ELTA VL250 Inline Duct Fan Instruction Manual
- May 15, 2024
- elta
Table of Contents
VERSALINE VL
Installation & Maintenance
Installation Instructions
- WARNING – This fan is fitted with a non self-resetting thermal cut-out which switches the fan off in the event of a fault condition. To reset, urn the power off for one minute, then back on. Only a suitably qualified and competent person may carry out maintenance after the electrical supply has been isolated.
CAUTION – In order to avoid a hazard due to inadvertent resetting of the thermal cut-out, this appliance must not be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly switched on and off by the utility.
WARNING – The appliance can only be used indoors.
General
2.1 It is important these Installation and Maintenance Instructions are fully
adhered to.
2.2 Full details of the unit supplied are shown on the product nameplate. If
in doubt about any detail contact Elta or its agents for clarification.
2.3 All electrical installation must be carried out by suitably qualified and
competent personnel in accordance with all current statutory requirements.
2.4 These instructions cover only the Elta Ltd product and do not include the
supply or installation of any safety equipment that may be required e.g.
adequate guarding or protection from rotating parts and proper electrical
isolation.
2.5 Any declarations made by Elta Ltd about product installation and safety,
are dependent on the fan equipment being used within installations which
themselves meet the requirements of the relevant Standards and Directives of
your region.
2.6 The fan is designed for use in up to 95% relative humidity. The fan is not
suitable for corrosive or explosive atmospheres.
2.7 The installer should provide easy access to the fan to facilitate future
maintenance.
2.8 The installer should ensure the fan is adequately supported.
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children without supervision.
2.10 The below statement is only applicable to the non-European market.
2.9 The below statement is only applicable to the European market.
This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance.
2.11 Means for electrical disconnection must be incorporated in the wiring
installation in accordance with the relevant wiring and electrical
regulations.
WARNING -The fan must be isolated from the power supply during
installation and maintenance. The fan must be earthed in accordance with the
local regulations. The appliance can only be used indoors.
3.1 Refer to the appropriate wiring diagram. Ensure that all earth connections
are made.
3.2 The fan is to be installed so that the blades are more than 2.3m above the
floor (for fans intended to be mounted at high level).
3.3 Precaution must be taken to locate the exhaust discharge terminal so as to
avoid the backflow of gases into the room from the open flue of gas or other
fuel burning appliances.
Owner / installer: The life of this apparatus and its efficiency will be
increased if its use and maintenance is carried out in accordance with these
instructions and current statutory requirements. The installation and initial
adjustments should be carried out by a qualified and competent technician.
Elta Limited should be consulted before substituting or fitting parts from
another manufacturer. It is the responsibility of the installer to verify that
the installation is in accordance with the following standards and the owner
is given the current User’s Manual. Any modifications to the fan or its
installation, even the smallest modification, change or elimination of
security components or pieces that influence the efficiency or loss of
ventilation, will result in Elta’ warranty being cancelled.
Installation
4.1 Upon receipt, the fan equipment should be visually inspected to check for
any damage. Ensure that the impeller is free to rotate.
4.2 If there are any queries concerning the fan equipment, Elta should be
contacted prior to the installation.
4.3 Use the mounting bracket set supplied with the VL fan to fix the fan in
the desired position to suit the application. The fan can be mounted at any
angle. If the fan is mounted with vertical outlet, a weather proof cover must
be installed at the ducted outlet.
VL100, VL125 and VL150
Screw bracket side to fan using self tapping screws. (a) Mounting bracket set (supplied)
VL100, VL125 and VL150 2 off bracket sides.
Fixings set (supplied)
a. 4 off M4x8mm Phillips hexagon with pad flange head self tapping screws
Tool requirements (not supplied)
Phillips head point size #1 screw driver VL200, VL250 and VL315
Screw bracket side to fan using self tapping screws.
(a) Bolt the bracket support/spacer using the button head screws. Mounting bracket set (supplied)
VL200, VL250 and VL315 2 off bracket sides,
- off bracket support/spacer.
Fixings set (supplied)
a. 4 off M4x8mm Phillips hexagon with pad flange head self tapping screws
b. 4 off M4x15mm button head screws
c. 4 off M4 hexagon nuts
d. 4 off flat washers Tool requirements (not supplied)
Phillips head point size #1 screw driver 7mm Hexagon Socket Wrench or Spanner
Hand Tool 4.4 A minimum of 1 metre of duct at least the same diameter as the
fan spigots diameter is to be fitted to the fan inlet and discharge spigots.
Fans can be pushed directly into the duct and fastened. Make sure the ducting
system is not deformed or twisted. For mounting, we recommend using cushioned
fast clamps to reduce noise transmission into the ducting system. This
requires a tool for fixing.
4.5 Minimum 150mm clearance between the fan and the surrounding structure
should be reserved. See dimensional data section 7.
4.6 Unit is pre-fitted with mains lead and UK 3-pin plug for ease of
connection, for alternative connection refer to 4.7.
4.7 Each VL unit comes pre-fitted with an M20 cable gland, tightened to the
terminal box to 50N force. Suitable for receiving a HO5VV-F 3 x 0.5-1.5mm²
cable between 7mm minimum diameter and 10mm maximum diameter. Strip the cable
outer sheath exposing the individual cable cores. Leaving sufficient space for
the cables to be separated and fixed into the terminal strip connections.
Strip each individual core back 10mm, exposing the cable.Ensure the dome cap is tightened enough that the
cable is securely clamped and cannot move.
Tool requirments (not supplied)
24mm Spanner
Terminal screw driver
4.8 If the supply cord is damaged, it must be replaced by the manufacturer,
its service agent or similarly qualified persons in order to avoid hazards.
4.9 Check the details on the motor rating plate to ensure that the correct
power supply (voltage, frequency and phase) is available.
An incorrect power supply will lead to permanent damage to the fan motor.
Start-up
5.1 Before power is supplied to the unit, check that the wiring is correct as
per the fan connection diagram.
5.2 At initial start-up, check that impeller rotation and airflow direction is
correct.
5.3 Check that the motor amperage draw does not exceed the nameplate rating.
Fan Maintenance
6.1 Inspection of the fan at least once every 12 months is recommended to
ensure that the motor, fan blades, and supporting guards, are clean. Any build
up of dust and deposits on the blades or guards should be removed using a non-
abrasive cleaner.
6.2 All fastenings should be checked for tightness. In addition, all rotating
items should be checked.
6.3 Bearings are of the ‘sealed for life’ type and will not need a detailed
inspection.
General Sales
Code | Article No. | Supply | FL Amps | Watts | r/min |
---|---|---|---|---|---|
VL100 | 8000 | 220-240V/1Ph/50-60Hz | 0.14-0.13 | 26-25 | 2725-3150 |
VL125 | 8001 | 220-240V/1Ph/50-60Hz | 0.14-0.12 | 26-25 | 2690-3200 |
VL150 | 8002 | 220-240V/1Ph/50-60Hz | 0.28-0.36 | 65-84 | 2595-2858 |
VL200 | 8003 | 220-240V/1Ph/50-60Hz | 0.46-0.60 | 105-130 | 2565-2900 |
VL250 | 8004 | 220-240V/1Ph/50-60Hz | 0.48-0.57 | 106-130 | 2555-2950 |
VL315 | 8005 | 220-240V/1Ph/50-60Hz | 0.69-0.84 | 158-182 | 2190-2600 |
Dimensional Data
Product Code| A| B| C| D| E| F| G|
Weight kg
---|---|---|---|---|---|---|---|---
VL100| 98| 204| 130| 237| 284| 270| 47| 3.7
VL125| 123| 202| 130| 237| 284| 270| 47| 3.7
VL150| 148| 195| 165| 278| 326| 312| 47| 3.6
VL200| 198| 242| 190| 333| 392| 372| 100| 5.5
VL250| 248| 210| 190| 333| 392| 372| 100| 5.3
VL315| 313| 280| 227| 400| 460| 440| 100| 8.8
7.1 Minimum space required for installation Wiring
Unit is pre-wired with flying lead and UK 3-pin plug, where connection to
control devices (all units) or change of operating speed (Units 150-315) refer
to diagrams below.
8.1 VL100 – 125. 8.2 VL150 – 315. Guarantee
Elta or its agents will, within a period of one year from the date of
dispatch from their works, at its option, replace any goods, which are proven
to have defects as a result of defective materials or workmanship. The goods
must be inspected by a Elta official and if necessary returned, with a Returns
Note Number, carriage paid, for further examination.
535-IOM0082 Issue C
Hydor and Elta, are Companies and brands,
wholly owned by the Elta Group Limited
Te l +44 (0) 1384 275800
Email info@eltauk.com
eltauk.com