Danfoss MCE100A PID Transmission Controller Installation Guide

May 15, 2024
Danfoss

Installation GuideDanfoss MCE100A PID Transmission
Controller MCE100A,B
PID Transmission Controller

Application

The PID Controller provides a means of controlling the output shaft speed of a hydrostatic transmission.
By comparing actual motor speed against a setpoint command and using proportional, integral and de-rivative stages that operate on the error, accurate and responsive control is achieved.
Inatypical application, the PID Controller maintains an accurate output shaft speed on a hydrostatic transmission coupled to the vibratory drive of a roller compactor. Other applications include motor gen-erator frequency control, motor speed control for resonant beam systems, crawler forward speed control or torque control for pressure-control pumps.
A series of parameters is varied for each individual application.
The MCE100A senses output speed with either a pulse pickup or adctachometerfeedback. Forthose cases in which maximum response to pump RPM changes is necessary, a feedforward MC Controller is also available.

Features

  • Withstands mobile equipment vibration and shock conditions
  • Electronic components selected and tested for mobile environmental conditions
  • Printed circuit boards coated with electronic- grade conformal coating for moisture protection
  • Reverse polarity protection
  • Short circuit protection
  • Shorted valve + lead will not damage unit
  • Loss-of-feedback protection foropen or shorted wires
  • Maintains setpoint upon loss of feedforward sensor
  • Ramp stanub

Specifications

Electrical
INPUT VOLTAGE RANGE
11 to 16 Vdc (12 volt models)
20 to 28 Vdc (24 volt models)
SUPPLY CURRENT (EXCLUDING LOAD CUR-RENT)
100 ma, maximum
OUTPUT VOLTAGE AT 4 VOLT TERMINAL (VR ±4 .4Vde
FEEDBACK INPUT VOLTAGE
.5 – 20 volts, peak to peak (pulse pickup)
0 -4 volts dc (protected to 16 Vdc) (dc tachome-ter)
FEEDBACK INPUT IMPEDENCE
.01 pf paralieled with 50 k Ω (pulse pickup) 40 k Ω (dc tachometer)
FEEDBACK DUTY CYCLE (PULSE PICKUP)
30 – 70%
FEEDFORWARD INPUT VOLTAGE
.5 to 20 Vdc, peak to peak (pulse pickup)
FEEDFORWARD CORRECTION RANGE
425 Hz, maximum (pulse pickup)
100 Hz, minimum (pulse pickup)
For non-standard frequencies, see Ordering Information
FEEDFORWARD INPUT IMPEDANCE
.01 microfarads paralleled with 50 kilohms (pulse pickup)
EXTERNAL COMMAND INPUT VOLTAGE RANGE
0TO 4 Vdc
EXTERNAL COMMAND INPUT IMPEDANCE
200 kilohm, minimum
OUTPUT CURRENT RANGE (Current Source)
300 ma, maximum (V7058)
150 ma, maximum (MCV101A)
QUTPUT LOAD RESISTANCE
10 ohms, minimum
OUTPUT LOAD INDUCTANCE
.4 henries, maximum
METER CURRENT ADJUST
450 to 800 microamps at maximum setpoint
REVERSE POLARITY
The power and ground inputs may be reversed without incurring damage to the device.
SHORT CIRCUIT PROTECTION
The valve output will sustain indefinite short
circuits to ground.
TRANSIENT PROTECTION
The valve output will sustain inductive switch transients of less than 15 millijoules.
OPEN FEEDBACK PROTECTION
150 msec, maximum
Defined as the time from loss of feedback to zero output current when operating at 50% of full scale command. For non-standard values, see Ordering Information.
Environmental
OPERATING TEMPERATURE
-29° to +66° C (-20° to +150° F)
STORAGE TEMPERATURE
-34° to +66° C (-30° to +150° F)
VIBRATION
Withstands a vibration test designed for mobile equipment controls consisting of two parts:

  1. Cycling from 5 to 2000 Hz in each of the three axes.
  2. Resonance dwell for one million cycles in each of the three axes.

