) where a traditional “within the plane of the wall” fire damper installation is not possible.

NOTES:

IMPORTANT: DAMPER IS FURNISHED FULL-SIZE

  1. Installation shall be under the appropriate requirements of the National Fire Protection Association Standard NFPA 90A latest edition.

  2. Damper Sleeve: These dampers are supplied with a factory-furnished sleeve which shall not be less than 16 gauge (1.16) coated steel.
    Sleeve thickness must be equal to or thicker than the duct connected to it. Sleeves may be attached to the duct with cleats, screws or other types of mechanical fasteners. The maximum sleeve thickness for such rigid joints is 10 gauge (3.51) for coated steel.

  3. Expansion Clearance and Opening Preparation. To accommodate the damper sleeve thickness and insulation, frame and finish the opening so that it is 1/2″ (13) larger in width and height than the duct size. Dampers are furnished with an inside sleeve dimension full ordered size to facilitate grille installation.

  4. Fasteners and Retaining Angles. For installation in a masonry wall or floor/ceiling and metal stud drywall partitions, no rear retaining angles are required. Insert the damper/sleeve combination into the opening so that the 3/4″ (19) flange is tight to the drywall or concrete. Secure the damper in the wall opening from inside the sleeve as shown above by use of the following:

    • a. In metal stud/drywall walls, partitions and cavity shaft wall partitions, use minimum #10 sheet metal screws.
    • b. In masonry walls or floor/ceilings use minimum #10 self-tapping concrete wall anchors. Anchors must penetrate the wall or floor a minimum of 1 1/2″ (38).
    • c. In wood stud, use minimum #10 steel screws, 2 1/2″ (64) long with minimum 1 1/2″ (38) penetration into the framing.
    • Maximum distance of damper outside of the barrier shall be 1″ (25).
    • Fasteners shall be spaced a maximum of 6″ (152) on the center and 2″ (51) maximum from corners, a minimum of two per side is required.
    • Alternatively, 1 1/2″ x 1 1/2″ x 16 gauge (38 x 38 x 1.61) rear retaining angles may be used instead of the above-prescribed method and secured to the sleeve with 1/2″ (12.7) long welds, 1/4″ (6.35) dia. bolts and nuts, 3/16″ (4.76) dia. steel rivets or #8 sheet metal screws, 8″ (203) on center and 2″ (51) maximum from corner of sleeve on all four sides.
  5. Maximum Size Limitations:

    • Model 0110GOW D0110GOW
    • System Static Dynamic
    • Mounting Vertical or Horizontal Vertical Horizontal
    • Single Section 36″ x 24″ (914 x 610) 24″ x 24″ (610 x 610) 24″ x 24″ (610 x 610)
    • Multiple Section 36″ x 24″ (914 x 610)

IMPORTANT

  • DO NOT CAST THE DAMPER IN PLACE.
  • DO NOT INSTALL DAMPER OUT OF THE SQUARE OR OUT OF THE FLAT.
  • REFER TO THE APPROPRIATE NAILOR INSTALLATION INSTRUCTION SUPPLEMENTS FOR ADDITIONAL INFORMATION OR SPECIAL REQUIREMENTS:
  • STEEL AND WOOD STUD FRAMING FDSWSFINST
  • CAVITY SHAFT WALL PARTITIONS FDCSWINST
  • FLANGED TYPE ALTERNATIVE BREAKAWAY CONNECTIONS FDFABC
  • QUICK-SET RETAINING ANGLES FDQSRA
  • Houston, Texas
  • Tel: 281-590-1172
  • Fax: 281-590-3086
  • www.nailor.com

Documents / Resources

| Nailor (D)0110GOW Out of Wall Curtain Fire Damper for Grilles and Registers [pdf] Instruction Manual
D 0110GOW Out of Wall Curtain Fire Damper for Grilles and Registers, D 0110GOW, Out of Wall Curtain Fire Damper for Grilles and Registers, Fire Damper for Grilles and Registers, Grilles and Registers
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals