ELTA SSQUHT Slim Qube Instructions

May 15, 2024
elta

ELTA SSQUHT Slim Qube

ELTA-SSQUHT-Slim-Qube-product

Product Information

Specifications

  • Product Name: SLIM QUBE SSQUHT
  • Manufacturer: Elta-UK Ltd
  • Installation & Maintenance Instructions

Product Usage Instructions

Installation Instructions

General
Before starting the installation process, please ensure that the following instructions are fully adhered to:

  • Verify all details on the product nameplate.
  • Electrical installation should be carried out by qualified personnel in compliance with statutory requirements.
  • Ensure proper electrical isolation and guarding as necessary.
  • The installer should provide easy access and adequate support for the fan.

Installation
Follow these steps for proper installation:

  1. Visually inspect the fan upon receipt for any damage.
  2. Contact Elta-UK Ltd for any queries regarding the equipment.
  3. Securely mount the fan and adjust the panels for the desired position.
  4. Check the motor/fan rating plate for correct power supply details.
  5. Refer to the wiring diagram and ensure all earth connections are made.
  6. Incorporate means for electrical disconnection as per regulations.
  7. Locate the exhaust discharge terminal to prevent the backflow of gases.

Storage
Proper storage is essential for maintenance:

  • Store in a vibration-free, clean, and dry place.
  • Avoid extreme temperature variations during storage.
  • For prolonged storage, inspect electrical components and bearings if motor rotation ceases.

Frequently Asked Questions (FAQ)

  • Q: Is the product suitable for use by individuals with reduced capabilities?
    A: The product is not intended for use by individuals with reduced physical, sensory, or mental capabilities unless supervised by a responsible person.

  • Q: How should I dispose of the unit at end-of-life?
    A: The unit must be disposed of in an environmentally friendly manner by qualified personnel by applicable Standards and Directives.

  • Q: Can I customize the installation according to my needs?
    A: Yes, the SSQU fan range is designed with rearrangeable panels, providing flexibility for customization. Contact Elta for guidance if needed.

General Information

  • These Installation and Maintenance Instructions must be fully adhered to.
  • Full details of the unit supplied are shown on the product nameplate. If in doubt about any detail contact Elta-UK Ltd or its agents for clarification.
  • All electrical installations must be carried out by suitably qualified and competent personnel according to all current statutory requirements.
  • These instructions cover only the Elta-UK Ltd product and do not include the supply or installation of any safety equipment that may be required e.g. adequate guarding or protection from rotating parts and proper electrical isolation.
  • Any declarations made by Elta-UK Ltd about product installation and safety, are dependent on the fan equipment being used within installations which themselves meet the requirements of the relevant Standards and Directives of your region.
  • The fan is designed for use at an ambient temperature of -20°C up to +120°C.
  • The installer should provide easy access to the fan to facilitate future maintenance.
  • The installer should ensure the fan is adequately supported.
  • This product is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the product by a person responsible for their safety.
  • Children should be supervised to ensure that they do not play with the product
  • At end-of-life, the unit must be disposed of in an environmentally friendly manner by suitably qualified and competent personnel under the requirements of applicable Standards and Directives.

Installation

WARNING
The fan must be isolated from the power supply during installation and maintenance. The fan must be earthed by the local regulations.

  1. Upon receipt, the fan equipment should be visually inspected to check for any damage. Ensure that the impeller is free to rotate.
  2. If there are any queries concerning the fan equipment, Elta-UK Ltd should be contacted before the installation.
  3. The fan must be securely mounted and the panels adjusted to suit the desired position to suit the application.
  4. Check the details on the motor/fan rating plate to ensure that the correct power supply (voltage, frequency, and phase) is available. An incorrect power supply will lead to permanent damage to the motor.
  5. Refer to the appropriate wiring diagram. Ensure that all earth connections are made.
  6. This means that electrical disconnection must be incorporated into the wiring installation by the relevant wiring and electrical regulations.
  7. Precaution must be taken to locate the exhaust discharge terminal to avoid the backflow of gases into the room from the open flue of gas or other fuel-burning appliances.
  8. The SSQU fan range is designed with rearrangeable panels, providing you with the flexibility to customize the installation according to your specific needs. If in doubt, contact Elta.