Runfrom 1 g to 8 g’s. Acceleration level varies with frequency.
SHOCK
50 g for 11 milliseconds. Three shocks in both directions of the three mutually perpendicular axes for a total of 18 shocks.
HUMIDITY
Afterbeing placed in a controlled atmosphere of 95% humidity at 38° C (100° F) for 10 days, the controller will perform within specification limits.
RAIN
After being showered from all directions by a high pressure hose down, the controller will perform within specification limits.

Performance
SETPOINT STABILITY
Less than .5% of setting over supply range Less than 2% of setting over temperature range Defined as the percent of variation from setting in plant output in stable closed loop control.
COMMAND THRESHOLD
30 ± 2%, 18 ± 2%, 10 ± 2%, 2.5%
Defined as a percentage of full scale for lowest closed loop control.
COMMAND RAMP UP RATE
4.4 ± 8seconds,04±.2,25±.8,20± .8
Defined as the time for command input signal to reach 90% of full scale with internal or external command set to full scale.
DUAL RAMP UP RATE
.45 ± .07 seconds to reach 40%
6.3 ± .6 seconds to reach 90%
Defined as the time for command input signal to reach 90% of full scale with internal or external command set to full scale.
FEEDBACK FREQUENCY
500 Hz, 1khz ± 1%, 1.1 khz ± 1%, 5 khz ± 1%,
3khz ± 1%, 1.65 khz ± 1%
Defined with command set to maximum (+4 Vdc) and with stable, closed loop control. For non-standard feedback frequencies, see Order-ing Information.
FEEDBACK PHASE ANGLE
41° ± 5° phase lead at 2 Hz modulation 0°±5°
Defined as the phase lead from the feedback input’s sinusoidally varying frequency to the input.
FEEDFORWARD LOAD CURRENT CHANGE
100+ 5ma
Defined as the open loop change in load current output for an input frequency change of 1 khz to 5khz. Fornon-standard changes, see Ordering Information.
PROPORTIONAL GAIN
.43 t0 3.5 ma/%
.27 t0 2.4 ma/%
.29 t0 2.4 ma/%
23210 2.0 ma/%
.11 to .85 ma/%
5to 3.5 ma/%
.05 to .43 ma/%
Defined as the gain rates at the low and high ends of the proportional gain adjustment. For non-standard settings, see Ordering Informa-tion.
INTEGRATION TIME CONSTANT
100 to 300 msec, 100 to 1100 msec
For non-standard settings, see Ordering Infor-mation.
DERIVATIVE TIME CONSTANT
0 to 550 msec
For non-standard settings, see Ordering Infor-mation.
DIMENSIONS
See Figure 1.

Theory Of Operation

Aninternal or external command signal proportional to the desired hydrostatic transmission speed is input to the MCE100 PID Controller. See Figure 2.
Command conditioning circuitry provides a slow ramp up to prevent excessive start up acceleration and a quick ramp down for safety in sudden stops. A low limit threshold must be crossed before any control action begins. This low speed limit is im-posed by inherent constraints on the feedback pulse rate in a responsive closed loop control system and by loss of feedback considerations.
When the command exceeds the threshold point, it is compared to the feedback signal from the first pulse pickup. See Figure 3. The feedback has been converted from frequency to a dc voltage if the sensor is a pulse pickup. If a dc tachometer is substituted, this is unnecessary. After the feedback is subtracted from the command, a loss-of-feedback circuit monitors the output. If an excessive error signal exists for an extended duration of time (indi- cating a loss of feedback signal), the controller will latchoff (on some units). A power down andback up cycle will effect a reset.
The error signal is then passed to the PID stages.
The first correction mode, proportional (P), in-creases the cormective output in response to the magnitude of the error – the larger the error, the bigger the response. The proportional stage allows the system to respond almost immediately to changes. It acts in series with the paralleled and D stages, as shownin Figure 2. The second correction mode, integral (I), increases the output with the integral of time – error is summed as time pro-gresses, and by adding these signals overtime even small errors can be recognized and corrected, giv-ing zero-droop control. The third correction mode, derivative (D), increases the output with the deriva-tive of time – fast changes produce alarge corrective signal. The derivative stage adds stability to most systems.
The feedforward stage is an option for those appli-cations needing further response in their systems.
See Figure 4. A second pulse pickup on the pump input shaft senses prime mover speed input changes before they are reflected at the motor output shaft. Again, either a pulse pickup or dc tachometer may be used and a low-idle threshold must be crossed before corrective action begins.
Because the feedforward signal is added algebrai-cally to the output stage, a faulty sensor or broken wire will not stop the controliing action; two potenti-ometers set the zero and span of feedforward ac-tion.
The four signals are added in the summing stage, where they are converted to a current output to the pump stroker (V7058 or Electrical Displacement Control). The current levelis varied by the controller to maintain the desired speed from the hydraulic motor’s output shaft. Danfoss MCE100A PID Transmission
Controller - Fig 1 FIGURE 4. Effect of feedforward on control action. Peaks S, and S, have the same feedforward amplitude and are smaller than those of feedback only.

