aldes 699674 InspirAIR TOP Centralized Air Purification User Manual
- May 15, 2024
- aldes
Table of Contents
InspirAIR® TOP
Installation Instructions
FOREWORD
FIND ALL INSPIRAIR® DOCUMENTS
Visit www.aldes-na.com to consult documents
concerning the InspirAIR® TOP product line.
Thank you for choosing an ALDES product. We recommend that you read this
document carefully and follow the instructions to ensure optimum operation of
your unit. We cannot be held liable as manufacturers for improper use, lack of
maintenance or improper installation. In order to constantly improve the
quality of its products, ALDES reserves the right to modify the
characteristics indicated in this document at any time.
SAFETY INSTRUCTIONS
2.1. General Instructions
Please read carefully before installation and start-up. Keep these
instructions for the life of the unit.
Precautions and restrictions of use :
– This appliance is intended exclusively for domestic use, to ensure air
renewal in a home as part of a Controlled Mechanical Ventilation system.
– Do not connect this unit to the exhaust of a chimney or appliances such as:
motorized hoods, air conditioning, heating, tumble dryers, gas boilers or any
other appliance discharging air or dust.
– Do not suck in hot air over 40°C, explosive vapors or air containing dust
particles.
– Do not use the device in the presence of flammable substances or vapors such
as alcohol, insecticides or gasoline.
– The manufacturer cannot be held responsible and declines all liability in
the event of damage to persons or property as a result of inappropriate use.
Personal safety :
– To avoid any risk of injury or damage to your unit, it is not recommended to
repair the electrical or mechanical components of your unit yourself.
The HRV or ERV must be installed and serviced by a CERTIFIED heating and air-
conditioning contractor.
– Children should be supervised to ensure that they do not play with the
device.
Installation and maintenance precautions :
– The unit must be installed in a room where the ambient temperature does not
exceed 60°C.
– The electrical connection must be made by a professional in accordance with
the local electrical code.
– In particular, a contact separation device with an opening distance of at
least 3 mm on each pole and a protection device with a suitable rated current
must be provided in the fixed wiring (circuit breaker). Copper conductor
cross-sections must be at least 1.5 mm².
– Prior to start-up, all conduits and the discharge must be connected.
– Conduits must be secured with screwed clamps, or with the clamps supplied
with the product.
– Precautions must be taken to prevent the backflow of gas from the exhaust
pipe of gas appliances or other open-fire appliances into the room.
– Switch off the power supply before any maintenance or cleaning operation,
and ensure that the unit cannot be switched on accidentally.
– For units fitted with a power cable, do not use extension cords, adapters or
multiple sockets.
– If the power cable is damaged, it must be replaced by the manufacturer, its
after-sales service or similarly qualified persons to avoid danger.
– If the problem persists, contact your installer or retailer.
– Use only original manufacturer’s spare parts.
End of product life :
**** If you have any problems, please contact your installer or dealer. This
product must not be disposed of with household waste. At the end of its life,
or when it is replaced, it must be handed over to a dealer or collection
center. ALDES is a member of the Eco Systemes ecoorganization
www.ecosystem.eco/
Product certifications :
Certificates of conformity with current standards are available from the
manufacturer.
For installation or maintenance problems, please contact your installer or
retailer.
2.2. Mechanical hazards
Always connect the air ducts to the control unit before connecting the power
supply. This ensures that it is impossible to touch the motors while the unit
is running.
2.3. Electrical hazards
The unit must not be switched on and left in the user’s use until the front
panel has been secured in place.
GENERAL INFORMATION
3.1. Technical Specifications
Weight and Dimensions
| InspirAIR ® **TOP
---|---
(P/N 699673)
A (inches)| 22 3/64
B (inches)| 22 3/64
C (inches)| 41 9/64
D (inches)| 42 53/64
E (inches)| 6 19/64
F (inches)| 12 19/32
G (inches)| 11 37/64
H (inches)| 12 23/32
I (inches)| 5 9/32
J (inches)| 4 23/32
K (inches)| 4 23/32
L (inches)| 5 33/64
M (inches)| 4 1/4
N (inches)| 13 37/64
kg (lb)**| 41 (90)
Electrical Data
Product Name| Power Supply| Max. Power| MCA|
MOP
---|---|---|---|---
InspirAIR ® **TOP (P/N 699673)**| 230V +/- 10% 50/60 Hz
+/- 10%| 350 W| 4 A| 15 A
3.2. List of Accessories Connectable to the Unit
The InspirAIR® TOP unit can be operated with various accessories connected to
its electronic board.