Storage

  1. The storage place must be vibration-free, clean, dry, and not subject to extreme temperature variations.
  2. When storing for prolonged periods, whereby nonrotation of the motor occurs, we recommend electrical and bearing inspection, as they may have incurred damage or require possible re-lubrication.

WARNING
Elta-UK Ltd should be consulted in instances where speed controllers or inverter devices are to be used.

Start-Up

  1. Before power is supplied to the unit, check that the wiring is correct as per the fan connection diagram.
  2. At initial start-up, check that the impeller rotation and airflow direction are correct.
  3. Check that the motor amperage draw does not exceed the nameplate rating.

Fan Maintenance

  1. Inspection of the fan at least once every 12 months is recommended to ensure that the motor, fan blades, and supporting guards, are clean. Any build-up of dust and deposits on the blades or guards should be removed using a non-abrasive cleaner.
  2. All fastenings should be checked for tightness. In addition, all rotating items should be checked.
  3. Bearings are of the ‘sealed for life’ type and will not need a detailed inspection.
  4. The SSQU range has an easily removable panel arrangement fixed to Multi-thread “U” nuts, ideal for frequent cleaning.

WARNING
Fuses/circuit breakers are used to provide short-circuit protection only. A starter panel with overload protection should be used to protect the motor. Only a suitably qualified and competent person may carry out maintenance after the electrical supply has been isolated.

Table 1: Operational Maintenance

Activity Frequency
Inspect AV mounts for Corrosion or “Sag” 6 months
Check earth bonding 6 months

Dampers check rubber stops and grease (lithium-based) pivot points, by removing plastic caps| Yearly
Check fixings tightness and conditions of brass track and rivets| 26,000 hours / 3 years
Inspect and clean the impeller| 26,000 hours / 3 years
Remove dirt from motor cooling fins| 26,000 hours / 3 years
Check the operation of anti-condensation heaters| 26,000 hours / 3 years
Check for even tip clearance between the impeller and casing| 26,000 hours / 3 years
Check motor Amps| 26,000 hours / 3 years
Any corrosion – treat with suitable chemicals| 26,000 hours / 3 years
Check casing seals| 26,000 hours / 3 years

Table 2: Terminal Box Maintenance

Activity Frequency
Check that the lid seal is in place and not damaged Each time the enclosure

is opened
Check that lid fixing screws are in place and secured| Each time the enclosure is closed
Check that the mounting bolts are tight and free from corrosion| Annually
Check the security of all cable glands| Annually
Check that all screw clamps terminals are secure| Annually and each time the enclosure is opened
Check the enclosure for damage| Annually

Guarantee

Elta-UK Ltd will, free of charge, within 1 year from the date of dispatch from their works, repair or at its option replace any goods which are provided to have defects as a result of defective materials or workmanship. The goods MUST be returned to Elta Ltd carriage paid for examination.

Recycling

Elta uses components, when possible, that are suitable for recycling at the end of the product’s life, components can be segregated as stated below and processed by local regulations. Metallic items can be segregated and recycled; Electrical and Electronic equipment such as motors, cables,s and control devices can be segregated for WEEE recycling; Cardboard, wood, packaging, and plastic components can be widely recycled. Items not listed should be segregated by local authority zero waste hierarchy recommendations.

Wiring

WARNING
Correct rotation must be ensured as the Air flow direction will be correct even if the impeller is rotating in the wrong direction. Incorrect direction of rotation will result in lower air volumes, increased noise, and higher electrical current, which will harm the motor.

Please use the table(s) below to match up the product code and the wiring diagram number.

Single Phase 220V to 240V/50Hz

Page No.

|

Product Code

|

Wiring Diagram No.

---|---|---
5| SSQUHT50/350-4-3| 152-600
5| SSQUHT67/400-4-3| 152-600
5| SSQUHT67/500-4-3| 152-600
5| SSQUHT82/500-4-3| 152-600
5| SSQUHT82/560-4-3| 152-600
5| SSQUHT102/630-4-3| 152-600

Wiring Diagrams

ELTA-SSQUHT-Slim-Qube-fig-1 ELTA-SSQUHT-Slim-Qube-
fig-2

All wiring and control equipment must comply with the latest IEE regulations, in particular part 552-01-02/03.

  • MK-152-600 Issue B: 29.04.2015
  • Check the individual product accessories table for fan controller compatibility.