Wiring

Figure 5 shows a typical wiring connection for the PID control loop. The cable extending from the controller terminates in a connector that mates to a female MS connector, Bendix part number PT06-14-188S (left side of the connector, as diagramed).
The MS connector attaches to a color-coded cable, which is fanned out into a customer-supplied termi-nalstrip. Ifthe customer chooses to connectdirectly to the terminal strip, the mate to the terminal is a number 4 spade lug.
The following cable/connector assemblies are avail- able. See Figure 6.

  1. One six-foot cable with the MS connector speci- fied above.
  2. One twenty-foot two wire valve cable with an amphenol 44-103-10002 connector and mate.
  3. One twenty-foot two-wire Belden 9318 shielded feedforward or feedback cable with a pair of number 6 spade lugs on one end and a pair of 1/4 inch push-on terminals at the other.

Initial Installation

Overall System Considerations
For stable and responsive closed loop speed con-trol, the open loop characteristics of the rest of the system should be optimized with the following crite-ria in mind.

  • The system must be capable of delivering the selected RPM setpoint over the full range of engine input speeds and output loads. The smallest pump-to-motor size ratio should be chosen that meets this criterion.

  • Pump/motor interconnect hoses are energy storage elements. Excessive length and/or diameter causes poor open loop transient re-sponse and loss of stability under closed loop control. Therefore, hose lengths should not exceed ten feet, and lines over three feet should not exceed three-quarter inch in diameter for high pressure hose. Longer lines may require hard piping.

  • Load variation should not cause wide move-ments in engine RPM levels. A “soft” engine governor will result ina less responsive and less stable control loop.

  • A standard feedforward frequency from the Ppump pulse pickup is 333 Hz at 2000 RPM (10 tooth gear), handled by the standard controller.
    Other frequency ranges may be accomodated, such as 500 Hz from an engine flywheel gear.
    Acceptable pulse pick-up voltages:
    500 MV peak to peak minimum,
    20 volts peak to peak maximum.

  • The drive signal from the controller necessary for optimum performance depends on the type of pump stroker used.

  • Controllers are available for either 12 or 24 Vdc systems.

  • Because of their energy storage capabilities, pressure filters in the high side of the hydrostatic loop are detrimental to control performance.

  • All pump and motor combinations may be equipped with speed control; however, optimal parameter settings will vary with each combina-tion, as will control performance.

FIGURE 5. Wiring connection to the controller. All cables have one end with no termination; user cuts to length and terminates. Danfoss MCE100A PID
Transmission Controller - Fig 4

Adjustment Procedure

Once familiar with the user’s application, the PID Controller can be factory- shipped with standard potentiometer settings. If the application is new, or if the settings need re-adjustment due to wear in the hydrostatic transmission, hoses, control valves, etc., the procedure listed below should be followed to maximize the controller’s efficiency. The proce-dure assumes that the user has either a voltmeter or oscilloscope attached to the controller to track sys-tem response.
When making gain changes and testing for stability, itis recommended that small adjustments be made before upsetting the system and observing how it recovers. Asthe system approachesinstability it will tend to “ring” somewhat before settling out. This helps identify when instability is being approached and minimizes the chance of a dangerous instabil-ity level, which could damage the equipment.