P/N| Product Name| Control| Power supply (see
section 4.8)
---|---|---|---
699674| InspirAIR® CO2 Control| Connected and powered by unit – control input
699850| InspirAIR® Control| Connected and powered by unit – control
INSTALLATION INSTRUCTIONS
4.1. Transport / unpacking
On receipt, check the condition of the product and make any necessary
reservations with the carrier on the delivery note. The standard delivery
includes:
– The unit and a wall-mounting system
– Documentation
– A connector to attach the drain to the unit (the drain is sold as an
accessory)
Remove product strapping. Lift the top cardboard cover.
Important: Do not handle the product by its openings.
Important: the product packaging must be recycled by the installer.
Permissible storage and transport temperatures are between -20°C and +60°C.
Transport and unpack the unit with care.
4.2. Product Environment
The product and ducts must be installed in a heated room to ensure optimum
thermal performance and to prevent condensation forming in areas designed for
proper drainage. The system must not be installed in a room where there is a
risk of explosion due to gas, fumes or dust.
Condensate must be drained (drain sold as accessory).
It is not recommended to install the unit in areas with high humidity.
Electrical installation must be adapted to the unit’s maximum power rating
(see point 3.2). Location and mounting must ensure minimum maintenance access.
4.3. Choice of A/B Version
By default, the product is delivered in configuration A
The installer must select configuration A to confirm that nothing has been
changed at start-up ( 1 ) .
To physically switch to configuration B :
The installer must tick configuration B to confirme the change.
– Reverse the 2 filters (see procedure and reference details § 6.1).
– Confirm this configuration using the remote control or Configurator
software.
4.4. Wall Mounting
Wall mounting is the recommended method for mounting the unit.
The wall plugs must be suitable for the supporting wall and sized to withstand
a load of 120 kg.
4.4.1. Mounting the Product
– Fix the mounting bracket to the wall ( 1 ) (the cardboard packaging includes
a template for drilling the wall to the correct dimensions).
– Hang the product on the bracket ( 1 + 2).
– Check that the product is stable and horizontal.
– Use the mounting bracket supplied with the product to secure it in place.
Use a wall plug (not supplied) ( 3 ).
4.5. Installation on Feet (Accessory)
The unit can be installed on the floor using an accessory floor stand. The
unit must be accessible for maintenance.
– Assemble the stand according to the instructions supplied.
– Check that the unit is securely supported by the feet.
– Refer to the instructions supplied with the accessory for further details.
4.6. Connecting Ventilation Ducts from the Unit
To ensure optimum sound levels, we recommend a straight duct length of at
least 50 cm at the unit outlet. Elbows are not recommended.
4.7. Electrical Connections
Connect the unit to the connector under the electrical box, using a cable
directly connected to the installation’s electrical panel.
Mains: 230 V single-phase alternating current. Characteristics and
installation requirements for power cable (not supplied).
– Cable cross-section: 3 x 1.5 mm2 minimum (maximum 2.5 mm 2 with insulated
end ferrule or 4 mm2).
– The ground wire must be longer than the others (the last wire to be
disconnected in the event of a pull).
Stripping length: 10 mm.
The installer must check that the wires are correctly inserted into the
connector each time.
The installation will include :
– A two-pole circuit breaker
Connection to the terminal block installed on the product. Be sure to observe
the connections and polarities marked on the connector.
4.8. Electronic Connections
View of electronic board customer connections :
START-UP / SETTINGS
5.1. Getting Started
The product must be set up via one of these two interfaces:
– Aldes InspirAIR® control unit
– Aldes Configurator software
Please refer to the documentation for these components.
