Nailor Industries 1000 Standard Multiple Section Control Damper Drive Arrangements Instruction Manual
- June 1, 2024
- Nailor Industries
Table of Contents
**Nailor Industries 1000 Standard Multiple Section Control Damper Drive Arrangements Instruction Manual
**
INSTALLATION INSTRUCTIONS
-
Control dampers are classified as follows:
With Seals: Single-skin Blades – 1010 Parallel, 1020 Opposed
Steel Airfoil Blades – 1110 Parallel, 1120 Opposed
Aluminum Airfoil Blades – 2010 Parallel, 2020 Opposed
No Seals: Single-skin Blades – 1012 Parallel, 1022 Opposed
Maximum single section size is 48″ wide x 72″ high (1219 x 1829) for all models except 2000 series which is 60″ wide x 72″ high (1524 x 1829). -
Dampers larger than the maximum single section size are fabricated in multiple section assemblies. These assemblies consist of sections of equal size which are coupled together with a jackshaft. The jackshaft runs parallel to the “w” dimension.
A. 1/2″ (13) Diameter Jackshaft:-
Used on two sections wide with a maximum of 32 sq. ft. with blade and jamb seals; or a maximum of 40 sq. ft. without seals.
B. 1″ (25) Diameter Jackshaft: -
Used on two sections wide over 32 sq. ft. with blade and jamb seals; or over 40 sq. ft. without seals.
-
Used on assemblies of more than two sections wide, regardless of area.
Maximum Section Size for all Multiple Section Dampers: 48″ wide x 72″ high (1219 x 1829).
-
-
Use the details on page 2 and 3 to determine how multiple section dampers with standard construction and sizes up to 240″ wide x 144″ high (6086 x 3658) will be manufactured. Details do not apply if the control damper has any of the following non-standard features:
A. Unequal section sizes.
B. Face and By-pass arrangement.
For sizes larger than 240″ x 144″ (6096 x 3658), consult factory. -
How to determine your damper configuration:
A. Calculate the damper area in square feet:
Area = (W in. wide x H in. high) = sq. ft. 144
B. Based on the W and H dimensions and the area of your damper, determine the appropriate assembly detail using the chart on page 2.
Example: Model 1020 (with seals) 96″ wide x 96″ high.
Area = (96 x 96) = 64 sq. ft. From chart and drawings, damper configuration is per detail 22Q. Your damper will be 144 built this way. -
Multiple section assemblies require bracing to support the weight of the assembly and to hold against system pressure.
Appropriate bracing must support the damper horizontally at least once for every 8 ft.(2438) of damper width.
Vertical assemblies and higher system pressures require more bracing. -
The maximum shipping size is 96″ x 72″ (2438 x 1829) or two sections wide. Larger units are shipped in sections for field assembly.
Refer to the Control Damper Installation Instructions on page 4 for joining multiple sections. -
Optional 1/2″ (13) dia. and 1″ (25) dia. crankarms are available for field applications that utilize linear type actuators (usually pneumatic).
You can order the crankarms illustrated below (at additional cost) by the associated part number.
1/2″ (13) CRANKARM
A = 5-15/16″ (151)
1″ (25) CRANKARM
A = 7-13/16″ (198)
1/2″ (13) DIA. CRANK ARM (OPTIONAL)
PART NO. CD005
1″ (25) DIA. CRANK ARM (OPTIONAL)
PART NO. CD010
HOLE NO. | CRANK ARM RADIUS |
---|---|
8 | 1 3/8″ (35) |
7 | 1 9/16″ (40) |
6 | 1 9/16″ (40) |
5 | 2″ (51) |
4 | 2 13/16″ (72) |
3 | 3 3/16″ (81) |
2 | 4 1/4″ (108) |
1 | 4 3/4″ (121) |
DIMENSION “W” WIDTH IN INCHES (mm) | |
--- | --- |
DIMENSION “H” HEIGHT IN INCHES(mm ) | ALL MODEL SERIES |
1100 SERIES ONLY** | 2000 SERIES ONLY |
48″ (1219) AND UNDER | OVER 48″ (1219)THRU 96″ (2438) |
(1524) | OVER 60″ (1124)THRU 96″ (2438) |
144″ (3658)THRU 192″ (4877) | OVER 192″ (4877)THRU 240″ (6096) |
72″ (1829) AND UNDER | – |
D | DETAIL 41 S OR D |
OVER 72″ (1829)THRU 144″ (3658) | DETAIL 12 S OR D |
22S, D or Q | DETAIL 32 D OR Q |
DETAIL 21S
25 SQ. FT. AND UNDER WITH SEALS
48 SQ. FT. AND UNDER NO SEALS
DETAIL 31S
25 SQ. FT. AND UNDER WITH SEALS
50 SQ. FT. AND UNDER NO SEALS
DETAIL 41S
25 SQ. FT. AND UNDER WITH SEALS
50 SQ. FT. AND UNDER NO SEALS
DETAIL 51S
25 SQ. FT. AND UNDER WITH SEALS
50 SQ. FT. AND UNDER NO SEALS
DETAIL 21D
OVER 25 THRU 48 SQ. FT. WITH SEALS
DETAIL 31D
OVER 25 THRU 50 SQ. FT. WITH SEALS
OVER 50 THRU 72 SQ. FT. NO SEALS
DETAIL 41D
OVER 25 THRU 96 SQ. FT. WITH SEALS
OVER 50 THRU 96 SQ. FT. NO SEALS
DETAIL 51D
OVER 25 THRU 120 SQ. FT. WITH SEALS
OVER 50 THRU 120 SQ. FT. NO SEALS
SUPPLIED WITH JACKSHAFT CROSSOVER
DETAIL 12S
25 SQ. FT. AND UNDER WITH SEALS
48 SQ. FT. AND UNDER NO SEALS
SUPPLIED WITH 1/2″ DIA. EXTENDED SHAFTS (NO JACKSHAFTS)
DETAIL 12D
OVER 25 THRU 48 SQ. FT. WITH SEALS
DETAIL 22S
OVER 24 THRU 25 SQ. FT. WITH SEALS
OVER 24 THRU 50 SQ. FT. NO SEALS
DETAIL 22D
OVER 25 THRU 50 SQ. FT. WITH SEALS
OVER 50 THRU 96 SQ. FT. NO SEALS
DETAIL 22Q
OVER 50 THRU 96 SQ. FT. WITH SEALS
DETAIL 32D
OVER 48 THRU 50 SQ. FT. WITH SEALS
OVER 48 THRU 100 SQ. FT. NO SEALS
DETAIL 42D
OVER 72 THRU 100 SQ. FT. NO SEALS
DETAIL 52D
OVER 96 THRU 100 SQ. FT. NO SEALS
ETAIL 32Q
OVER 50 THRU 144 SQ. FT. WITH SEALS
OVER 100 THRU 144 SQ. FT. NO SEALS
DETAIL 42Q
OVER 72 THRU 192 SQ. FT. WITH SEALS
OVER 100 THRU 192 SQ. FT. NO SEALS
DETAIL 52Q
OVER 96 THRU 240 SQ. FT. WITH SEALS
OVER 100 THRU 240 SQ. FT. NO SEALS
- RECEIVING/INSPECTION
Upon delivery, inspect shipping containers and dampers carefully. Note any damage on trucker’s delivery receipt. Contact the freight
company within 24 hours for inspection. Do not install dampers. It is easier to repair on the floor than in the duct.
STORAGE
Store in an orderly manner. Do not pile dampers on each other. Cover with plastic sheeting to protect from excessive moisture, dirt and
debris. Avoid unnecessary handling of dampers.
INSTALLATION
Handle dampers by frame only. Do not lift by blades, linkage, actuator or jackshaft. Use sufficient people to evenly lift multiple section assemblies. Do not drop, drag, step on, or apply excessive bending, twisting or racking. Cycle dampers by hand before installation to ensure freedom of movement.
-
Inspect ductwork or opening where damper will be installed for any obstructions and to ensure it is straight and level.
It is essential to support ductwork to prevent sagging due to damper weight. -
Determine location of extended drive shaft or jackshaft before installation.
-
Position damper shipping sections together in duct or opening. Align and match frame markings on adjacent sections **(see fig. 1).
1/2″ (13) COUPLING DETAIL
**
-
Align holes on adjacent frame sections and fasten together on front and back sides with screws or nuts and bolts.
-
Use shims as appropriate between damper frame and duct opening and between damper sections as necessary to prevent distortion of frame by fasteners. Ensure fasteners do not interfere with blade movement or damper linkage. Bracing is required at every horizontal mullion for strength and to support weight. Vertical bracing is recommended at every 8 feet minimum of damper width for strength.
Dampers in high velocity and/or high pressure systems require more bracing. -
If the damper assembly is supplied with enjoined jack shafting and is operated by only one actuator, join jackshaft ends using coupling and set screws or nuts and bolts provided (see fig. 2).
1″ (25) COUPLING DETAIL
-
If applicable, connect lower and upper jackshafts with the connecting rod crossover supplied, through the swivel on crank arm at each jackshaft. Locate crank arm close to a jackshaft bearing bracket and not centrally in order to minimize play (see fig. 2).
-
Ensure dampers are set completely square, plumb and free from racking, twisting or bending and are free to operate without binding (see fig. 3).
Individual damper sections and multiple assemblies must be square.
Both dimensions across the diagonal must be equal ± 1/8″ (3).
FASTENERS:
USE S/M SCREWS
OR
_ NUTS & BOLTS. DO NOT DISTORT FRAME. USE SHIMS AS NECESSARY._
A clearance must be maintained between blade and blade bearing. Move blade solidly to one side against bearing and measure clearance at other end. If jamb seals are present, compress to determine clearance. Dampers must operate without binding. Before system operation, cycle damper after installation to assure proper operation. On multiple section assemblies, (with jackshaft coupling) all sections should open and close simultaneously. -
After installation of low leakage dampers with seals, caulk between frame and duct or opening to prevent leakage.