  1. With the system fully connected, remove the controller’s cover and locate the row of trim potentiometers on the main board and feedforward trim on the secondary board (if used). They are located near the plastic end cap. See Figure 7.Danfoss MCE100A PID Transmission Controller - Fig 4FIGURE 7. Location of setpoint trim poten-tiometers on the Controller’s main printed circuit board.

  2. Connect a voltmeter from terminal 8 to ground. A microammeter may be substituted for the VOM. Disconnect the microammeter if using a VOM.

  3. Adjust the internal setpoint counterclockwise until a slight click is heard, indicating the minimum setpoint. Then adjust the setpoint clockwise (increasing speed) to bring the system to the desired speed. The potenti-ometer will require several turns to surpass the threshold and come up to the proper speed. External setpoint would be similarly operated.

  4. Set the P potentiometer 90° clockwise from minimum; set | mid-position. Set D to its mid-point, asindicated in Figure 8. Onthe feedfor-ward circuit board, set gain and zero potenti-ometers to their midpoint.

  5. Set the engine at maximum RPM.Danfoss MCE100A PID Transmission Controller - Fig 6FIGURE 8. Adjustment range of the P, I, D and M setpoint potentiometers.

  6. Apply power to the controller. If the system starts to oscillate, as indicated by severe vi-bration in the hydrostatic transmission, shut off power to the controller.

  7. If the system oscillates and the driven load is massive and inertial, turn the D setting clock- wise. If the system oscillates and the load is not massive turn it counterclockwise. Con- tinue to adjust the D setting until the point that stability is achieved. Ifthe systemoscillates at all settings, consuit Danfoss.

  8. Increase the P gain until the system starts to gounstable orthe maximumis reached. Then decrease the gain by 1/3 of distance from countercloskwise end.

  9. Increase the l gain until the system starts to go unstable or the maximum is reached. Then decrease the gain by 1/3 of distance from counterclockwise end.

  10. Re-adjustthe D gainbyvaryingto instability in either direction and then re-setting midway between these instability points.

  11. Re-adjust the P gain by increasing it to insta-bility and then backing away from this setting by 1/3 of the distance from the counterclock-wise end.

  12. Feedforward Adjustment:
    a) Set Feedforward gain to mid position.
    b) Set zero to mid position.
    c) Start and set engine to some mid RPM.
    d) Start full PID Control at about 25% of the rated speed at full engine.
    e) Ground (or open) Feedforward pulse pickup.
    f) As the Feedforward PPU ground is re-moved, the valve + (PID terminal 10) shall reduce momentarily (for less than 1 sec-ond). This can also be observed by a mo-mentary drop in the set RPM. Adjust the Feedforward ZERO until the momentary voltage (speed) drop shows as the Feed-forward PPU is re-enabled.
    g) Make a step change (i.e., a sudden in-crease) to set engine to maximum throttle.
    Observe output speed deviations as the engine runs up. If the controlled hydrostatic output speed increases much as the engine runs up, increase Feedforward gain. Con-versely, if output speed decreases momen-tarily, then reduce Feedforward gain.
    h) There may be some over shooting during engine run up as shown in Figure 4. Adjust Feedforward gain for the least + or – speed changes. The adjustments of P, I, and D in the main PID board may also be varied to effect the least speed deviation as the engine runs up.

  13. If a permanently-installed microammeter s to be used, the mneter potentiometer (M) may be used for calibration. Ata known output speed (verified by a stroboscope, oscilloscope, ta-chometer or other), adjust the meter potenti-ometerforthe correct microammeter reading.