The unit will not operate if start-up is not successfully completed.
5.2. InspirAIR® TOP and InspirAIR® TOP CO2 Control Unit Menu Structure
The INFORMATION menu is accessible without a password. It displays the unit’s
key parameters without being able to modify them. It enables the installer to
familiarize himself with the unit’s characteristics and operation. The user
can easily use it to remotely communicate elements to the installer if the
unit does not seem to be operating correctly, and to perform an initial remote
diagnosis.
INFORMATION| Settings| Display key unit settings without being able to modify
them:
– type of regulation – time delay – filter type
– current speed – comfort temperature
---|---|---
Filter Alert| Display but cannot change:
– filter type
– filter status (timer elapsed or not)
– number of days remaining
Error| Display error code(s) activated by the unit
Product ID| Display but cannot modify :
– unit item number
– unit serial number
– unit and remote control software number
Connectivity| Display which accessory is connected to the unit and confirm its
operating status:
– remote controls (if CO2, PPM display)
The USER menu is dedicated to the user and accessible without a password. It allows you to adjust your ventilation on a daily basis and launch simple actions.
USER | Languages | Select language |
---|---|---|
Date and time | Set date and time if using time programming | |
Signal light | Select unit beat on Premium unit: |
– color change according to air quality
– beats in rhythm with fan speed
– off
Filters| Select duration and reset filter timer
Programming| Start rapid programming of ventilation in the home
Sensors| Activate or deactivate, temporarily or permanently, indoor air
quality control for automatic ventilation operation.
Open fireplace| Activate overpressure ventilation for 2 hours to make it
easier to light a fire in an open fireplace.
The INSTALLER menu is reserved for competent installers and can be accessed
with password 0405. It provides access to all machine settings, accessories,
operating and maintenance data.
First start-up: When starting up the unit for the first time, use of the
wizard is mandatory. The unit will not start if each step has been validated
by the installer, at least until the flow wizard has been completed.
First start-up: When starting up the unit for the first time, use of the wizard is mandatory. The unit will not start up unless each step has been validated by the installer, at least until the flow wizard has been completed.
| Element| Function
---|---|---
INSTALLER| Language| Customize remote control language for user and installer.
Installation Country| Allows the unit to adapt the menu to the country in
question. Some functions (flow assistant, fire-dam- pers, etc.) are specific
to certain countries only.
Orientation| Allows you to set the unit’s orientation. If the unit remains in
A, no action is required.
Config A| Config B| Allows you to set the unit’s orientation. If unit remains
in A, no action required.
↓
| Lettre B ok| If change to B, tick letter B
Reverse filter| If in B, reverse filters
Electric Coil| NO (accessory not available in North America)
Condensate connection| Confirms that the condensate connection has been made.
Regulation Mode| Selects the unit’s control mode (see details on next page)
Flow Assistant| Allows you to set the value of each ventilation level (L0-
Vacation / L1- Daily / L2-Pushbutton / L3- Boost)
Connectivity Assistant| Allows you to set the presence of specific
accessories. Optional menu
Detailed Menus
Menu | Description |
---|---|
Start-up | Allows you to restart the start-up wizard, as was done when the unit |
was first started up.
This is not a factory reset: values already entered will be proposed again. To
perform a factory reset, use the dedicated function.
Settings
Language| Customize the remote control language for the user and installer.
Installation Country| Allows the unit to adapt the menu to the country in
question. Some functions (flow assistant, fire-dampers, are specific to
certain countries only).
Mode Regulation| Allows selection of product control mode:
-In France, only constant flow is possible. Outside France, constant speed is also standard
-For constant pressure, a change of card is mandatory “constant pressure card kit”.
Configuration Level| Allows you to set each of the 4 ventilation levels:
L0-Vacation / L1-Daily / L2-Pushbutton / L3-Boost. This setting, available for
countries outside France, is in m3/h or in %, or in pa depending on the
control system.
Housing Type| Based on the home’s characteristics, the unit automatically sets
the flow rates for each ventilation level. This wizard is not available
outside France.
Imbalance| Used to adjust an imbalance between air supply and air discharge.