Troubleshooting

Shouldthe speed control loop fail to maintain speed properly, any one of its components could be atfault.
Table A provides a means of diagnosing these fail-ures. Shouldthe procedure failto solve the problem, consult Danfoss. ForPID Controllers that need repair, see Ordering Information.
TABLE A. Troubleshooting procedure for failures in the PID control loop. Symptoms are on the left and areas to check are on top. Areas should be checked in the numerical order shown (l.e., check “1”s first, “2”s second, etc.).

| FEEDBACK PPU
FAULT| EXTERNAL
CIAO FAULT| POWER FAULT| VALVE
FAULT| ENGINE
RPM| FEEDFORWARD
PPU
---|---|---|---|---|---|---
OPEN/
SHORT| INT| OPEN/ SHORT| INT| OPEN| LOW OR INT| OPEN/ SHORT| INT| LOW| OPEN/
SHORT| INT
1.| WILL NOT TURN SYSTEM AT ALL| | | 1| | 1| | 1| | | |
2.| MOTOR STARTS TO TURN, THEN SHUTS OFF| 1| 2| | 3| 1| 2| 1| 2| 2| | 2
3.| SYSTEM HUNTS EXCESSIVELY, NON-PERIODIC| | 1| | 1| | 1| | 1| | | 1
4.| SYSTEM RUNS OK, THEN SHUTS DOWN OR SPEEDS UP, THEN SHUTS DOWN| | 1| | 1| | | | 1| | | 1
5.| SYSTEM RUNS FULL SPEED| 1| | | | | | | | | |
6.| CANNOT SET TO FULL SPEED| | 2| | 2| | 1| | | 1| | 2
7.| POOR RESPONSE TO RPM CHANGE| | | | | | | | | | 1| 2
E.| CANNOT MAKE SYSTEM STABLE (OSCILLATES CYCLICALLY)| | 3| | 5| | 4| | 4| | | 3
9.| ENGINE RPM AND SYSTEM BOTH OSCILLATE| | | | | | | | | | |
10.| POOR RESPONSE TO LOAD CHANGE| | | | | | | | | | |
11.| METER READ-OUT NOT WORKING (KNOW 1ACROA1AMETER IS OK)| | | | | | | | | | |

INT MAY GE INTERMITTENT CONNECTION ON EITHER WIRE OR MARGINAL VOLTAGE OFF SENSOR
GROUND FAULT (OPEN)
SHORT TO POWER SOURCE
SYSTEM STABILITY IS ALSO AFFECTED BY THE ENGINE GOVERNOR

| METER OUT| INT OR EXT
CMD| IM.
PROPER
P,I,D
ADJ| FEEDFORWARD
GAIN| HOSE.
LEN.
DIA.
---|---|---|---|---|---
OPEN/
SHORT| INT| TO LOW| TOO
HIGH| TO LOW| TO HIGH| TOO LAR.
1. WILL NOT TURN SYSTEM AT ALL| | | 1| | | | |
2. MOTOR STARTS TO TURN, THEN SHUTS OFF| | | | | | | |
3.SYSTEM HUNTS EXCESSIVELY, NON-PERIODIC| | | | | | | |
4. SYSTEM RUNS OK. THEN SHUTS DOWN OR SPEEDS UP, THEN SHUTS DOWN| | | | | | | |
5. SYSTEM RUNS FULL SPEED| | | | 1| | | |
6. CANNOT SET TO FULL SPEED| | | | | | | |
7. POOR RESPONSE TO RPM CHANGE| | | | | | 2| |
8. CANNOT MAKE SYSTEM STABLE (OSCILLATES CYCLICALLY)| | | | | 1| | 2| 1
9. ENGINE RPM AND SYSTEM BOTH OSCILLATE| | | | | 2.4| 1.4| |
10. POOR RESPONSE TO LOAD CHANGE| | | | | 1| | | 1
11. METER READ-OUT NOT WORKING (KNOW MCROAIAMET ER 5 OK)| 1| 2| | | | | |

TABLE B. MCE100 Standard Units.