This single % value will apply to all fan speeds. This setting is only
available in “self-adjusting” and “constant pressure” control modes.
Radon Mode| Allows rapid adjustment of a 15% favorable imbalance between air
supply and exhaust, permanently and for all speeds, based on ventilation
recommendations for Radon risk. This action can only be activated in constant
flow control mode.
Open Fireplace| Enables the user, via the remote control menu, to initiate an
imbalance of +15% in air supply compared to exhaust air for 2 hours, the time
it takes for an open fireplace to burn at its best.
Timer Filters| Allows you to adjust the duration of the filter timer according
to the characteristics of the dwelling, location or occupant’s needs: Possible
values: from 6 to 12 months.
Units| Customize units C°, m3/h, etc…
T° Comfort| Allows you to set the air supply temperature between 16 and 23
degrees, when an electric coil is installed.
Certifications| Allows you to specify the type of dwelling and its possible
PassivHaus certification. If so, the unit will adapt its defrosting strategy
accordingly (no single insufflation motor cut-off allowed).
Aldes recommends the “Non Passiv Haus” configuration if possible.
Factory Reset| Resets the unit to factory settings. A new start up will be
necessary.
Quick Adjustment| Allows correction of flow rates measured at vents by up to
10%. It is only available for the “self-adjusting” mode and the L1 and L2
speeds.
Connectivity
Sensors| Used to set parameters for various 0-10V sensors (see diagram)
Dry Contact| Used to set the status of the unit’s dry contact. Factory
setting: NO (Normally Open). Alternative value: NC (Normally Closed).
Maintenance
Real Values| Allows you to examine in real time the various key values of the
unit in operation: (flow setpoints, motor voltages, probe temperatures, etc.)
for rapid maintenance diagnostics.
Demo Signal| Launches a demonstration phase of the different light signal
colors (for InspirAIR TOP Premium only). Leaving this menu stops the
demonstration.
5.3. Diagram
0-10 V sensor control
5.4. Unit Software Update from USB Key
To update the software, follow the steps below:
- Stop the product (switch it off) [Open the metal trunking].
- Insert USB key into USB port
- Switch the product back on
- Wait until the LED is green, or approx. 30s for the classic unit
- Remove USB key
The USB key should contain only the update file supplied by Aldes.
The latest software versions available for the InspirAIR® Top range can be
found at: https://inspirair-top-software.aldes.com/fr/
5.5. Bypass Function
The bypass is controlled 100% automatically by the unit according to the
season that is registered by the unit.
Seasonal registration
The unit registers the on-going season (summer or winter) by checking the
outside air temperature every hour every day.
– If the average of T is > 19°C or if T max. is > 28°C and T min. > 7°, we are
in summer.
– If the average T is < 19°C, or if T max. is < 28°C, we are in winter.
The season is registered 24 hours after starting the unit.
According to the season, the unit will give priority to heating the air in the
heating element in winter or cooling the air in summer:
MAINTENANCE
6.1. Filter Replacement
Filters should be changed regularly, depending on the unit’s operating
conditions and environment. The filter counter can be set by the user and
installer from 6 to 12 months.
Filter References
P/N| Product Name| For Configuration A| For
Configuration B
---|---|---|---
Left| Right| Left| Right
699678*| Pollen Filter MERV 8| Standard Top 450| | | Standard Top 450
Particle filter MERV 10| | Right only| Left only|
699675| Fine Particle Filter MERV 13| | Right only| Left only|
699676| Bacteria filter MERV 15| | Right only| Left only|
699677| VOC filter MERV 13 with active chacoal| | Right only| Left only*|
*These filters, sold as accessories, include a pre-filter to be placed on top of the filter, to guarantee its lifespan and efficiency.
**Filters MERV 8 and MERV 10 are sold together in a kit (1 unit of each).
6.2. Cleaning the Recovery Core
Maintenance of the recovery core is recommended every two years according to
the following procedure:
Replace the heat exchanger cap, then the front door and finally the filter cap (steps 1 to 5).
6.3. Maintenance
- Do not attempt to repair the unit yourself.
- This device contains no user-serviceable parts.
- Removing one of the covers may expose you to dangerous electrical voltages.
- Switching off the power supply is not sufficient to protect you from electric shocks (capacitors).
- If you notice any abnormal noises, odors or smoke coming from the unit, disconnect the power supply and contact your installer.
- Before cleaning, disconnect the unit from the power supply.
- Do not use strong cleaning fluids or solvents to clean the unit.
- Do not use a pressure washer to clean the air vents. You risk damaging the recovery core and allowing water to enter the electrical circuits.
6.4. Error Codes
# | Diagnostic | Solution |
---|---|---|
49 | Product ID Missing | Enter product ID |
50 | Product Not Configured | Check that product has been start-up for the first |
time
53| Pressure Sensor Fault| Replace card and pressure sensor
70| Dry Contact Activated| Check dry contact status
72| HR Sensor Fault| If the product is not equipped with an RH sensor,
deactivate the entry in the installer menu:
Installer > Connectivity > HR sensor > Deactivate. If the product is equipped
with a faulty sensor, replace the sensor.
74| Loss of Communication Between Remote Control and Product| Check remote
control characteristics and correct connection. Disconnect the remote control,
disconnect the unit, then reconnect the remote control and the unit.
76| Remote Control CO2 Sensor Fault| Check if its value is out of line with
the situation. If so, replace remote control.
81| No External Preheater Detected| Check Ibus port wiring.
83| External Preheat Resistor Does Not Heat Up| Check that sensor temperature
values are consistent and within defrost strategy values.
84| Internal Preheat Coil Connected to Wrong Air Supply| Reinstall internal
coil on correct side.
85| Post-heating Battery Operation| Check wiring of post-heating coil and
temperature sensor.
90| Test Fire Damper KO| Check that the number of fire dampers is set to 0 in
the remote control menu, if you have not connected any.
91| Fire Damper Tripped| Check that the number of fire dampers is set to 0 in
the remote control menu, if you have not connected any.
92| Fire damper communication failure| Check that the number of fire dampers
is set to 0 in the remote control menu, if you have not connected any.
182| Motor-fan Error Exhaust Disconnected or Motor Out of Order| – Switch off
the power supply for 30 minutes, then switch it on again.
– Check motor wiring
– Change motors
183| Motor-fan Air Supply Error Disconnected or Motor Out of Order
239| Exhaust Air T° Sensor Fault (Tr)| – Check sensor location
– Replace temperature sensors
240| Outdoor T° Sensor Fault (Te)
241| Air supply T° Sensor Fault (Ti)
243| External Coil T° Fault
251| VMC Temperature Sensor T° (Tv)
All these error numbers disappear once the fault has been rectified. In the
event of a problem, please consult your dealer.
6.5. Spare Parts List
Please refer to Aldes: Guide SAV InspirAIR® Top NA.
WARRANTY
7.1. General Warranty Conditions
Please refer to the general sales conditions on www.aldes-na.com. The system must be installed by a qualified professional in
accordance with good practice, current standards and our instructions. The
system must be operated normally and regularly maintained by a specialist.
7.2. Warranty Period
The product is covered by a 2-year parts warranty (excluding labor). The
warranty takes effect on the date of purchase of the product, as evidenced by
the invoice.
7.3. Warranty Exclusions
This warranty does not cover any installation failure resulting from non-
compliance with the manufacturer’s recommendations, including lack of
drainage, non- compliance with current standards and regulations, or lack of
maintenance.
7.4. After-Sales Service
**** In the event of a problem, please contact your installer or dealer. This
product must not be disposed of with household waste.
At the end of its life or when it is replaced, it must be handed over to a
dealer or collection center.
ETATS-UNIS
Need after sales technical support?
Visit our website for more information: www.aldes-na.com
CANADA
Need after sales technical support?
Visit our website for more information: www.aldes-na.com
For more information, contact your Aldes sales advisor, visit aldes-
na.com, call 1.800.255.7749, or find us on
©2024 Aldes North America. InspirAIR TOP IOM. Aldes reserves the right to
modify its products at any time to introduce new technologies.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>