OS NUMBER POWER SETPOINT FEEDBACK FEED RAMP OUPUT CONNECTOR LOSS OF
VOLTS DC KILOHERTZ FORWARD • FEEDBACK
MCE100A1018 14 INTERNAL 1 NONE SINGLE W058 TERM STRIP YES
MCE100A1026 14 EXTERNAL 1 NONE DUAL W058 TERM STRIP YES
MCE100A1042 14 EXTERNAL 5 NONE SINGLE V7058 TERM STRIP YES
MCE100A1059 14 EXTERNAL 1 NONE SINGLE W058 TERM STRIP YES
MCE100A1067 28 INTERNAL 4 NONE SINGLE W058 MS YES
MCE100A1075 28 INTERNAL NONE SINGLE EDC MS YES
MCE100A1084 28 INTERNAL 900 HETRZ NONE SINGLE EDC TERM STRIP NO
MCE100A1091 14 INTERNAL 1 NONE SINGLE EDC MS NO
MCE100A1109 14 INTERNAL .025 – 1 NONE SINGLE EDC MS NO
MCE100A1117 14 EXTERNAL 1 NONE SINGLE EDC TERM STRIP NO
MCE100A1125 28 INTERNAL 900 HERTZ NONE SINGLE EDC MS NO
MCE100A1133 14 EXTERNAL 1 NONE 2 SEC EDC TERM STRIP NO
MCE100A1141 14 EXTERNAL 3 NONE SINGLE EDC TERM STRIP NO
MCE100A1156 14 EXTERNAL 1.65 NONE 2 SEC EDC TERM STRIP NO
MCE100A1166 14 EXTERNAL 500 HERTZ NONE SINGLE EDC TERM STRIP NO
MCE100B1009 14 INTERNAL 1 425 HERTZ SINGLE W058 TERM STRIP YES
MCE100B1017 14 INTERNAL 900 HERTZ 425 HERTZ SINGLE W058 MS YES
MCE100131025 14 INTERNAL 900 HERTZ 425 HERTZ SINGLE EDC MS YES
MCE100B1033 14 900 HZ INT 1 1KHZ-5KHZ SINGLE EDC MS YES
MCE100B1058 14 INTERNAL 900 HERTZ 1KHZ SINGLE EDC MS YES
  • Max Hz. Min Hz = 20% of Max.

Ordering Information

The MCE100A, B PID Controller has been designed 1o be customized, through a series of optional gain settings, additional features and extra circuit compo- nents, to each user’s requirements. The specifica-tions listed are for a “standard™ controller, but they can usually be modified to fit individual user needs.
Consult….Danfoss…..for these customiza-tions. See Table B for standard units.

CUSTOMER SERVICE
NORTH AMERICA
ORDER FROM
Danfoss (US) Company
Customer Service Department
3500 Annapolis Lane North
Minneapolis, Minnesota 55447
Phone: ( 7632) 509-2084
Fax: ( 763) 559-0108
DEVICE REPAIR
For devices in need of repair, include a description of the problem, a copy of the purchase order and your name, address and telephone number.
RETURNTO
Danfoss (US) Company
Return Goods Department
3500 Annapolis Lane North
Minneapolis, Minnesota 55447
EUROPE
ORDER FROM
Danfoss (Neumiinster) GmbH & Co.
Order Entry Department
Krokamp 35
Postfach 2460
D-24531 Neuminster
Germany
Phone: 49-4321-8710
Fax:49-4321-871-184

SPECIFY STANDARD OPTIONS
Supply Vottage 12 Vdc 24 Vdc
Command Internal External
Feedback Pulse Pickup dc Tach

Maximum Pulse
Pickup
Feedback
Frequency| 1 kHz| Variable
Feedforward| No| Yes
Maximum Pulse
Pickup
Feedforward
Frequency| 1 kHz to 5 kHz| Variable (450 Hz,1 kHz)
Output Stage| V7058| EDC
Command Ramp Time
(90% of full scale)| 4.4 sec| Variable
Ramp Type| Single| Dual
Connector| Screw Terminal| MS or Packard Connector
Cabling| N/A| Feed-forward, Feed-back, Valve,
Main Controller

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals